Provides Followup Rept for Tech Spec fire-rated Assemblies Found Inoperable During Dec 1989 Routine Surveillances & Informs That Unit 1 Fire Doors Found Inoperable During Surveillances Now Included in Rept Following Implementation
ML13322B088
Person / Time
Site: San Onofre  
Issue date: 01/16/1990
From: Nandy F
SOUTHERN CALIFORNIA EDISON CO.
To: Martin J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
NUDOCS 9002050096
Download: ML13322B088 (5)


Text

Southern California Edison Company 23 PARKER STREET IRVINE. CALIFORNIA 92718 F. R. NANDY TELEPHONE MANAGER OF NUCLEAR LICENSING January 16, 1990 (714) 5 U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region V 1450 Maria Lane, Suite 210 Walnut Creek, California 94596-5368 Attention:

Mr. J. B. Martin, Regional Administrator

Subject:

Docket Nos. 50-206, 50-361 and 50-362 Followup Report, Inoperable Fire Doors - December 1989 San Onofre Nuclear Generating Station, Units 1, 2 and 3 The purpose of this letter is to provide a follow-up report for Technical Specification (TS) fire-rated assemblies (specifically fire doors) found inoperable during routine surveillances in December 1989. This monthly report and previous monthly reports provide updated information associated with the initial 1983 report for Units 2 and 3. Unit 1 fire doors found inoperable during routine surveillances are now included in this report following implementation, in December 1989, of Amendment 131 to Provisional Operating License No. DPR-13 The enclosed report identifies: a) 2 latching mechanism failures and 1 closure mechanism failure for Unit 1 and, b) 19 latching mechanism failures and 14 closure mechanism failures for Units 2 and 3. As each of these deficiencies was identified, compensatory fire watches were established pursuant to TS 3.14.7, Action "A" for Unit 1 and TS 3.7.9, Action "a" for Units 2 and 3. No doors were found to be blocked open in December.

9)0020500'96 900 116 F'DR A

05000206 P

P DC i\\7

Mr. J.

January 16, 1990 If you require any additional information, please let me know.

Very truly yours, Enclosure cc:

C. W. Caldwell (NRC Senior Resident Inspector, Units 1, 2 and 3)

U. S. Nuclear Regulatory Commission Document Control Desk Institute of Nuclear Power Operations (INPO)

ATTACHMENT SOUTHERN CALIFORNIA EDISON COMPANY INOPERABLE FIRE DOORS FOR THE MONTH OF DECEMBER 1989 SAN ONOFRE NUCLEAR GENERATING STATION UNIT 1, DOCKET NO. 50-206 I.

Latching Mechanism Failures:

Number of doors inoperable - 2, as follows:

Door Number Inoperable Operable S1-FBD-148 11/29/89 12/09/89 S1-FBD-130 12/13/89 II.

Closure Mechanism Failures:

Number of doors inoperable - 1, as follows:

Door Number Inoperable Operable S1-FBD-148 11/29/89 12/08/89 III.

Doors Blocked Open:

Number of doors blocked open -

None fdr.dec/1

ATTACHMENT SOUTHERN CALIFORNIA EDISON COMPANY INOPERABLE FIRE DOORS FOR THE MONTH OF DECEMBER 1989 SAN ONOFRE NUCLEAR GENERATING STATION UNITS 2 AND 3, DOCKET NOS. 50-361 AND 50-362 I.

Latching Mechanism Failures:

Number of doors inoperable - 19, as follows:

Door Number Inoperable Operable AC-108 08/16/89 12/06/89 AC-428 09/21/89 FH2-101 10/10/89 AC-325 10/24/89 12/21/89 C3-406 11/15/89 12/08/89 FH2-404 11/28/89 AC-349 12/06/89 12/15/89 AC-107 12/07/89 S2-016 12/07/89 S3-016 12/07/89 AC-223 12/13/89 AR-504 12/14/89 AC-239 12/18/89 12/26/89 FH2-404 12/28/89 AC-349 12/29/89 FH3-303 12/29/89 FH3-403 12/29/89 S2-018 12/29/89 AC-101 12/31/89 fdr.dec/2

ATTACHMENT SOUTHERN CALIFORNIA EDISON COMPANY INOPERABLE FIRE DOORS FOR THE MONTH OF NOVEMBER 1989 SAN ONOFRE NUCLEAR GENERATING STATION UNITS 2 AND 3, DOCKET NOS. 50-361 AND 50-362 II.

Closure Mechanism Failures:

Number of doors inoperable - 14, as follows:

Door Number Inoperable Operable AC-119 04/30/89 12/01/89 AC-108 08/16/89 12/06/89 AC-428 10/10/89 AC-242 11/02/89 S2-018 11/19/89 12/08/89 C3-406 11/25/89 12/08/89 FH2-404 11/28/89 AC-108 11/29/89 12/06/89 S2-016 12/07/89 S3-016 12/07/89 AC-402 12/12/89 12/15/89 AC-458 12/12/89 12/15/89 AC-218 12/14/89 AC-119 12/27/89 III.

Doors Blocked Open:

Number of doors blocked open -

None fdr.dec/3