Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 7 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5203-----..P30 Equipment Class:
(5) Horizontal Pumps Equipment
Description:
DIESEL GENERATOR/ Fuel Oil Transfer Pump Project:
Dresden 3 SWEL Location (Bldg, Elev, Room/Area):
Turbine, 517.50 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Anchora-qe
- 1.
Is anchorage configuration verification required (i.e., is the item one of the 50%
of SWEL items requiring such verification)?
Yes
- 2.
Is the anchorage free of bent, broken, missing or loose hardware?
Yes
- 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes
- 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
Yes Minor crack in grout pad judged to be acceptable.
- 5.
Is the anchorage configuration consistent with plant documentation? (Note:
This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Yes
- 6.
Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
Yes C-396
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 7 Status: F N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5203-----P30 Equipment Class:
(5) Horizontal Pumps Equipment
Description:
DIESEL GENERATOR/ Fuel Oil Transfer Pump Interaction Effects
- 7.
Are soft targets free from impact by nearby equipment or structures?
Yes
- 8.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Yes
- 9.
Do attached lines have adequate flexibility to avoid damage?
Yes
- 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Other Adverse Conditions
- 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Comments SEWS Anchorage Notes:
Small transfer pump anchored by four 3/8" cast-in-place anchors.
Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 7/31/2012 Evaluated by:
James Griffith Date:
9/30/2012 Michael Wodarcyk 9/30/2012 C-397
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 7 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5203----P30 Equipment Class:
(5) Horizontal Pumps Equipment
Description:
DIESEL GENERATOR/ Fuel Oil Transfer Pump zu1Lut,ii-uresoen-i 1.5 C-398
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 7 Status: E1 N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5203 ------
P30 Equipment Class:
(5) Horizontal Pumps C-399
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 7 Status: EY1 N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5203---P30 Equipment Class:
(5) Horizontal Pumps I
C-400
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 7 Status: F N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
Equipment Class:
D03-5203----P30 (5) Horizontal Pumps D03-503 P3 C-401
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 7 of 7 Status: F-N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5203----P30 Equipment Class:
(5) Horizontal Pumps Equipment
Description:
DIESEL GENERATOR/ Fuel Oil Transfer Pump C-402
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 7 Status:
Y-K N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5746-A---H15 Equipment Class:
(10) Air Handlers Equipment
Description:
LPCI/ LPCI Emergency Room Air Cooler Project:
Dresden 3 SWEL Location (Bldg, Elev, Room/Area):
Reactor, 476.50 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Anchoracqe
- 1.
Is anchorage configuration verification required (i.e., is the item one of the 50%
Yes of SWEL items requiring such verification)?
- 2.
Is the anchorage free of bent, broken, missing or loose hardware?
Yes Abandoned anchor hole located at least 2 anchor diameters away from one rod support in accordance with station procedures. Judged to be acceptable.
- 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes
- 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
Yes Minor shrinkage cracks in underside of ceiling slab judged to be acceptable.
- 5.
Is the anchorage configuration consistent with plant documentation? (Note:
Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
- 6.
Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?
C-403
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 7 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5746-A----H15 Equipment Class:
(10) Air Handlers Equipment
Description:
LPCI/ LPCI Emergency Room Air Cooler Interaction Effects
- 7.
Are soft targets free from impact by nearby equipment or structures?
- 8.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
- 9.
Do attached lines have adequate flexibility to avoid damage?
Cooler secured to wall. Thus, there are no relative flexibility concerns between cooler and associated piping.
- 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Yes Yes Yes Other Adverse Conditions
- 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Comments SEWS Anchorage Notes:
Air cooler is hung from the ceiling with six 1/2" diameter rod hangers (3 on each side).
Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/1/2012 Evaluated by:
ýr ' V" James Griffith Date:
9/30/2012 Michael Wodarcyk 9/30/2012 C-404
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 7 Status: [Y71 N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5746-A ---- H15 Equipment Class:
(10) Air Handlers Equipment
Description:
LPCI/ LPCI Emergency Room Air Cooler C-405
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 7 Status:
Y-E N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
Equipment Class:
D03-5746-A-HI 5 (10) Air Handlers C-406
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 7 Status: [Y N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5746-A--H15 Equipment Class:
(10) Air Handlers C-407
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 7 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5746-A---H15 Equipment Class:
(10) Air Handlers C-408
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 7 of 7 Status: F N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
Equipment Class:
D03-5746-A--HI 5 (10) Air Handlers C-409
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 14 Status: FY N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5747----H15 Equipment Class:
(10) Air Handlers Equipment
Description:
HPCI/ HPCI Emergency Air Cooler Project:
Dresden 3 SWEL Location (Bldg, Elev, Room/Area):
Reactor, 476.50 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Anchora-qe
- 1.
Is anchorage configuration verification required (i.e., is the item one of the 50%
of SWEL items requiring such verification)?
Yes
- 2.
Is the anchorage free of bent, broken, missing or loose hardware?
Yes
- 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes
- 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
Yes Minor shrinkage cracks in ceiling judged to be acceptable.
- 5.
Is the anchorage configuration consistent with plant documentation? (Note:
This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Yes
- 6.
Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
Yes C-410
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 14 Status: T N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5747-----H15 Equipment Class:
(10) Air Handlers EauiDment
Description:
HPCI/ HPCI EmerQencv Air Cooler Interaction Effects
- 7.
Are soft targets free from impact by nearby equipment or structures?
Potential interaction between cooler and channel support of HVAC duct judged to be non-damaging and acceptable.
Insulated pipe for cooler touching duct judged to be acceptable.
- 8.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Yes Yes
- 9.
Do attached lines have adequate flexibility to avoid damage?
Yes
- 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Other Adverse Conditions
- 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Comments SEWS Anchorage Notes:
Air cooler is hung from the ceiling with sixl/2" diameter rod hangers (3 on each side).
Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/3/2012 See U3 HPCI Room area walk-by for further information.
Evaluated by:
APO James Griffith Date:
9/30/2012 Michael Wodarcyk 9/30/2012 C-411
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 14 Status: [-Y N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5747---H15 Equipment Class:
(10) Air Handlers Equipment
Description:
HPCI/ HPCI Emergency Air Cooler Photos 201 C-412
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 14 Status: F N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
Equipment Class:
D03-5747---H1 5 (10) Air Handlers C-413
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 14 Status: FY-] N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5747----H15 Equipment Class:
(10) Air Handlers icy Air C-414
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 14 Status: r-ý N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5747---H15 Equipment Class:
(10) Air Handlers C-415
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 7 of 14 Status: [-ý N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5747---H15 Equipment Class:
(10) Air Handlers C-416
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 8 of 14 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5747 ------
H15 Equipment Class:
(10) Air Handlers C-417
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 9 of 14 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5747---H115 Equipment Class:
(10) Air Handlers C-418
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 10 of 14 Status: r-ý N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
Equipment Class:
D03-5747---H 15 (10) Air Handlers C-419
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 11 of 14 Status: F N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5747---H15 Equipment Class:
(10) Air Handlers inment Descriintion HPCI/ HPCI Emera C-420
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 12 of 14 Status: F N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5747----.H15 Equipment Class:
(10) Air Handlers C-421
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 13 of 14 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5747---H15 Equipment Class:
(10) Air Handlers C-422
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 14 of 14 Status: F N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-5747.-----H15 Equipment Class:
(10) Air Handlers Eauioment Descriotion:
HPCI/ HPCI Emeraencv Air Cooler C-423
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 7 Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-6601 ------
G05 Equipment Class:
(17) Engine-Generators Equipment
Description:
DIESEL GENERATOR/ Diesel Engine Driven Generator Status: F N U Project:
Dresden 3 SWEL Location (Bldg, Elev, Room/Area):
Turbine, 517.50 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Anchorage
- 1.
Is anchorage configuration verification required (i.e., is the item one of the 50%
of SWEL items requiring such verification)?
Yes
- 2.
Is the anchorage free of bent, broken, missing or loose hardware?
Yes
- 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes
- 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
Yes Minor shrinkage cracks in floor judged to be acceptable.
- 5.
Is the anchorage configuration consistent with plant documentation? (Note:
This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Yes
- 6.
Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
Yes C-424
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 7 Seismic Walkdown Checklist (SWC)
Status: EY-N U Equipment ID No.:
D03-6601 ------
G05 Equipment Class:
(17) Engine-Generators Eauiiment
Description:
DIESEL GENERATOR/ Diesel Enqine Driven Generator Interaction Effects
- 7.
Are soft targets free from impact by nearby equipment or structures?
Yes
- 8.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Adjacent masonry wall is safety-related.
- 9.
Do attached lines have adequate flexibility to avoid damage?
Yes Yes
- 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Other Adverse Conditions
- 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Comments SEWS Anchorage Notes:
Anchored by 14 cast-in-place 1.25" diameter bolts.
Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 7/31/2012 Evaluated by:
James Griffith Date:
9/30/2012 Michael Wodarcyk 9/30/2012 C-425
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 7 Status: [-* N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-6601---G05 Equipment Class:
(17) Engine-Generators Equipment
Description:
DIESEL GENERATOR/ Diesel Engine Driven Generator C-426
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 7 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-6601---G05 Equipment Class:
(17) Engine-Generators I
C-427
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 7 Status: [YII] N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-6601 ---- G05 Equipment Class:
(17) Engine-Generators I
C-428
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 7 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-6601 ---- G05 Equipment Class:
(17) Engine-Generators C-429
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 7 of 7 Status:
Y N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-6601 ---
G05 Equipment Class:
(17) Engine-Generators I
C-430
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 9 Status:
V N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-67341--S35 Equipment Class:
(3) Medium Voltage Switchgear Equipment
Description:
4160V AC/ Switchgear 34-1 Project:
Dresden 3 SWEL Location (Bldg, Elev, Room/Area):
Reactor, 545.50 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SVVEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Anchora-qe
- 1.
Is anchorage configuration verification required (i.e., is the item one of the 50%
of SWEL items requiring such verification)?
Yes
- 2.
Is the anchorage free of bent, broken, missing or loose hardware?
Yes
- 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes
- 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
Yes
- 5.
Is the anchorage configuration consistent with plant documentation? (Note:
This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Yes
- 6.
Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
Yes C-431
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 9 Status: LY-1 N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-67341 -S---
S35 Equipment Class:
(3) Medium Voltage Switchgear Equipment
Description:
4160V AC/ Switchgear 34-1 Interaction Effects
- 7.
Are soft targets free from impact by nearby equipment or structures?
- 8.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Overhead roof structure well-supported and judged to be acceptable.
Overhead light fixtures are judged to be acceptable.
Masonry wall at east end of switchgear is safety-related.
- 9.
Do attached lines have adequate flexibility to avoid damage?
- 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Yes Yes Yes Other Adverse Conditions
- 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Comments SEWS Anchorage Notes:
Anchored by small base plates welded to switchgear and anchored by 3/8" concrete expansion anchors.
Switchgear braced back to wall.
Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/2/2012 Evaluated by:
James Griffith Date:
9/30/2012 Michael Wodarcyk 9/30/2012 C-432
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 9 Status: F N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-67341---S35 Equipment Class:
(3) Medium Voltage Switchgear Equipment
Description:
4160V AC/ Switchgear 34-1 Photos C-433
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 9 Status: [-* N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-67341---S35 Equipment Class:
(3) Medium Voltage Switchgear 34-1 C-434
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 9 Status: Y N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
Equipment Class:
D03-67341 --- S35 (3) Medium Voltage Switchgear 34-1 C-435
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 9 Status: E[ý N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-67341---S35 Equipment Class:
(3) Medium Voltage Switchgear 34-1 C-436
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 7 of 9 Status: E-I N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-67341---$35 Equipment Class:
(3) Medium Voltage Switchgear Equipment
Description:
4160V AC/ Switchgear 34-1 C-437
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 8 of 9 Status: [Z N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-67341---S35 Equipment Class:
(3) Medium Voltage Switchgear C-438
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 9 of 9 Status:
Y--] N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-67341 --
S35 Equipment Class:
(3) Medium Voltage Switchgear 34-1 C-439
Dresden Generating Station Unit 3 12QO108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 8 Status: [T N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7338 -S----
S35 Equipment Class:
(2) Low Voltage Switchgear Equipment
Description:
480V AC/ Switchgear 38 Project:
Dresden 3 SWEL Location (Bldg, Elev, Room/Area):
Reactor, 570.00 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findinas. Additional space is Drovided at the end of this checklist for documentina other comments.
Anchoraaqe
- 1.
Is anchorage configuration verification required (i.e., is the item one of the 50%
of SWEL items requiring such verification)?
No
- 2.
Is the anchorage free of bent, broken, missing or loose hardware?
- 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes Yes Yes
- 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
- 5.
Is the anchorage configuration consistent with plant documentation? (Note:
This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Not Applicable
- 6.
Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
Yes C-440
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 8 Status: FYZ N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7338-S35 Equipment Class:
(2) Low Voltage Switchgear Eauir~ment Descriotion:
480V ACI Switchciear 38 Interaction Effects
- 7.
Are soft targets free from impact by nearby equipment or structures?
IR 1396562:
UNPINNED SWITCHGEAR HOISTS During Fukushima seismic walkdowns, two movable trolley hoists mounted on top of SWGR 38 and one movable trolley hoist mounted on top of SWGR 39 were found unrestrained against horizontal movement due to the restraining pin for each hoist not being installed while each hoist was in the stored position. The switchgears are located at U3, N-47, EL. 570.
Unit supervisor and shift manager were informed of the condition and station personnel installed the pins for the trolley hoists. Therefore, hoists are judged acceptable.
- 8.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Overhead light fixture judged to be acceptable.
- 9.
Do attached lines have adequate flexibility to avoid damage?
- 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Yes Yes Yes Other Adverse Conditions
- 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/2/2012 C-441
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 8 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7338-----.35 Equipment Class:
(2) Low Voltage Switchgear Equipment
Description:
480V AC/ Switchgear 38 Evaluated by:
James Griffith Date:
10/24/2012 C/
Michael Wodarcyk 10/24/2012 C-442
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 8 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7338 --.... S35 Equipment Class:
(2) Low Voltage Switchgear 38 20120802-Dresden-3 038 C-443
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 8 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7338-...-S35 Equipment Class:
(2) Low Voltage Switchgear C-444
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 8 Status: EY N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7338 -S----
S35 Equipment Class:
(2) Low Voltage Switchgear 38 C-445
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 7 of 8 Status:
Y-1 N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7338 --.... S35 Equipment Class:
(2) Low Voltage Switchgear 38 C-446
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 8 of 8 Status: EZII N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7338 --.... S35 Equipment Class:
(2) Low Voltage Switchgear C-447
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 5 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7338 ------
T10 Equipment Class:
(4) Transformers Eauipment
Description:
480V AC/ Transformer 38, Feed to Switchgear 38 Project:
Dresden 3 SWEL Location (Bldg, Elev, Room/Area):
Reactor, 570.00 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Anchorage
- 1.
Is anchorage configuration verification required (i.e., is the item one of the 50%
of SWEL items requiring such verification)?
No
- 2.
Is the anchorage free of bent, broken, missing or loose hardware?
Yes
- 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes
- 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
Yes
- 5.
Is the anchorage configuration consistent with plant documentation? (Note:
This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Not Applicable
- 6.
Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
Yes C-448
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 5 Status: FT] N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7338----T1O Equipment Class:
(4) Transformers Eauipment
Description:
480V AC/ Transformer 38, Feed to Switchgear 38 Interaction Effects
- 7.
Are soft targets free from impact by nearby equipment or structures?
Yes
- 8.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
- 9.
Do attached lines have adequate flexibility to avoid damage?
Yes Yes
- 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Other Adverse Conditions
- 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/2/2012 Transformer has been replaced since SQUG walkdown.
Evaluated by:
4 -A James Griffith Date:
9/30/2012 Michael Wodarcyk 9/30/2012 C-449
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 5 Status: r N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7338----TI0 Equipment Class:
(4) Transformers Equipment
Description:
480V AC/ Transformer 38, Feed to Switchgear 38 201 C-450
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 5 Status: FY N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7338----T1O Equipment Class:
(4) Transformers r
C-451
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 5 Status: F N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7338----T1O Equipment Class:
(4) Transformers r
C-452
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 7 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7339 ------
S35 Equipment Class:
(2) Low Voltage Switchgear Eauipment
Description:
480V AC/ 480V Switchqear 39 Project:
Dresden 3 SWEL Location (Bldg, Elev, Room/Area):
Reactor, 570.00 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Anchorage
- 1.
Is anchorage configuration verification required (i.e., is the item one of the 50%
of SWEL items requiring such verification)?
No Yes
- 2.
Is the anchorage free of bent, broken, missing or loose hardware?
- 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes
- 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
Yes
- 5.
Is the anchorage configuration consistent with plant documentation? (Note:
This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Not Applicable
- 6.
Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
Yes C-453
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 7 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7339 -S----
S35 Equipment Class:
(2) Low Voltage Switchgear Equipment
Description:
480V AC/ 480V Switchgear 39 Interaction Effects
- 7.
Are soft targets free from impact by nearby equipment or structures?
Bottom of eastern-most door at back of switchbear is bent out slightly. Door is adequately latched and judged to be acceptable.
IR 1396562:
UNPINNED SWITCHGEAR HOISTS During Fukushima seismic walkdowns, two movable trolley hoists mounted on top of SWGR 38 and one movable trolley hoist mounted on top of SWGR 39 were found unrestrained against horizontal movement due to the restraining pin for each hoist not being installed while each hoist was in the stored position. The switchgears are located at U3, N-47, EL. 570.
Unit supervisor and shift manager were informed of the condition and station personnel installed the pins for the trolley hoists. Therefore, hoists are judged acceptable.
- 8.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Overhead light fixtures judged to be acceptable.
Yes Yes
- 9.
Do attached lines have adequate flexibility to avoid damage?
Yes
- 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Other Adverse Conditions
- 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
C-454
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 7 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7339----S35 Equipment Class:
(2) Low Voltage Switchgear EquiDment
Description:
480V AC/ 480V Switchgear 39 Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/2/2012 Evaluated by:
4e James Griffith Date:
9/30/2012 Michael Wodarcyk 9/30/2012 Photos C-455
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 7 Status: FYI N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7339---S35 Equipment Class:
(2) Low Voltage Switchgear C-456
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 7 Status: FY-] N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7339-----.35 Equipment Class:
(2) Low Voltage Switchgear C-457
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 7 Status: FY] N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7339-----.35 Equipment Class:
(2) Low Voltage Switchgear
==
Description:==
480V AC/ 480V C-458
Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 7 of 7 Status: FYI N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
D03-7339-----.35 Equipment Class:
(2) Low Voltage Switchgear C-459