UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555 April 20, 1992 Docket No. 50-261 Mr. R. A. Watson Executive Vice President Power Supply Carolina Power & Light Company Post Office Box 1551 Raleigh, North Carolina 27602

Dear Mr. Watson:

SUBJECT:

RELIEF FROM ASME CODE, SECTION XI, SERVICE WATER SYSTEM REPAIR - H. B. ROBINSON STEAM ELECTRIC PLANT, UNIT NO. 2, (TAC NO. M82080)

By letter dated September 27, 1991, as supplemented January 29, 1992, jCarolina Power and Light Company (CP&L) requested relief from the requirements of American Society of Mechanical Engineers Boiler and Pressure Vessel Code (ASME Code),Section XI, pursuant to 10 CFR 50.55a(g)(6)(i). The relief for temporary non-code repair of the Service Water (SW) system piping welds related to Containment Fan Cooler HVH-4 and welds at the SW containment penetrations had been previously approved in NRC letter of January 23, 1991, under the condition that a permanent repair of the piping welds in compliance with the ASME code would be performed during the next Refueling Outage (Refueling Outage 14 in 1992).

However, CP&L has subsequently determined that the extensive engineering and construction planning necessary to perform the permanent repairs could not be completed in time to be accomplished during Refueling Outage 14 and now requests continuation of the relief until the permanent repairs are made during Refueling Outage 15 (presently scheduled for late 1993).

In accordance with the requirements of 10 CFR 50.55a, the staff has performed a review of your request. The staff concludes that compliance with the ASME Code requirements would be impractical to perform and that performance of the temporary nontcode repair you proposed would provide an acceptable level of quality and safety. The staff has determined that granting relief, pursuant 9204300330 920420 PDR ADOCK 05000261 P

PDR

Mr. Lynn W. Eury

-2 10 CFR 50.55a(a)(3)(i), (a)(3)(iii), or (g)(6)(i), is authorized by law and will not endanger life or property, or the common defense and security and is otherwise in the public interest giving due consideration to the burden upon CP&L that could result if the ASME Code requirements were imposed on the facility.

This relief is granted until the completion of Refueling Outage 15 scheduled for late 1993. The staff's Safety Evaluation on this request is enclosed.

Sincerely, Orignal signed by:

Elinor G. Adensam, Director Project Directorate I/II Division of Reactor Projects -

I/II Office of Nuclear Reactor Regulation cc:

See next page LA:

£ PE:PD21:Afi M:PD

06)

OGCQ~~

PAnt h n Webb:d Lo:~tAV 3/ j) /92 Y/

4 92 3/ 4/92 3 ff//92 D:P 1 RPE EAde am 4 /1. /92 ROB82080.1tr

Mr. L. W. Eury H. B. Robinson Steam Electric Carolina Power & Light Company Plant, Unit No. 2 cc:

Mr. H. Ray Starling Mr. Dayne H. Brown, Director Manager - Legal Department Department of Environmental, Carolina Power & Light Company Health and Natural Resources P. 0. Box 1551 Division of Radiation Protection Raleigh, North Carolina 27602 P. 0. Box 27687 Raleigh, North Carolina 27611-7687 Mr. H. A. Cole Special Deputy Attorney General Mr. Robert P. Gruber State of North Carolina Executive Director P. 0. Box 629 Public Staff - NCUC Raleigh, North Carolina 27602 P. 0. Box 29520 Raleigh, North Carolinia 27626-0520 U.S. Nuclear Regulatory Commission Mr. C. R. Dietz Resident Inspector's Office Vice President H. B. Robinson Steam Electric Plant Robinson Nuclear Department Route 5, Box 413 H. B. Robinson Steam Electric Plant Hartsville, South Carolina 29550 P. 0. Box 790 Hartsville, South Carolina 29550 Regional Administrator, Region IT U.S. Nuclear Regulatory Commission Mr. Heyward G. Shealy, Chief 101 Marietta Street Bureau of Radiological Health Suite 2900 South Carolina Department of Health Atlanta, Georgia 30323 and Environmental Control 2600 Bull Street Mr. Ray H. Chambers, Jr.

Columbia, South Carolina 29201 General Manager H. B. Robinson Stedm Electric Plant P. 0. Box 790 HartsvRlle, South Carolina 29550

DISTRIBUTION.

NRC &Local PDRs PD21 Reading File S. Varga G. Lainas E. Adensam J. Wiggins G. Hornseth R. Lo P. Anderson OGC ACRS (10)

L. Reyes RH