McGuire Nuclear Station Units 1 & 2 Proposed Relief Request 13-MN-002 Risk-Informed/Safety Based (RIS_B)

ISI Alternative for Class 1 and 2 Piping Pre-Submittal Meeting with NRC 7/30/13 1

07/30/2013

Proposed RR 13-MN-002 Pre-Submittal Meeting

  • Purpose of this RR is to request the use of RIS_B ISI for Class 1 and 2 piping
  • A lot of precedents available (see Slide 7)
  • Need NRC approval by end of July 2014 to support next Unit 1 outage in September of 2014
  • Plan to submit this RR by 8/13/13
  • If approved by NRC, Unit 1 weld exam scope in 1EOC23 will be significantly reduced 2

07/30/2013

Proposed RR 13-MN-002 Pre-Submittal Meeting

  • Dose saving for the site
  • RR structure

- Standard RR items (see Slides 4-7)

- Template: Application of N-716 (see Slides 8-10)

- Attachment A: McGuire PRA Quality Review (see Slides 10-12) 3 07/30/2013

Proposed RR 13-MN-002 Pre-Submittal Meeting

  • ASME Code Components Affected:

- Classes 1 and 2

- Exam Categories: B-F, B-J, C-F-1, and C-F-2

  • Applicable Code Edition and Addenda:

- Unit 1: 1998 Edition with 2000 Addenda for Period 1; same Code of Record for Unit 2 4th Interval for Periods 2 and 3.

- Unit 2: 2007 Edition with 2008 Addenda 4

07/30/2013

Proposed RR 13-MN-002 Pre-Submittal Meeting

Reason for Request

Use Risk-Informed/Safety Based (RIS_B) ISI process in lieu of traditional Section XI requirements By focusing inspections on the most safety-significant welds, the number of inspections can be reduced while maintaining protection of public health and safety Proposed Alternative and Basis for Use RIS_B is based on Code Case N-716 N-716 is based, in large part, on NRC-Approved EPRI TR 112657 Rev. B-A EPRI TR 112657 Rev. B-A satisfies RG 1.174 and RG 1.178 EPRI TR 112657 Rev. B-As steps applied to RIS-B RR:

Scope Definition Consequence Evaluation Degradation Mechanism Evaluation Piping Segment Definition Risk Categorization Inspection/NDE Selection Risk Impact Assessment Implementation and Feedback 5

07/30/2013

Proposed RR 13-MN-002 Pre-Submittal Meeting

- N-716:

  • Replaces detailed evaluation of each piping segments safety significance with a generic population of high safety significant (HSS) segments based on exhaustive risk informed ISI experience to date
  • Low safety significant (LSS) welds shall include all other class 2, 3 or non-class welds not classified as HSS

- All piping components subject to current ASME requirements, regardless of risk classification, will continue to receive ASME pressure testing 6

07/30/2013

Proposed RR 13-MN-002 Pre-Submittal Meeting

  • Duration of Proposed Alternative

- Both units: duration of the 4th ISI Intervals

  • Precedents

- Vogtle 1&2

- DC Cook 1&2

- Grand Gulf

- Waterford

- North Anna

- Calvert Cliffs 1&2

- River Bend

- ANO 1&2

- Ginna

- Farley 1&2 7

07/30/2013

Proposed RR 13-MN-002 Pre-Submittal Meeting

  • Template: Application of ASME N-716 (by Structural Integrity, Inc. except where stated otherwise)

- Introduction

  • PRA Quality (by Duke)

- Proposed Alternative to Current ISI Program

  • Augmented Programs 8

07/30/2013

Proposed RR 13-MN-002 Pre-Submittal Meeting

- RIS_B ISI Process

  • Safety Significance Determination
  • Failure Potential Assessment
  • Element and NDE Selection

- Current Examinations

- Successive Examinations

- Scope Expansion

- Program RRs

  • Risk Impact Assessment

- Quantitative Analysis

- Defense-in-Depth 9

07/30/2013

Proposed RR 13-MN-002 Pre-Submittal Meeting

  • Implementation
  • Feedback (Monitoring)

- Proposed ISI Plan Change

- References/Documentation

  • Attachment A: McGuire PRA Quality Review

- Introduction

  • Purpose is assessment of the technical adequacy of the MNS PRA model of record for use in the RIS_B ISI submittal to NRC. Any discrepancies between the model of record and the technical adequacy assessment will be supported using sensitivity studies 10 07/30/2013

Proposed RR 13-MN-002 Pre-Submittal Meeting

- Description of Method

  • A qualitative discussion is provided for the disposition of each finding and observation (F&O) from the internal gap assessment to the ASME/ANS PRA Standard and peer review to NEI 00-02

- Sensitivity Studies

- Assessment of Technical Adequacy for the Internal Events Model 11 07/30/2013

Proposed RR 13-MN-002 Pre-Submittal Meeting

- Internal Events Peer Review to NEI 00-02

  • Strengths
  • Recommended Areas for Improvement 12 07/30/2013

Proposed RR 13-MN-002 Pre-Submittal Meeting

  • Contacts:

- Sect. XI: Hoang Dinh

- Structural Integrity: Scott Chesworth

- PRA: Lee Kanipe

- Regulatory Affairs: P T Vu 13 07/30/2013