1 NRR-PMDAPEm Resource From:

Minarik, Anthony Sent:

Thursday, May 14, 2015 11:25 AM To:

Bryan, Robert H Jr (rhbryan@tva.gov)

Cc:

Park, Sunwoo; Lupold, Timothy

Subject:

Containment ISI Request for Alternative RAI's (MF6154)

Attachments:

WBN-2 RAI-1 RfA CISI (MF6154) FINAL.pdf Mr. Bryan:

Please see the attached questions from the NRC related to TVA's March 17, 2015 request for alternative regarding the containment in-service inspection program for the Watts Bar Nuclear Plant, Unit 2.

TVA expressed that they understood the questions as presented here, and will provide their responses by June 15, 2015.

Anthony Minarik 301-415-6185 Office of Nuclear Reactor Regulation (NRR)

Division of Operating Reactor Licensing (DORL)

Watts Bar Special Projects Branch (LPWB)

Normal Hours:

0600-1545: Mon-Fri

Hearing Identifier:

NRR_PMDA Email Number:

2070 Mail Envelope Properties (Anthony.Minarik@nrc.gov20150514112500)

Subject:

Containment ISI Request for Alternative RAI's (MF6154)

Sent Date:

5/14/2015 11:25:15 AM Received Date:

5/14/2015 11:25:00 AM From:

Minarik, Anthony Created By:

Anthony.Minarik@nrc.gov Recipients:

"Park, Sunwoo" <Sunwoo.Park@nrc.gov>

Tracking Status: None "Lupold, Timothy" <Timothy.Lupold@nrc.gov>

Tracking Status: None "Bryan, Robert H Jr (rhbryan@tva.gov)" <rhbryan@tva.gov>

Tracking Status: None Post Office:

Files Size Date & Time MESSAGE 562 5/14/2015 11:25:00 AM WBN-2 RAI-1 RfA CISI (MF6154) FINAL.pdf 56118 Options Priority:

Standard Return Notification:

No Reply Requested:

No Sensitivity:

Normal Expiration Date:

Recipients Received:

REQUEST FOR ADDITIONAL INFORMATION REQUEST FOR ALTERNATE ASME CODE SECTION XI FOR CONTAINMENT INSERVICE INSPECTION UTILIZING ASME CODE SCTION XI, 2007-2008 TENNESSEE VALLEY AUTHORITY WATTS BAR NUCLEAR PLANT, UNIT 2 DOCKET NUMBER 50-391 By letter dated March 17, 2015, Tennessee Valley Authority, submitted a request to use an alternative Edition and Addenda of American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code Section XI for the Watts Bar Nuclear Plant (WBN) Unit 2 Containment lnservice Inspection (CISI) Program. The CISI Program applicable to WBN Unit 2 is the ASME Code Class MC (Metallic Containment) components for the initial 120-month inspection interval. The proposed alternative requests the use of the 2007 Edition with 2008 Addenda of ASME Code Section XI per 10 CFR 50.55a(b)(2) as conditioned by 10 CFR 50.55a(b)(2)(ix) on the date 12 months prior to Full-Power Licensing of WBN Unit 2.

The NRC staff requests the following additional information for its detailed safety evaluation.

1. In the cover page and in Executive Summary Section of the Enclosure the licensee characterized its request, as one seeking authorization to use an alternative to the codes and standards requirements pursuant to 10 CFR 50.55a(z)(1). However, in Basis For Alternative Section of the Enclosure, the licensee appears to invoke 10 CFR 50.55a(g)(4)(iv) as a regulatory basis for the request. It is to be noted that a request for authorization to use an alternative to the regulatory requirements pursuant to 10 CFR 50.55a(z)(1) is differentiated from a request for approval to use a subsequent Code edition and addenda incorporated by reference pursuant to 10 CFR 50.55a(g)(4)(iv).

Please clarify and revise the request as needed.

2. In the cover page of the letter, the licensee states that the proposed alternative requests the use of the 2007 Edition with 2008 Addenda of ASME Code Section XI. Whereas, in the Enclosure, the licensee states that the proposed alternative is to utilize the latest-approved Edition and Addenda of ASME Code Section XI on the date 12 months prior to full-power licensing of WBN Unit 2. It is to be noted that the NRC may review and authorize the use of a singly designated Edition and Addenda and therefore the licensee is requested to provide clarity in this regard.
3. In several places in the Enclosure of its letter, the licensee made a reference to 10 CFR 50.55a(b)(2) which is believed to mean 10 CFR 50.55a(a)(1)(ii) in the newest version of 10 CFR 50.55a Section. Please clarify and correct accordingly.