Notice of Violation from Insp on 920509-0627.Violation Noted:Maint Procedures Not Adequately Established in That on 920616,CM-303 Did Not Provide Instructions to Remove All non-qualified or Braided Jacket Matl from Splice Area
ML14178A251
Person / Time
Site: Robinson 
Issue date: 07/23/1992
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML14178A250 List:
References
50-261-92-16, NUDOCS 9208110006
Download: ML14178A251 (2)


Text

ENCLOSURE 1 NOTICE OF VIOLATION Carolina Power and Light Company Docket No. 50-261 H. B. Robinson Unit 2 License No. DPR-23 During the NRC inspection conducted on May 9 -

June 27, 1992, violations of NRC requirements were identified. In accordance with the "General Statement of Policy and Procedure For NRC Enforcement Actions," 10 CFR Part 2, Appendix C (1992), the violations are listed below:

A.

Technical Specification 6.5.1.1.1 requires written proce dures be established for activities referenced in Appendix A of Regulatory Guide 1.33, revision 2, February 1978.

Appen dix A paragraph 9 requires that maintenance which can affect the performance of safety related equipment be performed in accordance with written procedures appropriate to the cir cumstances. CM-303 was established to provide a written procedure for the installation of environmentally qualified taped splices.

CM-508 was established to provide a written procedure to disassemble and reassemble the emergency diesel generator (EDG) fuel oil filter cartridge assembly.

Contrary to the above, maintenance procedures were not adequateley established in that:

1.

On June 16, 1992, CM-303 did not provide instructions to remove all non-qualified or braided jacket material from the splice area.

2.

On May 26, 1992, the steps provided in CM-508 for the reassembly of the EDG fuel oil filter cartridge assem bly were incorrectly sequenced. This contributed to the improper assembly of the B EDG fuel oil filter cartridge assembly and subsequent failure of the B EDG during testing.

This is a Severity Level IV violation (Supplement I).

B.

10 CFR 50 Appendix B Criterion V requires that activities affecting quality shall be prescribed by documented instruc tions appropriate to the circumstances. Modification M-1128 provided documented instructions for the reconfiguration of the safety injection cold leg injection containment isolation boundary.

9208110006 920723 PDR ADOCK 05000261 0

PDR 2

Contrary to the above, M-1128 did not provide instructions appropriate to the circumstances in that the modification created a potential for an unmonitored release pathway during normal operation.

This is a Severity Level IV violation (Supplement I).

Pursuant to the provisions of 10 CFR 2.201, Carolina Power and Light Company is hereby required to submit a written statement or explanation to the U. S-. Nuclear Regulatory Commission, ATTN:

Document Control Desk, Washington, DC 20555, with a copy to the Regional Administrator, Region II, and a copy to the NRC Resident Inspector, within 30 days of the date of the letter transmitting this Notice of Violation (Notice). This reply should be clearly marked as a "Reply to a Notice of Violation" and should include for each violation:

(1) the reason for the violation, or, if contested, the basis for disputing the violation, (2) the corrective steps that have been taken and the results achieved, (3) the corrective steps that will be taken to avoid further violations, and (4) the date when full compliance will be achieved. If an adequate reply is not received within the time specified in this Notice, an order may be issued to show cause why the license should not be modified, suspended, or revoked, or why such other action as may be proper should not be taken.

Where good cause is shown, consideration will be given to extend ing the response time.

Dated at Atlanta, Georgia this 23rd of July 1992