Supplemental Information Application for Technical Specification Improvement to Adopt TSTF-501-A. Revision 1
ML14042A046
Person / Time
Site: Calvert Cliffs  Constellation icon.png
Issue date: 02/07/2014
From: George Gellrich
Calvert Cliffs, Constellation Energy Nuclear Group, EDF Group
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
TSTF-501-A, Rev 1
Download: ML14042A046 (4)


Text

George H. Gellrich Site Vice President Calvert Cliffs Nuclear Power Plant, LLC 1650 Calvert Cliffs Parkway Lusby, Maryland 20657 410.495.5200 410.495.3500 Fax CENG.

a joint venture of Cao*tellation CALVERT CLIFFS NUCLEAR POWER PLANT February 7, 2014 U. S. Nuclear Regulatory Commission Washington, DC 20555 ATTENTION:

Document Control Desk

SUBJECT:

Calvert Cliffs Nuclear Power Plant Unit Nos. 1 & 2; Docket Nos. 50-317 & 50-318 Supplemental Information re:

Application for Improvement to Adopt TSTF-501-A. Revision I Technical Specification

REFERENCES:

(a) Letter from G. H. Gellrich (CCNPP) to Document Control Desk (NRC),

dated October 2,

2012, Application for Technical Specification Improvement to Adopt TSTF-501-A, Revision 1, "Relocate Stored Fuel Oil and Lube Oil Volume Values to Licensee Control" (b) Letter from G. H. Gellrich (CCNPP) to Document Control Desk (NRC) dated November 26, 2012, Supplemental Information re: Application for Technical Specification Improvement to Adopt TSTF-50 I-A, Revision I In Reference (a), Calvert Cliffs Nuclear Power Plant, LLC submitted a request for an amendment to the Technical Specifications for Calvert Cliffs Nuclear Power Plant (Calvert Cliffs) Units 1 and 2 to move the current stored diesel fuel oil numerical volume requirements from the Technical Specification to the Technical Specification Bases consistent with Technical Specification Task Force (TSTF)-501-A, Revision 1.

Reference (b) provided supplemental information regarding the method of calculating the required stored diesel fuel oil volume equivalent to a seven day supply. The method provided in American National Standards Institute (ANSI) N 195-1976, Section 5.4, as endorsed by Regulatory Guide 1.137, Revision 1, Section C.l.c, is used to calculate the required stored diesel fuel oil volume equivalent to a seven day supply. Calvert Cliffs uses the "conservative" calculational method described by ANSI N195-1976, Section 5.4 to calculate the required stored diesel fuel oil volume. These references are added to the marked up Technical Specification Bases as shown in Reference (b). In addition, Calvert Cliffs commits to providing the following discussion in the Updated Final Safety Analysis Report.

Document Control Desk February 7, 2014 Page 2 "The specific emergency diesel generator fuel oil volumes (equivalent to duration based requirements) contained in the fuel oil storage tanks referenced in Technical Specification 3.8.3 are calculated using the method provided in American National Standards Institute (ANSI)

N 195-1976, Section 5.4, as endorsed by Regulatory Guide 1.137, Revision 1, Section C.l.c. The fuel oil calculation is based on applying the conservative assumption that the emergency diesel generator is operated continuously at rated capacity.

This is one of two approved methods specified in Regulatory Guide 1.137, Revision 1."

This supplement does not change the No Significant Hazards Consideration previously provided in Reference (a). Attachment (1) contains the regulatory commitment described in this letter.

Should you have questions regarding this matter, please contact Mr. Douglas E. Lauver at (410) 495-5219.

I declare under penalty of perjury that the foregoing is true and correct. Executed on February 7, 2014.

Very truly yours, GHG/PSF/bJd

Attachment:

(1)

Regulatory Commitments Contained in This Correspondence cc:

N. S. Morgan, NRC Resident Inspector, NRC W. M. Dean, NRC S. Gray, DNR

ATTACHMENT (1)

REGULATORY COMMITMENTS CONTAINED IN THIS CORRESPONDENCE Calvert Cliffs Nuclear Power Plant, LLC February 7,2014

ATTACHMENT (1)

REGULATORY COMMITMENTS CONTAINED IN THIS CORRESPONDENCE The following table identifies actions committed to in this document.

Any other statements in this submittal are provided for information purposes and are not considered to be regulatory commitments.

Regulatory Commitment Due Date Calvert Cliffs commits to providing the following discussion Concurrent with implementation of the in the Updated Final Safety Analysis Report.

approved TSTF-501-A, Revision I license amendment "The specific emergency diesel generator fuel oil volumes (equivalent to duration based requirements) contained in the fuel oil storage tanks referenced in Technical Specification 3.8.3 are calculated using the method provided in American National Standards Institute (ANSI)

N195-1976, Section 5.4, as endorsed by Regulatory Guide 1.137, Revision 1, Section C.l.c.

The fuel oil calculation is based on applying the conservative assumption that the emergency diesel generator is operated continuously at rated capacity. This is one of two approved methods specified in Regulatory Guide 1.137, Revision 1."

1