MONTHYEAR2CAN031303, License Amendment Request - Adoption of Technical Specification Task Force (TSTF)-422, Revision 2 Change in Technical Specifications End States (CE NPSD-1186)2013-03-26026 March 2013 License Amendment Request - Adoption of Technical Specification Task Force (TSTF)-422, Revision 2 Change in Technical Specifications End States (CE NPSD-1186) Project stage: Request 1CAN031306, License Amendment Request, Adoption of Technical Specification Task Force (TSTF)-431, Revision 3 Change in Technical Specifications End States (BAW-2441)2013-03-26026 March 2013 License Amendment Request, Adoption of Technical Specification Task Force (TSTF)-431, Revision 3 Change in Technical Specifications End States (BAW-2441) Project stage: Request ML13182A3332013-07-0101 July 2013 Acceptance Review Email, License Amendment Request to Adopt Technical Specification Task Force (TSTF)-422, Revision 2 Change in Technical Specifications End States (CE NPSD-1186) Project stage: Acceptance Review 1CAN111302, Response to Request for Additional Information ANO-1 Adoption of TSTF-431, Revision 3, Change in Technical Specifications End States (BAW-2441)2013-11-14014 November 2013 Response to Request for Additional Information ANO-1 Adoption of TSTF-431, Revision 3, Change in Technical Specifications End States (BAW-2441) Project stage: Response to RAI ML13326A3452013-11-22022 November 2013 NRR E-mail Capture - RAI Related to the Adoption of (TSTF)-422, Revision 2 Project stage: RAI 2CAN121303, Response to Request for Additional Information Adoption of Technical Specification Task Force (TSTF)-4222013-12-12012 December 2013 Response to Request for Additional Information Adoption of Technical Specification Task Force (TSTF)-422 Project stage: Response to RAI ML14209A6272014-08-0404 August 2014 Request for Additional Information, Requests to Adopt Technical Specifications Task Force (TSTF)-431, Revision 3, for Unit 1 and TSTF-422, Revision 2 for Unit 2, Change in Technical Specifications End States. Project stage: RAI 0CAN081407, Response to Request for Additional Information Adoption of Technical Specification Task Force TSTF-431, Revision 3 and Adoption of TSTF-422, Revision 2 Regarding Technical Specifications End States2014-08-19019 August 2014 Response to Request for Additional Information Adoption of Technical Specification Task Force TSTF-431, Revision 3 and Adoption of TSTF-422, Revision 2 Regarding Technical Specifications End States Project stage: Response to RAI 2CAN101401, Arkansas, Unit 2 - License Amendment Request Supplemental Adoption of Technical Specification Task Force (TSTF)-422, Revision 2, Change in Technical Specifications End States (CE NPSD-1186)2014-10-22022 October 2014 Arkansas, Unit 2 - License Amendment Request Supplemental Adoption of Technical Specification Task Force (TSTF)-422, Revision 2, Change in Technical Specifications End States (CE NPSD-1186) Project stage: Supplement 2CAN121403, License Amendment Request Supplemental Adoption of Technical Specification Task Force (TSTF)-422, Revision 2, Change in Technical Specifications End States (CE NPSD-1186).2014-12-0505 December 2014 License Amendment Request Supplemental Adoption of Technical Specification Task Force (TSTF)-422, Revision 2, Change in Technical Specifications End States (CE NPSD-1186). Project stage: Supplement ML15068A3192015-03-31031 March 2015 Issuance of Amendment No. 301, Request to Adopt Technical Specification Task Force (TSTF)-422, Revision 2, Change in Technical Specifications End States (CE NPSD-1186) Project stage: Approval 2013-07-01
[Table View] |
|
---|
Category:Letter type:
MONTHYEAR2CAN012401, U.S. Additional Protocol2024-01-17017 January 2024 U.S. Additional Protocol 2CAN012403, Supplemental Information - Adopt Risk-Informed Completion Times TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative 42024-01-11011 January 2024 Supplemental Information - Adopt Risk-Informed Completion Times TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative 4 0CAN012401, Registration of Cask Use2024-01-10010 January 2024 Registration of Cask Use 1CAN122301, Responses to Request for Additional Information for Request for Alternative for Implementation of Extended Reactor Vessel Inservice Inspection Interval (ANO1-ISl-037)2023-12-14014 December 2023 Responses to Request for Additional Information for Request for Alternative for Implementation of Extended Reactor Vessel Inservice Inspection Interval (ANO1-ISl-037) 2CAN112302, Submittal of Amendment 31 to Safety Analysis Report2023-11-16016 November 2023 Submittal of Amendment 31 to Safety Analysis Report 0CAN102303, Registration of Cask Use2023-10-24024 October 2023 Registration of Cask Use 0CAN102302, (ANO) Emergency Plan Revision 49 and Emergency Plan On-Shift Staffing Analysis Revision 32023-10-11011 October 2023 (ANO) Emergency Plan Revision 49 and Emergency Plan On-Shift Staffing Analysis Revision 3 0CAN102301, Evacuation Time Estimate (ETE) Study2023-10-0404 October 2023 Evacuation Time Estimate (ETE) Study 1CAN092301, Supplemental Information - Adopt Risk-Informed Completion Times TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative 42023-09-21021 September 2023 Supplemental Information - Adopt Risk-Informed Completion Times TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative 4 0CAN092302, Supplement to Request for Alternative Frequency to Containment Unbonded Post-Tensioning System Inservice Inspection (ANO-CISI-002)2023-09-14014 September 2023 Supplement to Request for Alternative Frequency to Containment Unbonded Post-Tensioning System Inservice Inspection (ANO-CISI-002) 2CAN092301, Reply to a Notice of Violation2023-09-0808 September 2023 Reply to a Notice of Violation 0CAN092301, Emergency Plan Implementing Procedure Revision2023-09-0505 September 2023 Emergency Plan Implementing Procedure Revision 0CAN082301, Units 1 and 2 - Changes to the Quality Assurance Program Approval Form for Radioactive Material Package No. 03412023-08-17017 August 2023 Units 1 and 2 - Changes to the Quality Assurance Program Approval Form for Radioactive Material Package No. 0341 2CAN082301, Inservice Inspection Summary Report for the Arkansas Nuclear One, Unit 2, Twenty-Ninth Refueling Outage (2R29)2023-08-10010 August 2023 Inservice Inspection Summary Report for the Arkansas Nuclear One, Unit 2, Twenty-Ninth Refueling Outage (2R29) 0CAN072301, Registration of Cask Use2023-07-18018 July 2023 Registration of Cask Use 1CAN062304, Supplement Related to License Amendment Request to Remove Technical Specification Condition Allowing Two Reactor Coolant Pump Operation2023-06-29029 June 2023 Supplement Related to License Amendment Request to Remove Technical Specification Condition Allowing Two Reactor Coolant Pump Operation 0CAN062301, Status of Actions to Return to Compliance2023-06-26026 June 2023 Status of Actions to Return to Compliance 0CAN062302, Submittal of Revision 22 of the ANO Fire Hazards Analysis2023-06-20020 June 2023 Submittal of Revision 22 of the ANO Fire Hazards Analysis 1CAN062301, Request for Alternative for Implementation of Extended Reactor Vessel Inservice Inspection Interval (ANO1-ISI-037)2023-06-0808 June 2023 Request for Alternative for Implementation of Extended Reactor Vessel Inservice Inspection Interval (ANO1-ISI-037) 0CAN052303, Annual 10 CFR 50.46 Report for Calendar Year 20222023-05-24024 May 2023 Annual 10 CFR 50.46 Report for Calendar Year 2022 0CAN052302, Emergency Plan Rev. 482023-05-11011 May 2023 Emergency Plan Rev. 48 0CAN052301, Units 1 and 2 - Annual Radiological Environmental Operating Report for 20222023-05-0909 May 2023 Units 1 and 2 - Annual Radiological Environmental Operating Report for 2022 2CAN052301, Cycle 30 Core Operating Limits Report (COLR)2023-05-0303 May 2023 Cycle 30 Core Operating Limits Report (COLR) 0CAN042302, Annual Occupational Radiation Exposure Report for 20222023-04-27027 April 2023 Annual Occupational Radiation Exposure Report for 2022 0CAN042301, Radioactive Effluent Release Report for 20222023-04-14014 April 2023 Radioactive Effluent Release Report for 2022 2CAN042301, License Amendment Request to Revise Technical Specifications to Adopt Risk-Informed Completion Times TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative 42023-04-0505 April 2023 License Amendment Request to Revise Technical Specifications to Adopt Risk-Informed Completion Times TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative 4 1CAN032301, License Amendment Request to Modify the Arkansas Nuclear One, Unit 1, Technical Specification 3.3.1, Reactor Protection System Instrumentation, Turbine Trip Function on Low Control Oil Pressure2023-03-30030 March 2023 License Amendment Request to Modify the Arkansas Nuclear One, Unit 1, Technical Specification 3.3.1, Reactor Protection System Instrumentation, Turbine Trip Function on Low Control Oil Pressure 2CAN032303, Responses to Request for Additional Information Concerning the Request for Alternative Regarding the Half-Nozzle Repair of Reactor Vessel Closure Head Penetration 462023-03-29029 March 2023 Responses to Request for Additional Information Concerning the Request for Alternative Regarding the Half-Nozzle Repair of Reactor Vessel Closure Head Penetration 46 2CAN032304, Supplement to the Request for Alternative Regarding the Half-Nozzle Repair of Reactor Vessel Closure Head Penetration 462023-03-29029 March 2023 Supplement to the Request for Alternative Regarding the Half-Nozzle Repair of Reactor Vessel Closure Head Penetration 46 2CAN032305, 03 Post Examination Analysis2023-03-23023 March 2023 03 Post Examination Analysis 1CAN032302, Inspection Summary Report for the Thirtieth Refueling Outage (1R30)2023-03-20020 March 2023 Inspection Summary Report for the Thirtieth Refueling Outage (1R30) 1CAN012301, Responses to Request for Additional Information for Request for Relief ANO1-ISI-0352023-01-30030 January 2023 Responses to Request for Additional Information for Request for Relief ANO1-ISI-035 2CAN012303, U.S. Additional Protocol2023-01-23023 January 2023 U.S. Additional Protocol 2CAN012302, Relief Request ANO2-RR-23-001, Half-Nozzle Repair of Reactor Vessel Closure Head Penetration 462023-01-20020 January 2023 Relief Request ANO2-RR-23-001, Half-Nozzle Repair of Reactor Vessel Closure Head Penetration 46 1CAN122201, License Amendment Request to Revise Technical Specifications to Adopt Risk-Informed Completion Times TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative 42022-12-22022 December 2022 License Amendment Request to Revise Technical Specifications to Adopt Risk-Informed Completion Times TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative 4 0CAN122202, Registration of Cask Use2022-12-21021 December 2022 Registration of Cask Use 0CAN122201, Reply to a Notice of Violation; EA-22-0992022-12-0808 December 2022 Reply to a Notice of Violation; EA-22-099 0CAN112201, Request for Alternative Frequency to Containment Unbonded Post-Tensioning System Inservice Inspection (ANO-CISI-002)2022-11-10010 November 2022 Request for Alternative Frequency to Containment Unbonded Post-Tensioning System Inservice Inspection (ANO-CISI-002) 1CAN102202, Application to Remove Technical Specification Condition Allowing Two Reactor Coolant Pump Operation2022-10-31031 October 2022 Application to Remove Technical Specification Condition Allowing Two Reactor Coolant Pump Operation 1CAN102203, Cycle 31 Core Operating Limits Report2022-10-24024 October 2022 Cycle 31 Core Operating Limits Report 1CAN102201, Supplement to Proposed Technical Specifications 3.4.12 and 3.4.13 Revised Dose Calculations2022-10-13013 October 2022 Supplement to Proposed Technical Specifications 3.4.12 and 3.4.13 Revised Dose Calculations 0CAN092201, Supplement to License Amendment Request for Approval of Changes to the Emergency Plan Staffing Requirements2022-09-29029 September 2022 Supplement to License Amendment Request for Approval of Changes to the Emergency Plan Staffing Requirements 1CAN092201, Supplement to Request for Relief from American Society of Mechanical Engineers Section XI Volumetric Examination Requirements - Fifth 10-Year Interval, First Period2022-09-0808 September 2022 Supplement to Request for Relief from American Society of Mechanical Engineers Section XI Volumetric Examination Requirements - Fifth 10-Year Interval, First Period 0CAN082201, License Amendment Request for Approval of Changes to the Emergency Plan Staffing Requirements2022-08-30030 August 2022 License Amendment Request for Approval of Changes to the Emergency Plan Staffing Requirements 1CAN082201, Request for Relief from American Society of Mechanical Engineers Section XI Volumetric Examination Requirements - Fifth 10-Year Interval, First Period2022-08-24024 August 2022 Request for Relief from American Society of Mechanical Engineers Section XI Volumetric Examination Requirements - Fifth 10-Year Interval, First Period 2CAN072201, Response to Request for Additional Information Requests for Relief from American Society of Mechanical Engineers Section XI Volumetric Examination Requirements - Fourth 10-Year Interval, Second and Third Periods2022-07-20020 July 2022 Response to Request for Additional Information Requests for Relief from American Society of Mechanical Engineers Section XI Volumetric Examination Requirements - Fourth 10-Year Interval, Second and Third Periods 0CAN072201, Registration of Cask Use2022-07-14014 July 2022 Registration of Cask Use 0CAN062202, Registration of Cask Use2022-06-0909 June 2022 Registration of Cask Use 1CAN062201, Response to the Request for Additional Information Proposed Technical Specifications 3.4.12 and 3.4.13 Revised Dose Calculations2022-06-0202 June 2022 Response to the Request for Additional Information Proposed Technical Specifications 3.4.12 and 3.4.13 Revised Dose Calculations 1CAN052201, Request for Relief Related to American Society of Mechanical Engineers (ASME) Code Case N-729-6 Augmented Examination Requirements ANO1-ISI-0352022-05-31031 May 2022 Request for Relief Related to American Society of Mechanical Engineers (ASME) Code Case N-729-6 Augmented Examination Requirements ANO1-ISI-035 2024-01-17
[Table view] |
Text
Entergy Operations, Inc.
1448 S.R. 333 Russellville, AR 72802 Tel 479-858-3110 Jeremy G. Browning Site Vice President Arkansas Nuclear One 0CAN081407 August 19, 2014 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555
SUBJECT:
Response to Request for Additional Information Adoption of Technical Specification Task Force (TSTF)-431, Revision 3 (ANO-1), and Adoption of TSTF-422, Revision 2 (ANO-2) Regarding Technical Specifications End States Docket Nos. 50-313 and 50-368 License Nos. DPR-51 and NPF-6
Dear Sir or Madam:
By letter dated August 4, 2014 (Reference 3), the NRC requested additional information associated with the Entergy Operations, Inc. (Entergy) request to amend the Arkansas Nuclear One, Unit 1 (ANO-1) and Unit 2 (ANO-2) Technical Specifications (TS) to incorporate the NRC approved TSTF-431, Revision 3, and TSTF-422, Revision 2, regarding a change in TS end states. The proposed amendment would modify TSs to risk-inform requirements regarding selected Required Action end states.
During the license amendment request (LAR) review, the NRC staff noted that one of the regulatory guidance documents used in the staffs regulatory assessment for the TSTFs, and referenced in the staffs associated model safety evaluations (SEs), has since been superseded. The issue concerns a specific reference to Regulatory Guide (RG) 1.182, Assessing and Managing Risk Before Maintenance Activities at Nuclear Power Plants, contained in both TSTF-431 and TSTF-422. RG 1.182 was withdrawn since it was determined that the document was redundant due to the inclusion of its subject matter in Revision 3 of RG 1.160, Monitoring the Effectiveness of Maintenance at Nuclear Power Plants. The withdrawal notice for RG 1.182 was published in the Federal Register on November 27, 2012 (78 FR 70846).
In addition, the NRC staff observed that RG 1.160 endorsed Revision 4A of the Nuclear Management and Resources Council (NUMARC) 93-01, Industry Guideline for Monitoring the Effectiveness of Maintenance at Nuclear Power Plants. NUMARC 93-01 provides methods that are acceptable to the NRC staff for complying with the provisions of 10 CFR 50.65, Requirements for Monitoring the Effectiveness of Maintenance at Nuclear Power Plants. The model SEs for the TSTFs currently refer to the guidance in Revision 2 of the NUMARC 93-01.
0CAN081407 Page 2 of 4 In order to justify adoption of the TSTF changes, the NRC has requested (Reference 3) confirmation that ANO-1 and ANO-2, adhere to the RG 1.160 guidance, including the updated version of NUMARC 93-01. The response should confirm that the topical reports supporting the LARs comply with NUMARC 93-01, Section 11, and identify, if any, inconsistencies with this section.
Entergys confirmation of the subject matter follows.
Entergy committed ANO-1 and ANO-2 to follow the guidance established in TSTF-IG-07-01, Revision 1, Implementation Guidance for TSTF-431, Revision 3, Change in Technical Specifications End States, BAW-2441-A," and WCAP-16364-NP, Revision 2, Implementation Guidance for Risk Informed Modification to Selected Required Action End States at Combustion Engineering NSSS Plants (TSTF-422), respectively, as part of the original LARs (References 1 and 2). Both guidance documents require plants adopting the end states TSTFs to commit to the guidance contained in Section 11 of NUMARC 93-01, Revision 3, for assessing risk associated with maintenance activities. RG 1.182 is referenced in both guidance documents only to state that RG 1.182 endorses NUMARC 93-01 as one acceptable approach to implement 10 CFR 50.65(a)(4), but is not otherwise mentioned.
Topical Report BAW-2441, Risked Informed Justification for LCO End State Changes, and the associated NRC SE do not reference RG 1.160, RG 1.182, or NUMARC 93-01, but do require a program be established to address 10 CFR 50.65(a)(4) Maintenance Rule aspects with respect to risk management. Similar to the aforementioned guidance for Combustion Engineering (CE) plants, Topical Report CENSPD-1186, Technical Justification for the Risk Informed Modification to Selected Required Action End States for CEOG Member PWRs, and its associated NRC SE, references RG 1.182 with regard to its endorsement of NUMAR 93-01.
Both Revisions 2 and 3 of the NUMARC are mentioned in the CE report. NUMARC 93-01, Revision 4A, incorporated additional guidance related to fire risk, equipment to be scoped in the Maintenance Rule, and the definition of availability was modified. The guidance included in RG 1.160, Revision 3, and NUMARC 93-01, Revision 4A, built upon and/or enhanced that provided in RG 1.182 or in previous revisions to the NUMARC; therefore, application of RG 1.160, Revision 3, and NUMARC 93-01, Revision 4A, does not result in inconsistencies with the intent of the topical reports, supporting topical report SEs, or the aforementioned TSTF end state implementation guidance.
Entergy fleet procedure EN-DC-203, Maintenance Rule Program, currently references NUMARC 93-01 and RG 1.160 as the base guidance documents for implementation of the Maintenance Rule at Entergy sites, which includes ANO-1 and ANO-2. Furthermore, the industry committed (Reference 4) through the Nuclear Energy Institute (NEI) to implement RG 1.160, Revision 3, which endorses NUMARC 93-01, Revision 4A. As a result, Entergy fleet procedure EN-OU-108, Shutdown Safety Management Program (SSMP), was revised with reference to NUMAR 93-01 to include qualitative risk guidance and risk management actions (RMAs), such as those applicable to fire-related features which become unavailable during shutdown operational modes. ANO procedure COPD-024, Risk Assessment Guidelines, was also revised to include comprehensive guidance related to fire risks and RMAs, and specifically discusses the guidance contained in NUMARC 93-01, Revision 4A.
The ANO end state LARs committed to Section 11 of NUMARC 93-01, Revision 3, with regard to assessing risk in support of the new Mode 4 end states delineated in the subject TSTFs. As stated previously, the ANO LARs also committed to the respective implementation guidance documents, which refer to Revision 3 of the NUMARC. Although the ANO Maintenance Rule
0CAN081407 Page 3 of 4 program is currently based on NUMAR 93-01, Revision 4A, the aforementioned commitments are updated to reflect the intended guidance. Attachments 1 and 2 of this letter provide an updated list of regulatory commitments associated with the ANO-1 and ANO-2 end state LARs (References 1 and 2), respectively. The complete table listing of commitments is included from each original LAR for completeness. These two attachments supersede Attachment 2 of the Reference 1 and 2 LARs, respectively.
Additional information, as detailed in this letter, with respect to the original Entergy requests (References 1 and 2) has been reviewed and Entergy has determined that the information does not invalidate the no significant hazards consideration discussed in the Reference 1 and 2 letters.
In accordance with 10 CFR 50.91(b)(1), a copy of this response is being provided to the designated Arkansas state official.
Revised commitments are included in Attachments 1 and 2 of this letter.
If you have any questions or require additional information, please contact Stephenie Pyle at 479-858-4704.
I declare under penalty of perjury that the foregoing is true and correct.
Executed on August 19, 2014.
Sincerely, ORIGINAL SIGNED BY JEREMY G. BROWING JGB/dbb Attachments:
- 1. Revised List of Regulatory Commitments - ANO-1 End States
- 2. Revised List of Regulatory Commitments - ANO-2 End States
0CAN081407 Page 4 of 4
REFERENCES:
- 1. Entergy letter dated March 26, 2013, License Amendment Request -
Adoption of Technical Specification Task Force (TSTF)-431, Revision 3, "Change in Technical Specifications End States (BAW-2441)"
(1CAN031306) (ML13085A282)
- 2. Entergy letter dated March 26, 2013, License Amendment Request -
Adoption of Technical Specification Task Force (TSTF)-422, Revision 2, Change in Technical Specifications End States (CE NPSD-1186)
(2CAN031303) (ML13085A283)
- 3. NRC letter dated August 4, 2014, Request for Additional Information Regarding License Amendment Requests to Adopt Changes to Technical Specification End States (0CNA081401) (ML14209A627)
- 4. NEI letter dated January 4, 2011, Revision 4 to NUMARC 93-01, Industry Guideline for Monitoring the Effectiveness of Maintenance at Nuclear Power Plants (ML110280083) cc: Mr. Marc L. Dapas Regional Administrator U. S. Nuclear Regulatory Commission Region IV 1600 East Lamar Boulevard Arlington, TX 76011-4511 NRC Senior Resident Inspector Arkansas Nuclear One P. O. Box 310 London, AR 72847 U. S. Nuclear Regulatory Commission Attn: Ms. Andrea E. George MS O-8B1 One White Flint North 11555 Rockville Pike Rockville, MD 20852 Mr. Bernard R. Bevill Arkansas Department of Health Radiation Control Section 4815 West Markham Street Slot #30 Little Rock, AR 72205
Attachment 1 to 0CAN081407 Revised List of Regulatory Commitments - ANO-1 End States to 1CAN031306 Page 1 of 1 LIST OF REGULATORY COMMITMENTS The following table identifies those actions committed to by Entergy in this document. Any other statements in this submittal are provided for information purposes and are not considered to be regulatory commitments.
TYPE (Check one) SCHEDULED COMMITMENT COMPLETION ONE-TIME CONTINUING DATE ACTION COMPLIANCE Entergy will modify the Technical Upon Specification Bases for the revised implementation of specifications as adopted with the the approved TS applicable license amendment. amendment Entergy will follow the guidance established in Section 11 of NUMARC 93-01, Industry Guidance for Monitoring the Effectiveness Ongoing of Maintenance at Nuclear Power Plants, Nuclear Management and Resource Council, Revision 4A, April 2011.
Entergy will follow the guidance established Upon in TSTF-IG-07-01, Revision 1, implementation of Implementation Guidance for TSTF-431, the approved TS Revision 3, Change in Technical amendment, Specifications End States, BAW-2441-A, , when the TS with the exception that Section 11 of Required Action NUMARC 93-01, Revision 4A, will be End State utilized to meet 10 CFR 50.65(a)(4) remains within requirements in lieu of NUMARC 93-01, the Applicability Revision 3. of the TS
Attachment 2 to 0CAN081407 Revised List of Regulatory Commitments - ANO-2 End States to 2CAN031303 Page 1 of 1 LIST OF REGULATORY COMMITMENTS The following table identifies those actions committed to by Entergy in this document. Any other statements in this submittal are provided for information purposes and are not considered to be regulatory commitments.
TYPE (Check one) SCHEDULED COMMITMENT COMPLETION ONE-TIME CONTINUING DATE ACTION COMPLIANCE Entergy will modify the Technical Upon Specification Bases for the revised implementation of specifications as adopted with the the approved TS applicable license amendment. amendment Entergy will follow the guidance established in Section 11 of NUMARC 93-01, Industry Guidance for Monitoring the Effectiveness Ongoing of Maintenance at Nuclear Power Plants, Nuclear Management and Resource Council, Revision 4A, April 2011.
Entergy will follow the guidance established Upon in WCAP-16364-NP, Revision 2, implementation of Implementation Guidance for Risk the approved TS Informed Modification to Selected Required amendment, Action End States at Combustion when the TS Engineering NSSS Plants (TSTF-422),
Required Action dated May 2010, with the exception that End State Section 11 of NUMARC 93-01, remains within Revision 4A, will be utilized to meet the Applicability 10 CFR 50.65(a)(4) requirements in lieu of of the TS NUMARC 93-01, Revision 3.