Advises That Util Plans to Submit Amend Application in May 1989 to Revise Tech Specs to Reflect New Variable Low Pressure Trip Program Adjusted to Reduce T-average Operation
ML13331B100
Person / Time
Site: San Onofre 
Issue date: 11/15/1988
From: Medford M
Southern California Edison Co
To:
NRC Office of Administration & Resources Management (ARM)
References
TASK-15-07, TASK-15-7, TASK-RR NUDOCS 8811180242
Download: ML13331B100 (1)


Text

Southern California Edison Company P. 0.

BOX 800 2244 WALNUT GROVE AVENUE ROSEMEAD, CALIFORNIA 91770 M.0. MEDFORD TELEPHONE MANAGER OF (818) 302-1749 NUCLEAR REGULATORY AFFAIRS November 15, 1988 U. S. Nuclear Regulatory Commission Attention:

Document Control Desk Washington, D.C. 20555 Gentlemen:

Subject:

Docket No. 50-206 SEP Topic XV-7 San Onofre Nuclear Generating Station Unit 1

Reference:

Letter, M. 0. Medford, SCE, to USNRC, dated July 13, 1988 In the referenced letter, SCE committed to reanalyzing the RCP shaft break transient with a new Variable Low Pressure (VLP) trip program adjusted for reduced T-avg operation. This analysis has been completed and the results demonstrate that with the new VLP trip program, the transient acceptance criteria is met for reduced T-avg operation. The peak RCS pressure reached during the transient is less than that which would cause stresses to exceed the faulted condition stress limits; therefore, the integrity of the primary coolant system is maintained. The peak clad surface temperature calculated for the hot spot during the transient of 2390*F remains less than the Westinghouse acceptance criterion for stainless steel 304 (2450 0F);

therefore, the core will remain in place and intact with no loss of core cooling capability. Additionally, the results show no fuel rods in the core undergo DNB.

SCE plans to submit an amendment application to revise the technical specifications to reflect the new VLP trip program. Shaft break is an open SEP issue; therefore, implementation of any required actions would normally be scheduled in accordance with the Integrated Implementation Schedule (IIS).

Since no plant modifications are required in this case, SCE will submit this amendment application to the NRC in May 1989 so that this issue will be resolved independent of the IIS.

If there are any questions, please contact me.