MONTHYEARML12168A0012012-06-0808 June 2012 NRR E-mail Capture - Draft RAIs on VC Summer NFPA-805 Review Project stage: Draft RAI ML12202A0272012-07-26026 July 2012 Request for Additional Information Project stage: RAI RC-12-0142, License Amendment Request - LAR-06-00055, License Amendment Request to Adopt NFPA 805, Response to Request for Additional Information2012-10-10010 October 2012 License Amendment Request - LAR-06-00055, License Amendment Request to Adopt NFPA 805, Response to Request for Additional Information Project stage: Response to RAI RC-13-0017, License Amendment Request - LAR-06-00055, License Amendment Request to Adopt NFPA 805, Additional Information Regarding Response to Request for Additional Information2013-02-0101 February 2013 License Amendment Request - LAR-06-00055, License Amendment Request to Adopt NFPA 805, Additional Information Regarding Response to Request for Additional Information Project stage: Response to RAI ML13142A1572013-05-29029 May 2013 Update for 06/20/13 Meeting Notice with South Carolina Electric & Gas Company Regarding Voluntary Fire Protection Risk Initiative Self Assessment Project stage: Request ML13170A1192013-06-18018 June 2013 Public Slide - Control Room Evacuation Due to Fire, Based on NFPA 805 Project stage: Other ML13170A1302013-06-18018 June 2013 Public Slide - NFPA 805 Transient Combustible Controls Project stage: Other ML13199A1772013-07-31031 July 2013 Summary, June 20, 2013 Category 1 Meeting with South Carolina Electric and Gas Company, to Discuss Voluntary Fire Protection Risk Initiative Self-Assessment Project stage: Meeting ML13218A1952013-08-13013 August 2013 (VCSNS) - Request for Additional Information Project stage: RAI ML13234A4422013-08-28028 August 2013 (VCSNS) - Request for Additional Information Project stage: RAI RC-13-0142, License Amendment Request to Adopt NFPA 805, Response to Request for Additional Information2013-10-14014 October 2013 License Amendment Request to Adopt NFPA 805, Response to Request for Additional Information Project stage: Response to RAI ML13308B8002013-11-0707 November 2013 (VCSNS) - Request for Additional Information Project stage: RAI ML13347B0492013-12-19019 December 2013 (VCSNS) - Request for Additional Information Project stage: RAI ML14014A2352014-01-0909 January 2014 Annual Letter - Generic Fundamentals Examination (GFE) Section for Region II Project stage: Request RC-14-0002, Response to Request for Additional Information Regarding License Amendment to Adopt NFPA 8052014-01-0909 January 2014 Response to Request for Additional Information Regarding License Amendment to Adopt NFPA 805 Project stage: Response to RAI ML14056A5762014-02-25025 February 2014 Single Positive Test Form, for Pre-Access, Collected on 04/22/2013 Project stage: Request RC-14-0027, License Amendment Request- LAR-06-00055, License Amendment Request to Adopt NFPA 805, Response to Request for Additional Information2014-02-25025 February 2014 License Amendment Request- LAR-06-00055, License Amendment Request to Adopt NFPA 805, Response to Request for Additional Information Project stage: Response to RAI ML14071A1692014-03-24024 March 2014 Request for Additional Information Project stage: RAI RC-14-0067, License Amendment Request - LAR-06-00055, License Amendment Request to Adopt NFPA 805 Response to Request for Additional Information2014-05-0202 May 2014 License Amendment Request - LAR-06-00055, License Amendment Request to Adopt NFPA 805 Response to Request for Additional Information Project stage: Response to RAI RC-14-0083, License Amendment Request - LAR-06-00055, License Amendment Request to Adopt NFPA 805 - Response to Request for Additional Information2014-05-11011 May 2014 License Amendment Request - LAR-06-00055, License Amendment Request to Adopt NFPA 805 - Response to Request for Additional Information Project stage: Response to RAI ML14182A4732014-07-11011 July 2014 Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: RAI RC-14-0129, Response to Request for Additional Information on License Amendment Request LAR-06-00055 and to Adopt NFPA 8052014-08-14014 August 2014 Response to Request for Additional Information on License Amendment Request LAR-06-00055 and to Adopt NFPA 805 Project stage: Response to RAI ML14311A1402014-11-0707 November 2014 Final VC Summer Iepra Ror 10-10-2014.docx Project stage: Request RC-14-0196, License Amendment Request LAR-06-00055 - License Amendment Request to Adopt NFPA 805 Response to Request for Additional Information2014-12-11011 December 2014 License Amendment Request LAR-06-00055 - License Amendment Request to Adopt NFPA 805 Response to Request for Additional Information Project stage: Response to RAI ML14287A2892015-02-11011 February 2015 Issuance of Amendment Regarding Transition to a Risk-Informed, Performance-Based Fire Protection Program in Accordance with 10 CFR 50.48(c) Project stage: Approval ML15041A1682015-02-13013 February 2015 Summary of Site Audit to Support the Review of a License Amendment Request for Virgil C. Summer Nuclear Station, Unit 1, to Transition to the National Fire Protection Association Standard 805 Fire Protection Licensing Basis Project stage: Approval 2013-08-28
[Table View] |
Text
Security - Related Information -
Thomas D. Gatlin Withhold Under 10 CFR 2.390 Vice President, Nuclear Operations 803.345.4342 A SCANA COMPANY October 14, 2013 RC-1 3-0142 U.S. Nuclear Regulatory Commission Document Control Desk Washington, D.C. 20555-0001 Attn: S. A. Williams
Dear Sir or Madam:
Subject:
VIRGIL C. SUMMER NUCLEAR STATION (VCSNS) UNIT 1 DOCKET NO. 50-395 OPERATING LICENSE NO. NFP-12 LICENSE AMENDMENT REQUEST-LAR-06-00055 LICENSE AMENDMENT REQUEST TO ADOPT NFPA 805 RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION
References:
- 1. Thomas D. Gatlin, SCE&G, Letter to NRC Document Control Desk, License Amendment Request - LAR-06-00055, "License Amendment Request to Adopt NFPA 805 Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants (2001 Edition)" dated November 15, 2011 (RC-11-0149)
- 2.
Robert E. Martin, NRC, to Thomas D. Gatlin "Virgil C. Summer Nuclear Station Unit - 1 (VCSNS) - Request for Additional Information (TAC NO. ME7586)"
dated August 13, 2013 [ML13218A195]
- 3.
Letter from Thomas D. Gatlin to NRC Document Control Desk, "Notification of an Intended Change to a Commitment Date for NFPA 805 Emergency Communication System Made in LAR 06-00055" dated May 13, 2013 (RC 0061)
- 4. Thomas D. Gatlin Letter to NRC Document Control Desk, License Amendment Request - LAR-06-00055 License Amendment Request to Adopt NFPA 805 Response to Request for Additional Information" dated October 10, 2012 (RC-12-0142)
South Carolina Electric & Gas Company (SCE&G), acting for itself and as agent for South Carolina Public Service Authority pursuant to 10 CFR 50.90, submitted a License Amendment Request (LAR) per Reference 1 to adopt NFPA 805. NRC review and audit of this request determined that additional information was required When Separated from Attachments, this Transmittal Document is Decontrolled.
Ac t
Virgil C. Summer Station
- Post Office Box 88. Jenkinsville, SC
Document Control Desk LAR-06-00055 RC-1 3-0142 Page 2 of 3 and a Request for Additional Information (RAI) was issued per Reference 2.
Attachments 1 and 2 of this letter provide SCE&G's response to the RAIs.
In addition to responding to RAIs, SCE&G has revised LAR Attachments L and S, which are included as Attachments 3 and 4 of this letter. These attachments replace all previous versions in their entirety. reflects additional defense-in-depth discussions per RAI FPE 14.02 response, and two new additional approval requests. Approval request L12 is a new request related to the potential for oil misting from the reactor coolant pumps. Approval request L13, generated per RAI FPE 14.01 response, is a new request related to use of a performance-based method to establish inspection, testing, and maintenance frequencies for fire protection systems and features generated per RAI FPE 14.01 response. reflects editorial corrections of ECR numbers for penetration seal documentation and a communication upgrade. The 2014 completion date for this communication upgrade is provided in Reference 3. Two Implementation Items have also been added to Table S-2 (Reference 4) in response to PRA RAI 35 and PRA RAI 13. "List of Commitments" reflects the revisions of the ECR number for penetration seal documentation and the due date for Implementation Items (based on Item 22, added per response to PRA 13).
If you have any questions about this submittal, please contact Mr. Bruce L. Thompson at (803) 931-5042.
I certify under penalty of perjury that the foregoing is correct and true.
Executed on Thomas D. Gatlin RLP/TDG/wm
Document Control Desk LAR-06-00055 RC-1 3-0142 Page 3 of 3 Attachments:
- 1. Fire Modeling (FM) Request for Additional Information (RAI) Responses
- 2.
Fire Protection Engineering (FPE) Request for Additional Information (RAI)
Responses
- 3.
LAR Attachment L - NFPA 805 Chapter 3 Requirements for Approval (10 CFR 50.48(c)(2)(vii))
- 4.
LAR Attachment S - Plant Modifications and Items to be Completed During Implementation.