Text
July 29, 2013 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Peach Bottom Atomic Power Station, Units 2 and 3 10 CFR 50.55a Renewed Facility Operating License Nos. DPR-44 and DPR-56 NRC Docket Nos. 50-277 and 50-278
Subject:
Request for Relief from ASME OM Code 5-Year Test Interval for Class 1 Safety Relief Valves/Safety Valves (SRVs/SVs) (Relief Request 01A-VRR-3)
Attached for your review is Relief Request 01 A-VRR-3 associated with the fourth In service Testing (1ST) interval for Peach Bottom Atomic Power Station (PBAPS), Units 2 and 3. The fourth interval of the PBAPS, Units 2 and 3, 1ST program complies with the American Society of Mechanical Engineers (ASME) Code for Operation and Maintenance of Nuclear Power Plants, 2001 Edition with Addenda through 2003 Addenda. This relief request would implement ASME OM Code Case OMN-17. We request your approval by July 29, 2014.
There are no regulatory commitments in this letter.
If you have any questions concerning this letter, please contact Tom Loomis at (610) 765-5510.
Res~:~
James Barstow Director, Licensing & Regulatory Affairs Exelon Generation Company, LLC
Attachment:
Relief Request 01A-VRR-3 cc:
Regional Administrator, Region I, USNRC USNRC Senior Resident Inspector, PBAPS Project Manager, USNRC
AlTACHMENT RELIEF REQUEST 01 A.VRR-3
10 CFR 50.55a RELIEF REQUEST: 01 A-VRR-3 Revision 0 (Page 1 of 8}
Proposed Alternative to Utilize Code Case OMN-17 In Accordance with 10 CFR 50.55a(a)(3)(i)
- 1.
ASME Code Component(s) Affected Pump Description Class Category RV-2-02-070A Main Steam Safety Valve 1
c RV-2-02-0708 Main Steam Safety Valve 1
c RV 02-071 A Main Steam Safety Relief Valve 1
c RV-2-02-071 B Main Steam Safety Relief Valve 1
c RV-2-02-071 C Main Steam Safety_ Relief Valve 1
c RV 02-071 0 Main Steam Safety Relief Valve 1
c RV-2-02-071 E Main Steam Safety Relief Valve 1
c RV-2-02-071 F Main Steam Safety Relief Valve 1
c RV-2-02-071 G Main Steam Safety Relief Valve 1
c RV-2-02-071 H Main Steam Safety Relief Valve 1
c RV 02-071 J Main Steam Safety: Relief Valve 1
c RV-2-02-071 K Main Steam Safety Relief Valve 1
c RV-2-02-071 L Main Steam Safety Relief Valve 1
c RV-3-02-070A Main Steam Safety Valve 1
c RV-3-02-0708 Main Steam Safety Valve 1
c RV-3-02-071A Main Steam Safety Relief Valve 1
c RV-3-02-071 B Main Steam Safety Relief Valve 1
c RV-3-02-071 C Main Steam Safety Relief Valve 1
c RV-3-02-071 0 Main Steam Safety Relief Valve 1
c RV-3-02-071 E Main Steam Safety Relief Valve 1
c RV-3-02-071 F Main Steam Safety Relief Valve 1
c RV-3-02-071 G Main Steam Safety Relief Valve 1
c RV-3-02-071 H Main Steam Safety Relief Valve 1
c RV-3-02-071 J Main Steam Safety Relief Valve 1
c RV-3-02-071 K Main Steam Safety Relief Valve 1
c RV-3-02-071 L Main Steam Safety Relief Valve 1
c Component/System Function Unit 2
2 2
2 2
2 2
2 2
2 2
2 2
3 3
3 3
3 3
3 3
3 3
3 3
3 The ASME Code requires the reactor pressure vessel be protected from overpressure during upset conditions by self-actuated safety valves. As part of the nuclear pressure relief system, the size and number of Safety Relief Valves (SRVs) and Safety Valves (SVs) are selected such that peak pressure in the nuclear system will not exceed the ASME Code limits for the Reactor Coolant Pressure Boundary (RCPB).
The SRVs are Target Rock three-stage pilot operated safety/relief valves (11 SRVs per unit). The SVs are Dresser spring loaded safety valves (2 SVs per unit). The SRVs and SVs are located on the main steam lines between the reactor vessel and the first isolation valve within the drywell. The SRVs can actuate by either of two modes: the safety mode or the depressurization mode. In the safety mode, the pilot disc opens when steam
10 CFR 50.55a RELIEF REQUEST: 01 A-VRR-3 Revision 0 (Page 2 of 8) pressure at the valve inlet expands the bellows to the extent that the hydraulic seating force on the pilot disc is reduced to zero. Opening of the pilot stage allows a pressure differential to develop across the second stage disc which opens the second stage disc, thus venting the chamber over the main valve piston. This causes a pressure differential across the main valve piston which opens the main valve. The SVs are spring loaded valves that actuate when steam pressure at the inlet overcomes the spring force holding the valve disc closed. This satisfies the Code requirement. The proposed changes do not impact the depressurization mode function of the SRVs.
- 2.
Applicable Code Edition and Addenda
ASME OM Code-2001 Edition through 2003 Addendum
- 3.
Applicable Code Reguirement(s)
ASME OM Code Mandatory Appendix I, "lnservice Testing of Pressure Relief Devices in Light-Water Reactor Nuclear Power Plants," Section 1-1320, "Test Frequencies, Class 1 Pressure Relief Valves," paragraph (a), "5-Year Test Interval," states that Class 1 pressure relief valves shall be tested at least once every 5 years.
- 4.
Reason for Request
Section ISTC-3200, "lnservice Testing," states that inservice testing shall commence when the valves are required to be operable to fulfill their required function(s). Section ISTC-5240, "Safety and Relief Valves," directs that safety and relief valves meet the inservice testing requirements set forth in Appendix I of the ASME OM Code.
Appendix I, Section l-1320(a) of the ASME OM Code states that Class 1 pressure relief valves shall be tested at least once every 5 years, starting with initial electric power generation. This section also states a minimum of 20 percent of the pressure relief valves are tested within any 24-month interval and that the test interval for any individual valve shall not exceed 5 years. The required tests ensure that the SRVs/SVs, which are located on each of the main steam lines between the reactor vessel and the first isolation valve within the drywell, will open at the pressures assumed in the safety analysis.
The SRVs/SVs have shown acceptable test history at Peach Bottom Atomic Power Station (PBAPS), Units 2 and 3 as described in Section 5 below.
However, given the current 24-month operating cycle for each PBAPS unit, Exelon Generation Company, LLC (Exelon) is required to remove and test approximately half of the SRVs/SVs every refueling outage in order to ensure that all valves are removed and tested in accordance with the ASME OM Code requirements. This ensures compliance with the ASME OM Code requirements for testing Class 1 pressure relief valves within a 5 year interval. With the current 5 year interval, PBAPS is required to remove all 13 SRVs/SVs over 2 refuel cycles (i.e., 4 years). Approval of extending the test interval to 6.5 years would reduce the number of SRVs/SVs removed during an individual outage, such that the full scope of 13 SRVs/SVs are replaced over 3 refuel cycles (i.e., 6 years).
Without Code relief, the incremental outage work due to the inclusion of the additional 2-3 SRVs/SVs per outage would be contrary to the principle of maintaining radiation dose As Low As Reasonably Achievable (ALARA). The removal and replacement of the additional
1 0 CFR 50.55a RELIEF REQUEST: 01 A-VRR-3 Revision 0 (Page 3 of 8) 2-3 SRVs/SVs per outage without Code relief results in an additional exposure of approximately 2Y2 - 4 Rem each outage.
In accordance with 10 CFR 50.55a(a)(3)(i), Exelon requests approval of an alternative to the 5 year test interval requirements of ASME OM Code, Appendix I, Section l-1320(a) for the SRVs/SVs at PBAPS, Units 2 and 3. Exelon requests that the test interval be increased from 5 years to 6.5 years. All other requirements of the applicable ASME OM Code would be met.
- 5.
Proposed Alternative and Basis for Use As an alternative to the Code required 5-year test interval per Appendix I, paragraph l-1320(a), Exelon proposes that the subject Class 1 pressure relief valves be tested at least once every three refueling cycles (approximately 6 years/72 months) with a minimum of 20% of the valves tested within any 24-month interval. This 20% would consist of valves that have not been tested during the current 72-month interval, if they exist. The test interval for any individual valve would not exceed 72 months except that a 6-month grace period is allowed to coincide with refueling outages to accommodate extended shutdown periods and certification of the valve prior to installation.
After as-found set-pressure testing, the valves shall be disassembled and inspected to verify that parts are free of defects resulting from time-related degradation or service induced wear. As-left set-pressure testing shall be performed following maintenance and prior to returning the valve to service. Each valve shall have been disassembled and inspected prior to the start of the 72-month interval. Disassembly and inspection performed prior to the implementation of Code Case OMN-17 may be used.
The relief valve testing and maintenance cycle at PBAPS consists of removal of the SRV/SV complement requiring testing and transportation to an off-site test facility. Upon receipt at the off-site facility the valves are subject to an as-found inspection and set-pressure testing. Prior to the return of a complement of SRVs/SVs for installation in the plant, the valves are disassembled and inspected to verify that internal surfaces and parts are free from defects or service induced wear prior to the start of the next test interval.
During this process, anomalies or damage are identified for resolution. Damaged or worn parts, springs, gaskets and seals are replaced as necessary. Following reassembly, the valve's set pressure is recertified. This existing process is in accordance with ASME OM Code Case OMN-17 paragraphs (d) and (e). Exelon has reviewed the as-found set point test results for all of the SRVs/SVs tested since 2000 as detailed in Table 1.
Since 2000, the PBAPS, Units 2 and 3 SRVs/SVs have a history of 96 as-found lift tests.
Of these 96 tests, 99% have been found within a +/-3% tolerance. During the PBAPS Fall 2012 Unit 2 refueling outage, one of the main steam SVs (SIN 1 095) as-found lift pressure was identified to be 3.4% above the setpoint. An expanded scope removal of the other SV was performed with a satisfactory lift (the S/N 1093 as-found test (November 2012) was exactly at set pressure). An investigation was performed regarding the one valve that lifted outside of a +/-3% tolerance. It was identified that the previous certification practices were not using currently best known practices; procedure enhancements have been implemented to prevent future recurrence. Additionally, PBAPS has implemented
10 CFR 50.55a RELIEF REQUEST: 01 A-VRR-3 Revision 0 (Page 4 of 8) enhanced subcomponent replacement and testing criteria to provide further assurance of repeatable as-found lift results.
Accordingly, the proposed alternative of increasing the test interval for the subject Class 1 pressure relief valves from 5 years to 3 fuel cycles (approximately 6 years/72 months) would continue to provide an acceptable level of quality and safety while restoring the operational and maintenance flexibility that was lost when the 24-month fuel cycle created the unintended consequences of more frequent testing. This proposed alternative will continue to provide assurance of the valves' operational readiness and provides an acceptable level of quality and safety pursuant to 10 CFR 50.55a(a)(3)(i).
- 6.
Duration of Proposed Alternative The proposed alternative identified will be utilized during the fourth 1ST interval which began on August 15, 2008 and will conclude on August 14, 2018.
- 7.
Precedents Monticello Nuclear Generating Plant Relief Request VR-04 was approved in a Nuclear Regulatory Commission Safety Evaluation Report dated September 26, 2012 (ML12244A272).
Quad Cites Nuclear Power Station, Units 1 and 2 Relief Request RV-05 was approved in a Nuclear Regulatory Commission Safety Evaluation Report dated February 14, 2013 (ML13042A348).
Valve Install Install Number Unit Location 15 2
71K 3
71K 2
71B 16 3
71E 2
710 3
71E 17 2
71L 3
71G 2
71H 18 2
71E 3
710 2
710 3
710 19 2
71C 3
71C 2
71F 20 3
71G 2
71J 21 2
71G 3
71H 3
71G 22 3
71F 2
71F 23 3
710 2
710 24 3
71B 3
71A 2
71A TABLE 1 RELIEF VALVE HISTORY (Page 5 of 8)
As-Found Removal/ Test Set Pressure Date Sep-02 1155 Sep-07 1155 Sep-12 1155 Sep-01 1135 Feb-05 1135 Sep-09 1135 Sep-02 1145 Sep-07 1145 Sep-12 1145 Sep-00 1135 Sep-03 1135 Sep-06 1135 Jan-09 1135 Sep-02 1135 Sep-07 1135 Sep-12 1135 Sep-03 1145 Sep-10 1145 Sep-00 1145 Sep-05 1145 Sep-09 1145 Sep-03 1135 Sep-08 1135 Sep-05 1135 Sep-08 1135 Sep-03 1155 Sep-09 1155 Sep-12 1155 As-Found Set Deviation Pressure 1155 0.0%
1167 1.0%
1144
-1.0%
1149 1.2%
1138 0.3%
1129
-0.5%
1149 0.3%
1152 0.6%
1111
-3.0%
1129
-0.5%
1136 0.1%
1130
-0.4%
1127
-0.7%
1128
-0.6%
1149 1.2%
1116
-1.7%
1130
-1.3%
1137
-0.7%
1136
-0.8%
1129
-1.4%
1127
-1.6%
1126
-0.8%
1133
-0.2%
1114
-1.9%
1134
-0.1%
1139
-1.4%
1130
-2.2%
1121
-2.9%
Valve Install Install Number Unit Location 25 3
71K 2
718 3
718 73 3
71J 3
71H 77 3
71L 2
71H 78 2
71H 2
71L 3
71J 79 3
71A 2
71A 3
710 81 2
710 3
71F 2
71E 82 3
71G 3
71J 2
71G 83 3
710 2
71C 3
71F 84 3
71C 2
71E 3
71A 85 2
71J 3
71L 2
710 TABLE 1 RELIEF VALVE HISTORY (Page 6 of 8)
As-Found Removal I Test Set Pressure Date Sep-03 1155 Sep-08 1155 Nov-10 1155 Sep-03 1145 Sep-09 1145 Sep-03 1145 Sep-08 1145 Sep-00 1145 Sep-06 1145 Sep-11 1145 Sep-01 1155 Sep-06 1155 Sep-11 1135 Sep-02 1135 Sep-07 1135 Sep-12 1135 Sep-01 1145 Sep-07 1145 Sep-12 1145 Sep-01 1135 Sep-06 1135 Sep-11 1135 Sep-03 1135 Sep-08 1135 Sep-11 1155 Sep-02 1145 Sep-07 1145 Sep-10 1135 As-Found Set Deviation Pressure 1153
-0.2%
1163 0.7%
1144
-1.0%
1137
-0.7%
1137
-0.7%
1151 0.5%
1151 0.5%
1128
-1.5%
1142
-0.3%
1137
-0.7%
1130
-2.2%
1161 0.5%
1125
-0.9%
1126
-0.8%
1148 1.1%
1103
-2.8%
1151 0.5%
1137
-0.7%
1127
-1.6%
1135 0.0%
1134
-0.1%
1122
-1.1%
1144 0.8%
1128
-0.6%
1152
-0.3%
1141
-0.3%
1149 0.3%
1127
-0.7%
Valve Install Install Number Unit location 87 2
71H 2
71A 88 2
71B 3
71B 145 3
71H 2
71G 174 2
71A 3
71B 2
71K 178 2
71G 2
71L 179 2
71B 3
71A 3
71K 180 2
71E 3
710 182 2
71F 2
71C 183 2
71A 2
71K 190 2
71J 3
71L 193 2
71F 3
71E 3
71C 1093 2
70B 3
70B TABLE 1 RELIEF VALVE HISTORY (Page 7 of 8)
As-Found Removal/ Test Set Pressure Date Sep-04 1145 Sep-10 1155 Sep-04 1155 Sep-09 1155 Sep-01 1145 Sep-08 1145 Sep-02 1155 Sep-05 1155 Sep-10 1155 Sep-04 1145 Sep-10 1145 Sep-00 1155 Sep-05 1155 Sep-09 1155 Sep-04 1135 Feb-08 1135 Sep-04 1135 Sep-10 1135 Sep-00 1155 Sep-06 1155 Sep-06 1145 Sep-11 1145 Sep-00 1135 Sep-05 1135 Sep-09 1135 Sep-04 1260 Sep-09 1260 As-Found Set Deviation Pressure 1149 0.3%
1150
-0.4%
1152
-0.3%
1158 0.3%
1130
-1.3%
1169 2.1%
1144
-1.0%
1136
-1.6%
1165 0.9%
1144
-0.1%
1157 1.0%
1170 1.3%
1142
-1.1%
1154
-0.1%
1124
-1.0%
1135 0.0%
1138 0.3%
1154 1.7%
1146
-0.8%
1165 0.9%
1151 0.5%
1129
-1.4%
1158 2.0%
1145 0.9%
1134
-0.1%
1270 0.8%
1268 0.6%
Valve Install Install Number Unit Location 2
70A 1095 3
708 3
70A 2
70B 1102 2
70B 2
70A 3
708 1103 2
70A 2
708 1104 2
70A 3
708 1105 3
70A 3
70A TABLE 1 RELIEF VALVE HISTORY (Page 8 of 8)
As-Found Removal I Test Set Pressure Date Nov-12 1260 Sep-01 1260 Sep-07 1260 Sep-12 1260 Sep-00 1260 Sep-06 1260 Sep-11 1260 Sep-02 1260 Sep-08 1260 Sep-10 1260 Sep-05 1260 Sep-03 1260 Sep-09 1260 As-Found Set Pressure 1260 1268 1286 1303 1267 1288 1252 1249 1257 1296 1260 1278 1265
- S/N 1095-As-found deviation greater than +3% is discussed in the Relief Request Deviation 0.0%
0.6%
2.1%
- 3.4%
0.6%
2.2%
-0.6%
-0.9%
-0.2%
2.9%
0.0%
1.4%
0.4%