ACCELERATED IRIBUTIN 1dMNSTRATION SYSTEM REGULATORJNFORMATION DISTRIBUTION S EM (RIDS)
ACCESSION.NBR:8903240216 DOC.DATE: 89/03/17 NOTARIZED: NO DOCKET #
FACIL:50--261 H.B. Robinson Plant, Unit 2, Carolina Power & Light C 05000261 AUTH.NAME AUTHOR AFFILIATION TROSKOSKI,W.
Ofc of Enforcement (Post 870413)
LIEBERMAN,J.
Ofc of Enforcement (Post 870413)
RECIP.NAME RECIPIENT AFFILIATION
SUBJECT:
EN-88-051A:on 880610,notice of violation & proposed I
imposition of civil penalties in amount of $50,000.
DISTRIBUTION CODE: IE33D COPIES RECEIVED:LTR 0ENCL SIZE:
TITLE: Enforcement Notice (EN)
C NOTES:
RECIPIENT COPIES RECIPIENT COPIES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL INTERNAL: AEOD/DOA 1
AEOD/DSP/TPAB 1
DEDRO 1
NRR/DOEA/EAB 11 1
NRR/DREP/EPB 10 1
NRR/PMAS/ILRB12 1
NUDOCS-ABSTRACT 1
OE FILE 01 1
OE LIEBERMAN,J 1
c-REGjFIiE ;
02 1
RGN2/DRSS/EPRPB 1
EXTERNAL: LPDR 1
NRC PDR 1
NSIC 1
I D
S NOIE 'IO ALL "RIES" RECIPIENIS:
S PLEASE EP US IO REDUCE WASTE!
CONTACT THE DOCUMEN CDNIROL DESK, ROCM 1-37 (EXT.
20079) TO ELNDT OU NAME F10( DISTRIBUION LISTS OR DOCUMENTS YOU DCN'T NEED!
TOTAL NUMBER OF COPIES REQUIRED: LTTR ENL 14
0 WMarch 17, 1989 EN 88-51A OFFICE OF ENFORCEMENT NOTIFICATION OF SIGNIFICANT ENFORCEMENT ACTION Licensee:
Carolina Power & Light Company (EA 88-88)
(Robinson)
License No.
DPR-23 Docket No. 50-261
Subject:
IMPOSITION OF CIVIL PENALTY - $50,000 By EN 88-51 dated June 10, 1988 the Commission was notified of the intent of OE to issue a Notice of Violation and Proposed Imposition of Civil Penalty in the amount of Fifty Thousand Dollars ($50,000) to Carolina Power & Light Company.
This action was based on a violation involving failure of the 10 CFR 50.46, Appendix K required ECCS evaluation model used to reflect the most damaging single failure relative to the ECCS safety injection system. The evaluation erroneously assumed that two of the three SI pumps would be operable during a design basis accident, when, in fact, there were several single failure scenarios that could result in only one SI pump being operable.
The licensee responded to the Notice in a letter dated July 15, 1988. After careful consideration of the licensee's response, the staff has concluded that the violation did occur as set forth in the Notice of Violation and Proposed Imposition of Civil Penalty, less scenarios (2) and (3) of the violation. The original proposed civil penalty has not been changed because the basis in this case was the failure to comply with 10 CFR 50.46 and not solely the number of individual failure scenarios described. Because the licensee response raises questions concerning its ECCS design, the staff is pursuing this matter through a 10 CFR 50.54(f) letter to the licensee.
Accordingly, an Order Imposing Civil Penalty in the amount of $50,000 has been issued today.
Under the terms of the Order, the licensee may within 30 days of the date of the Order, pay the civil penalty or request a hearing.
Contact:
W. Troskoski, OE, 23281 J. Lieberman, OE, 20741 Distribution OWFN W
) Y/
MNBB 2 Chairman Zech EDO RM Comm. Roberts DEDR AEOD Comm. Carr NRR Comm. Rogers OE Comm. Curtiss NMSS SECY OGC ACRS 01 CA SP GPA Regional Offices MAIL RI '9f9iRIV
'§ADM:
Doc. Mgt. Br.
R I I PDR RIII c 5
RES OA 8903240216 890317 PDR I&E
/
EN-88-051A PNU