ML14190A145

From kanterella
Jump to navigation Jump to search
Forwards Technical Review Rept on Errors in Effective RT Settings or Monitoring Associated W/Excore Instrumentation. Study Initiated Because of LER from Hb Robinson & Harris
ML14190A145
Person / Time
Site: Robinson, Harris  
Issue date: 06/17/1992
From: Israel S
NRC OFFICE FOR ANALYSIS & EVALUATION OF OPERATIONAL DATA (AEOD)
To: Rosenthal J
NRC OFFICE FOR ANALYSIS & EVALUATION OF OPERATIONAL DATA (AEOD)
Shared Package
ML14190A146 List:
References
AEOD-T92-05, AEOD-T92-5, NUDOCS 9206250253
Download: ML14190A145 (2)


Text

0 ~

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 17 92 MEMORANDUM FOR:

Jack E. Rosenthal, Chief Reactor Operations Analysis Branch Division of Safety Programs Office for Analysis and Evaluation of Operational Data FROM:

Sanford L. Israel Reactor Systems Section W and B&W Reactor Operations Analysis Branch Division of Safety Programs Office for Analysis and Evaluation of Operational Data

SUBJECT:

ERRORS IN EFFECTIVE REACTOR TRIP SETTINGS OR MONITORING ASSOCIATED WITH EXCORE INSTRUMENTATION Enclosed is a technical review report on errors in effective reactor trip settings or monitoring associated with excore instrumentation. This study was initiated because of licensee event reports from H. B. Robinson and Shearon Harris. Excore instrumentation is used in the reactor protection system for overpower reactor trips, departure from nucleate boiling trips in certain plants (axial offset input) and periodic surveillance of core power and power distributions (axial power input), and flux rate. Calorimetric calculations are used to calibrate the core power function and incore instrumentation is used to calibrate the axial shape function.

The safety significance is that departure from nucleate boiling could occur during certain reactor transients if the calibration errors or deviations in the excore signals from actual reactor power are large. These instruments are also monitored to maintain the plant within licensed power and to maintain the axial power distribution within limits imposed by the LOCA analyses.

A wide range of human errors contributed to the observed errors in the effective trip settings.

These included those associated with writing procedures, administrative oversight of the calibration process, and actual technician errors. Most of these types of maintenance errors have been addressed in industry generic communications. Generally, none of the evaluations 9206250253 920617 PDR ADOCK 05000261 P

PDR

Jack E. Rosenthal

-2 in the LERs reviewed indicated consequences outside of the FSAR analyses. Consequently, no new generic activity appears warranted at this time. It should be noted that several of the LERs illustrated the benefits of monitoring alternate indications of core power to verify that the NIS indications are reasonable.

Sanford L. Israel Reactor Systems Section W and B&W Reactor Operations Analysis Branch Division of Safety Programs Office for Analysis and Evaluation of Operational Data

Enclosure:

As stated cc w/enclosure:

R. Jones, NRR H. Richings, NRR L. Kopp, NRR Distribution:

PDR EWeiss CBerlinger, NRR Central File SRubin ROAB R/F PBaranowsky SIsrael KBlack WJones RSavio, ACRS JRosenthal MTaylor, EDO EJordan KRaglin, TTC DRoss AChaffee, NRR TNovak PLewis, INPO VBenaroya DQueener, NOAC LSpessard VChexal, EPRI ROAB:DSP:AEOD ROAB:DSP:AEOD C

O

DSP:AEOD SIsrael:rgz CZ WJones JRosenthal 6/11/92 6//9/92