Text

0

REG-

UNITED STATES

4A

NUCLEAR REGULATORY COMMISSION

3

REGIONV

1450 MARIA LANE

WALNUT CREEK. CALIFORNIA 94596-5368

FEB 2 5 1993

Docket Nos.:

50-206, 50-361 and 50-362

License Nos.: DPR-13,

NPF-10 and NPF-15

Southern California Edison Company

Irvine Operations Center

23 Parker Street

Irvine, California 92718

Attention: Mr. Harold B. Ray

Senior Vice President, Nuclear

SUBJECT:

NOTICE OF VIOLATION

NRC INSPECTION RE ORT NOS. 50-206/93-01, 50-361/93-01 AND 50

362/93-01

This letter refers to the inspection conducted by Messrs. D. Acker and F. Gee

between January 11, 1993, and January 29, 1993, of activities authorized by

NRC License Nos. DPR-13, NPF-10 and NPF-15, and to the discussion of our

findings held with members of your staff on January 29, 1993.

- Specific areas examined during this inspection are described in the enclosed

inspection report. Within these areas, the inspection consisted of selective

examinations of procedures and representative records, and interviews with

personnel.

Based on the results of the inspection, one of your activities appeared to be

in violation of NRC requirements, as specified in the enclosed Notice of

Violation (Notice).

The attached Notice identifies that an emergency diesel generator fuel

storage calculation, issued in June 1991, did not correct an error in the

previous calculation, and that this error was specifically identified to you

in Inspection Report 89-200, dated January 12, 1990. While your preliminary

analysis indicates that diesel fuel oil actually stored on site was

sufficient during the period that the calculation error existed, this error

caused your calculated on-site storage requirement to be short by

approximately 2500 gallons per emergency diesel generator.

You are required to respond to this letter and should follow the instructions

specified in the enclosed Notice when preparing your response. In your

response, you should document the specific action taken and any additional

actions you plan to prevent recurrence. After reviewing your response to

this Notice, including your proposed corrective actions and the results of

future inspections, the NRC will determine whether further NRC enforcement

action is necessary to ensure compliance with NRC regulatory requirements.

9303120009 930225

PDR ADOCK 05000206

0

a

PDR

2

The response directed by this letter is not subject to the clearance

procedures of the Office of Management and Budget as required by the

Paperwork Reduction Act of 1980, Pub. L. No.96-511. In accordance with 10

CFR 2.790(a), a copy of this letter and enclosure will placed in the NRC

Public Document Room.

Should you have any questions concerning this inspection, we will be pleased

to discuss them with you.

Sincerely,

L. F. Miller, Jr., Chief

Reactor Safety Branch

Enclosures:

1. Notice of Violation

2.

Inspection Report Nos. 50-206/93-01, 50-361/93-01 and 50-362/93-01

cc w/enclosures (1) and (2):

H. E. Morgan, Vice President and Site Manager

R. W. Krieger, Jr., Station Manager

State of California (Gordon K. Van Vieck)

I3

bcc w/enclosures (1) and (2):

Docket File

Resident Inspector

Project Inspector

M. Fields, Project Manager

G. Cook

B. Faulkenberry

J. Martin

H. Wong

bcc w/o enclosures (1) and (2):

J. Zollicoffer

M. Smith

Region V/dg

D. Acke

F. Gee

R. Hyey

B. Ang

2 /

93

(/

/93

93

//93

3

[REQUEST COPY] [REQUES

COPY1

[5 YES NO

40,0

0 0

N

N

L. Miller

[RE UEST COPYI

[ E

NO]

[SEK

0T PDR]

r

EM

NO

1

110030