Ro:During Surveillance Testing,Main Feedwater Piping Snubber & Main Steam Piping Snubber Failed Functional Testing.Caused by Hydraulic Fluid Leakage & Locking Out on Piston Rod Assembly,Respectively.Addl Functional Testing Underway
ML13331B390
Person / Time
Site: San Onofre 
Issue date: 05/14/1980
From: Curran J
SOUTHERN CALIFORNIA EDISON CO.
To:
References
NUDOCS 8005280619
Download: ML13331B390 (2)


Text

REGULATORY INFORMAllON DISTRIBUTION SYSTEM (RTS)

ACCESSION NBR:8005280619 0CDATE: 80/05/14 NOTARIZED; NO DOCKET #

FACIL:50-206 San.0nofre Nuclear Station, Unit 1, Southern Californ 05000206 AUTH.NAME AUTHOR AFFILIATION CURRANJM.

Southern California Edison Co, RECIP.NAME RECIPIENT AFFILIATION

SUBJECT:

RO:during surveillance testingrmain feedwater piping snubber

& main steam piping snubber failed functional testing.Caused by hydraulic fluid leakage & locking out on piston rod assemblyvrespectively.Addl functional testing underway, DISTRIBUTION CODE: M007S COPIES RECEIVED:LTR ENCL J SIZE-.

TITLE: LER (6ackfit)

NOTES RECIPIENT COPIES RECIPIENT COPIES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL INTERNAL: 0 1

02 NRC PDR 1

1 04 I&E 2

AEOD 1

1 BERLINGERC, 1

HANAUERPS, 1

1 MPA 1

1 EXTERNAL: 03 LPDR 1

NSIC 1

MAY 2 9 19G TOTAL NUMBER OF COPIES REQUIRED: LTTR 10 ENCL WA

Southern Callforn/a Ed/son Company SA QMOUSt 5C4.sLAR

,ahgetAT4MQBTO u

P1.

pQA law SAW CLWMEETU. CA1tPOUNIA 92G98 Kay 14, 1980

u. S. Nuclear Regulatory Comnission Office of Inspection and Enforcoent Region V 1990 North California Boulevard Suite 202, Walnut Creek Plaza Walnut Creek, California 94596 Attention: Mr. R. H. Engelken, Director DOCKET No. 60*206 SAN ONOFRE - UNIT I

Dear Sir:

This letter describes a reportable occurrence as defined In Section 6,9.2.a(9) of Appendix A to the Provisional Operating License DPR-13.

During surveillance testing two snubbers located inside containment failed functional testing. The first, a main feedwater piping snubber, failed due to eKcessive hydraulic fluid leakage around the piston rod seal.

The second, a main steam piping snubber, had failed threads and a locking nut on the piston rod assembly. In accordance with Technical Specification 4.14, additional functional testing has been initiated.

A complete report on this matter, together with a Licensee Event Report, will be forwarded to your office within two weeks.

Sincerely, J.

M4.

Curran Plant Manager MPS:dh 8005 280 to'l