February 10, 1994 Docket No. 50-261 License No. DPR-23 Carolina Power and Light Company ATTN:

Mr. C. R. Dietz Vice-President H. B. Robinson Steam Electric Plant Unit 2 P. 0. Box 790 Hartsville, SC 29550-0790 Gentlemen:

SUBJECT:

ENVIRONMENTAL QUALIFICATION OF SUBMERGED CABLES (H. B. ROBINSON)

This refers to the conversation between Mr. A. F. Gibson, NRC, and Mr. C. R. Dietz, Carolina Power and Light Company on February 9, 1994, concerning the results of our safety evaluation on the Environmental Qualification (EQ) of certain cables installed in safety related systems at your H. B. Robinson-plant. The issue was first identified during an NRC Inspection (50-261/89-26) conducted by this office on October 23 -27, 1989.

During that inspection an unresolved item was identified regarding the adequacy of your EQ files in demonstrating qualification for certain safety related EQ cables which may become submerged during or after a loss-of-cooling accident (LOCA).

The issue was left unresolved pending further review by the NRC staff.

The NRC, with the assistance of Sandia National Laboratory, has completed the review of your EQ files, and your letter dated March 3, 1992, in which you documented your position on the qualification of specific cables that may become submerged. The staff has determined that post LOCA submergence qualification for the cables in question has not been established by your files. The basis for our conclusions are. discussed in the enclosed Safety Evaluation (SE).

Your technical arguments that water immersion tests performed by the vendors on unaged and un-irradiated specimens were sufficient to demonstrate qualification for post LOCA submergence was not acceptable. Additionally, the Sandia test data published in NUREG/CR-5655 dated May 1991 on post LOCA submergence testing of Boston Insulated Wire (BIW) and Samuel Moore cable.

cannot be used as a basis for qualification of your cable, due to the reason indicated in the SE.

9403280173 940210 PDR ADOCK 05000261 PPU

Carolina Power and Light 2

February 10, 1994 Company We refer you to the guidance of NRC Generic Letter 88-07 in handling NRC identifed safety issues involving unqualified equipment. Should you have any questions concerning this letter, please contact.us.

Sincerely, (ORIGINAL SIGNED BY A..F. GIBSON)

Albert F. Gibson, Director Division of Reactor Safety

Enclosure:

Safety Evaluation cc w/encl:

M. P. Pearson Plant Manager H. B. Robinson Steam Electric Plant P. 0. Box 790 Hartsville, SC 29550 H. W. Habermeyer, Jr.

Vice President Nuclear Services Department Carolina Power & Light Company P. 0. Box 1551 - Mail 0HS7 Raleigh, NC 27602 W. Dorman, Acting Manager Regulatory Compliance H. B. Robinson Steam Electric Plant P. 0. Box 790 Hartsville, SC 29550 Max Batavia, Chief Bureau of Radiological Health Dept. of Health and Environmental Control 2600 Bull Street Columbia, SC 29201 Dayne H. Brown, Director Division of Radiation Protection N. C. Department of Environment, Commerce & Natural Resources P. 0. Box 27687 Raleigh, NC 27611-7687 cc w/encl -

(cont'd see page 2)

Carolina Power and Light 3

February 10, 1994 Company.

(cc w/encl cont'd)

H. Ray Starling Manager - Legal Department Carolina Power and Light Co.

P. 0. Box 1551 Raleigh, NC 27602 Karen E. Long Assistant Attorney General State of North Carolina P. 0. Box 629 Raleigh, NC 27602 Robert P. Gruber Executive Director Public Staff - NCUC P. 0. Box 29520 Raleigh, NC 27626-0520 Public Service Commission State of South Carolina P. 0. Box 11649 Columbia, SC 29211 bcc w/encl:

H. Christensen, RII B. Mozafari, NRR Document Control Desk NRC Resident Inspector U. S. Nuclear Regulatory Commission 5421 Shearon Harris Road New Hill, SC 27562-9998.

DOCUMENT NAME: S:\\DRS\\EB\\ROB8926L.NXM It2 RII:DRS RII:DRS RII:D P NRR NMerriweather M'h ylock DVerrelli,

Bajwa 2//L0 /94 2/1- /94 2/10/94 2/V 194