Disagrees W/Nrc Re Masonry Wall Evaluations Under SEP Topic III-6.Nonlinear Inelastic Time History Analyses Demonstrate Capacity of Masonry Walls to Withstand 0.67g Housner Ground Motion.Addl Info Will Be Submitted 820430
ML13317B038
Person / Time
Site: San Onofre Southern California Edison icon.png
Issue date: 03/15/1982
From: Baskin K
Southern California Edison Co
To: Crutchfield D
Office of Nuclear Reactor Regulation
References
TASK-03-06, TASK-3-6, TASK-RR NUDOCS 8203170539
Download: ML13317B038 (2)


Text

Southern California Edison Company P. 0. BOX 800 2244 WALNUT GROVE AVENUE ROSEMEAD. CALIFORNIA 91770 K. P. BASKIN TELEPHONE MANAGER OF NUCLEAR ENGINEERING, March 15, 1982 1401 SAFETY, AND LICENSING Director, Office of Nuclear Reactor Regulation Attention:

D. M. Crutchfield, Chief Operating Reactors Branch No. 5 MAR 61982o.

Division of Licensing U. S. Nuclear Regulatory Commission Washington, D.C.

20555 Gentlemen:

Subject:

Docket 50-206 Masonry Wall Evaluations SEP Topic 111-6 Seismic Design Considerations San Onofre Nuclear Generating Station Unit 1 By letters dated January 11 and 15, 1982, we provided three reports describing the seismic reevaluation of masonry walls at San Onofre Unit 1.

On January 20, 1982 we met with the NRC staff to further describe the methods used for these evaluations.

In a letter dated February 17, 1982, the NRC staff stated that the non-linear inelastic time history analysis methodology could not be accepted as the sole basis for evaluation and qualification of the masonry walls. That letter further identified two options for timely completion of the masonry wall evaluations:

(a) a limited scope test program, or (b) elastic evaluation and modification as necessary of the masonry walls.

The letter further indicated that the second option is considered by the staff to be the more desirable and preferred from the standpoint of practicality and cost-effectiveness.

We have reviewed the NRC's February 17 letter and the basis for the conclusions therein. We disagree with the conclusions in that letter and we maintain that the inelastic analyses we have performed demonstrate the capacity of the masonry walls to withstand a 0.67g Housner ground motion.

It was our view at the time of the January 20 meeting, and still is, that we could respond to the NRC comments and demonstrate the adequacy of our approach. Therefore, we consider it appropriate for us to respond to the specific comments raised at the January 20 meeting and reiterated in the February 17 letter.

r 8203170539 820315 PDR ADOCK 05000206 t'.

PpDR

Mr. D.

March 15, 1982 As noted above, the NRC's February 17 letter identified two proposed options. We have examined those options along with other options for completion of the masonry wall evaluations.

We conclude that further testing of masonry walls to validate the inelastic methodology (option a) is not necessary and we would intend to respond to this issue further in our response to the specific NRC comments. Furthermore, we conclude that performance of an elastic linear analysis of the walls and implementation of modifications (option b) is neither practical nor cost-effective. Implementation of

-structural modifications required to force some of the masonry walls into the elastic range could be sufficient to require large scale reanalysis of some structures. This would impact the overall completion schedule for the seismic reevaluation of the San Onofre Unit 1 structures.

In view of the above, in order to respond to the NRC staff's stated concern that our non-linear time history analysis cannot be accepted as the sole basis for evaluation and qualification of the masonry walls, we propose to perform an alternate analysis utilizing the inelastic spectrum method as described in NUREG/CR-0098, "Development of Criteria for Seismic Review of Selected Nuclear Power Plants" and in Section 3.8.4.5.2 of our "Balance of Plant Structures Seismic Reevaluation Criteria" which was submitted to the NRC by letter dated February 23, 1981. This method relies solely on the elastic properties of the elements of the masonry walls, as defined by ASTM and ACI standards, to compute the member ductility associated with each wall segment.

This additional analysis will, therefore, provide a separate and independent basis for evaluation of the masonry walls.

In summary, we do not agree with the NRC conclusion that the analyses submitted to-date are inadequate for qualification of the masonry walls at San Onofre Unit 1 nor do we propose to pursue either of the options suggested by the NRC staff in their February 17, 1981 letter.

Rather, we propose to respond to the technical comments raised by the NRC staff and to perform an alternate analysis of the masonry walls in accordance with the inelastic spectrum method. We anticipate being able to submit this information to the NRC staff by about April 30, 1982. We believe that these actions will permit an expeditious completion of the review of the masonry walls at San Onofre Unit 1.

If you wish to further discuss this matter, please let us know.

Very truly yours,