ML15120A135

From kanterella
Jump to navigation Jump to search
Shine Medical Technologies V. 0 - Chapter 08 - Figure 8a2.1-001
ML15120A135
Person / Time
Site: SHINE Medical Technologies
Issue date: 04/10/2015
From: Bynum R
Shine Medical Technologies
To:
Office of Nuclear Reactor Regulation
Lynch S
References
SHINE, SHINE.SUBMISSION.12, SHN.PSAR.P, SHN.PSAR.P.5
Download: ML15120A135 (1)


Text

Chapter 8 - Electrical Power Systems Normal Electrical Power Systems Figure 8a2.1 One-Line Diagram - Normal Electrical Power Supply System 12kV UTILITY FEEDER 12kV UTILITY FEEDER 12kV-480Y/277V 12kV-480Y/277V 2000 kVA 2000 kVA 3PH 3PH TRANSFORMER TRANSFORMER OUTDOOR TYPE OUTDOOR TYPE M M FIRE PUMP CABLE BUS CABLE BUS CONTROLLER BOX (NOTE 7)

OUTDOOR OUTDOOR UTILITY INTERFACE UTILITY INTERFACE 200 HP FIRE PUMP FIRE PUMP ROOM (LOCATED OUTSIDE FACILITY)

FACILITY 480V AC PLANT SWGR A FACILITY 480V AC PLANT SWGR B NC NC NOTE 3 NOTE 3 480V-208Y/120V 480V-208Y/120V 75 kVA 75 kVA 3PH 3PH TO 480V AC 100 200 200 100 TO 480V AC 200 200 125 125 TO 480V AC TO 480V AC MCC A1 HP 208Y/120V HP HP HP MCC A2 208Y/120V HP HP HP HP MCC B1 MCC B2 200A 200A ZONE 2 CHILLER 1 CHILLER 2 ZONE 2 CHILLER 3 CHILLER 4 ZONE 1 ZONE 1 3PH, 4W 3PH, 4W EXHAUST EXHAUST EXHAUST EXHAUST FAN B FAN A FAN B FAN A (STANDBY) DISTRIBUTION DISTRIBUTION (STANDBY)

PANEL PANEL FOR TCAP FOR TCAP 1, 2, 3 & 4 5, 6, 7 & 8 NC NC NO NO FACILITY 480V AC SDG BUS A AT SWGR ROOM FACILITY 480V AC SDG BUS B AT SWGR ROOM NC NC NC NC NO NC NC NC NC NOTES:

1. BREAKERS DROP OUT (TRIP) ON LOSS OF POWER TO THE BUS AND CAN BE MANUALLY CLOSED SELECTIVELY AFTER SDG RESTORES POWER TO THE BUSES.
2. SDG AND AUTOMATIC TRANSFER EQUIPMENT LOCATED IN SEPARATE BUILDING.
3. RESPECTIVE 480V AC SWGR BUS A OR B POWERS THE SDG BUSES DURING NORMAL OPERATION. ON LOSS OF OFF-SITE POWER, BOTH AC SWGR A AND B WILL BE CONNECTED AS NEEDED.
4. ON LOSS OF OFF-SITE POWER SDG WILL START. AFTER RATED VOLTAGE AND FREQUENCY ARE ESTABLISHED AT THE SDG BUS, BREAKER FEEDS TO OTHER FACILITY LOADS WILL BE MANUALLY CONNECTED AS NEEDED.
5. LOAD BREAKERS EQUIPPED WITH SOFT STARTERS.
6. SDG - STANDBY DIESEL GENERATOR NOTE 4 TO 480V AC BATTERY EMERGENCY UPS VOLTAGE EMERGENCY BATTERY UPS VOLTAGE TO 480V AC 7. FIRE PUMP CONTROLLER BOX PER NFPA 20 AND IS LOCATED IN SIGHT OF FIRE NO NO OUTDOOR SDG MCC A CHARGER A LIGHTING REGULATING LIGHTING CHARGER B REGULATING SDG MCC B PUMP ROOM.

LOAD BANK PANEL XFMR FOR SDG PANEL XFMR ASSEMBLY A NO ASSEMBLY B TESTING PLUG-IN PORTABLE SDG DG FROM 480V AC 480V SUPPLY SDG MCC A LATER kW 3PH, 4W LOCATED IN SDG BUILDING SHINE Medical Technologies Rev. 0