1 NRR-PMDAPEm Resource From:

Dion, Jeanne Sent:

Tuesday, March 24, 2015 11:35 AM To:

rhbryan@tva.gov; Arent, Gordon <garent@tva.gov> (garent@tva.gov)

Cc:

Minarik, Anthony

Subject:

Watts Bar EMCB RAI - Lehman (3).docx Attachments:

Watts Bar EMCB RAI - Lehman (3).docx Bob, Please see the attached draft RAIs for the GSI-191 call. Im working on finding some dates for the clarification call. Please keep Anthony on cc.

Jeanne Dion Project Manager Watts Bar Special Projects Branch Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation 301-415-1349

Hearing Identifier:

NRR_PMDA Email Number:

1944 Mail Envelope Properties (0B8884532E5C074E972B443F6E8F592E7DE601D614)

Subject:

Watts Bar EMCB RAI - Lehman (3).docx Sent Date:

3/24/2015 11:35:05 AM Received Date:

3/24/2015 11:35:00 AM From:

Dion, Jeanne Created By:

Jeanne.Dion@nrc.gov Recipients:

"Minarik, Anthony" <Anthony.Minarik@nrc.gov>

Tracking Status: None "rhbryan@tva.gov" <rhbryan@tva.gov>

Tracking Status: None "Arent, Gordon <garent@tva.gov> (garent@tva.gov)" <garent@tva.gov>

Tracking Status: None Post Office:

HQCLSTR01.nrc.gov Files Size Date & Time MESSAGE 346 3/24/2015 11:35:00 AM Watts Bar EMCB RAI - Lehman (3).docx 28367 Options Priority:

Standard Return Notification:

No Reply Requested:

No Sensitivity:

Normal Expiration Date:

Recipients Received:

References:

1. Enclosure to Letter From William H. Ruland, Director, Division of Safety Systems, Office of Nuclear Reactor Regulation, U. S. Nuclear Regulatory Commission, to Anthony Pietrangelo, Vice President, Regulatory Affairs, Nuclear Energy Institute, Revised Content Guide for Generic Letter 2004-02 Supplemental Responses. November 21, 2007. (ML073110389)
2. Enclosure 1 to Letter from Michael K. Brandon, Tennessee Valley Authority, to NRC Document Control Desk, Watts Bar Nuclear Plant (WBN) Unit 1 - Supplemental Response to Nuclear Regulatory Commission Generic Letter 2004-02 (TAC No.

MC4730) dated March31, 2008. (ADAMS Accession No.: ML081090501)

3. Letter R. M. Krich, Vice President Nuclear Licensing, Tennessee Valley Authority, to NRC Document Control Desk, Response to Requests for Additional Information Related to NRC Generic Letter 2004-02, August 15, 2011. (ADAMS Accession No.:

ML112291047)

Mechanical and Civil Engineering Branch (EMCB)

Watts Bar GL 2004 EMCB RAI-1 In Reference 2, the licensee summarizes the design inputs and structural qualification for the WBN sump strainers. In that submittal, the licensee notes the strainer is designed for a differential pressure of 3.5 feet of water. In the Strainer Structural Qualification section of of Reference 3, the licensee states that the strainer is qualified using an input pressure load of 6.0 feet and that the most limiting component of the strainer will remain qualified up to 6.5 feet. However, no updated supporting information (such as design inputs and interaction ratios) are provided to support this updated pressure value.

Provide an updated response to items 3.k.1 and 3.k.2 from Reference 1 that reflects the updated pressure value, or explain why the previously submitted information remains valid for the new pressure value.