o UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 CAROLINA POWER AND LIGHT COMPANY DOCKET NO.

50-261 H. B. ROBINSON, UNIT NO. 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 49 License No.

DPR-23 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A. The application for amendment by Carolina Power and Light Company (the licensee) dated October 3, 1979 complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B. The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C. There is reasonable assurance (i) that the activities authorized by this amendment.can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D. The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the publicn; and E. The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

'8010140 fI(4

-2

2. Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 3.8 of Facility Operating License No.

DPR-23 is hereby amended to read as follows:

B. Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 49, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

3. This license amendment is effective as of the date of its issuance.

FOR THE NUC EAR REGULATORY COMMISSION Steven A. Varga, C e Operating Reactors ranch #1 Division of Licensing

Attachment:

Changes to the Technical Speci fications Date of Issuance:

September 19, 1980

ATTACHMENT TO LICENSE AMENDMENT NO.

49 FACILITY OPERATING LICENSE NO. DPR-23 DOCKET NO. 50-261 Revise Appendix A as follows:

Remove Insert 3.5-7A 3.5-10A 4.1-6A

Table 3.5-1 (Continued)

ENGINEERED SAFETY FEATURE SYSTEM INITIATION INSTRUMENT SETTING LIMITS NO.

FUNCTIONAL UNIT CHANNEL ACTION SETTING LIMIT 6

Loss of Power

a.

480V Emerg. Bus Undervoltage Trip Breaker 394 Volts + 1 volt (Loss of Voltage)

Instantaneous

b.

480V Emerg. Bus Undervoltage Trip Breaker 413 Volts + 1 volt (Degraded Voltage) 10.0 Second Delay + 0.5 sec.

(D C+

Table 3.5-3 (Continued) 1 2

3 MINIMUM MINIMUM OPERABLE DEGREE OF OPERATOR ACTION IF CONDITIONS NO.

FUNCTIONAL UNIT CHANNELS REDUNDANCY OF COLUMN 1 OR 2 CANNOT BE MET 3

Loss of Power

a.

480V Emerg. Bus 2/Bus 1/Bus Maintain Hot Shutdown.

Undervoltage (Loss of Voltage)

b.

480V Emerg. Bus 2/Bus 1/Bus Maintain Hot Shutdown.

Undervoltage (Degraded Voltage)

CL C+

0

Table 4.1-1 (Continued)

NO.

CHANNEL DESCRIPTION CHECK CALIBRATE TEST REMARKS 32 Loss of Power

a.

480V Emerg. Bus D

R MM (1) During hot shutdown and power Undervoltage (Loss operations.

When periods of of Voltage) reactor cold shutdown and refueling extend this interval

b.

480V Emerg. Bus D

R MM beyond one month, the test shall Undervoltage be performed prior to startup.

(Degraded Voltage)