Seismic Walkdown Report in Response to 50.54(f) Information Request Re Fukushima Near-Term Task Force Recommendation 2.3: Seismic, Updated Transmittal 1 (Annex a) for Dresden, Unit 3, Report No. RS-13-06, Part 6 of 13
ML13126A186
Person / Time
Site: Dresden 
Issue date: 03/28/2013
From: Ali E
Exelon Generation Co
To:
Office of Nuclear Reactor Regulation
References
RS-12-167, RS-13-067 12Q0108.30-R-002, Rev. 2
Download: ML13126A186 (70)


Text

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 7 Status:

T N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0003-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

HPCI/ Turbine Steam Line Valve Project:

Dresden 3 SWEL Location (Bldg, Elev, Room/Area):

Reactor, 476.50 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-326

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 7 Status: FI-N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0003-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves EauiDment DescriDtion:

HPCI/ Turbine Steam Line Valve Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Overhead light fixture with an open S-hook. Fixture has hard-wired cord and will not impact soft targets. Judged to be acceptable. See IR 1396017.

9.

Do attached lines have adequate flexibility to avoid damage?

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/1/2012 Evaluated by:

James Griffith Date:

9/30/2012 Michael Wodarcyk 9/30/2012 C-327

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 7 Status: [*

N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

Equipment Class:

Equipment

Description:

D03-2301-0003-V20 (8) Motor-Operated and Solenoid-Operated Valves HPCI/ Turbine Steam Line Valve Photos C-328

Dresden Generating Station Unit 3 12Q010830-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 7 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

Equipment Class:

D03-2301-0003-V20 (8) Motor-Operated and Solenoid-Operated Valves Line C-329

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 7 Status: [-7 N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0003-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves C-330

Dresden Generating Station Unit 3 12Q0O108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 7 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0003-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves C-331

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 7 of 7 Status: FYi N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0003-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment Descrption:

HPCI/ Turbine Steam Line Valve C-332

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 6 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0006-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

HPCI/ Condensate Tank Supply to HPCI Pump Valve Project:

Dresden 3 SWEL Location (Bldg, Elev, Room/Area):

Reactor, 476.50 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-333

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 6 Status:

Y-] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0006-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

HPCI/ Condensate Tank Supply to HPCI Pump Valve Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Overhead light fixture with an open S-hook. Fixture has hard-wired cord and will not impact soft targets. Judged to be acceptable. See IR 1396017.

Yes Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/1/2012 Evaluated by:

James Griffith Date:

9/30/2012 Michael Wodarcyk 9/30/2012 C-334

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 6 Status: F-Y N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

Equipment Class:

Eauioment Descrition:

D03-2301-0006-V20 (8) Motor-Operated and Solenoid-Operated Valves HPCI/ Condensate Tank Supply to HPCI Pump Valve Photos C-335

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 6 Status: r N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0006-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves C-336

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 6 Status: FYI] N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0006-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves inmDntnDqrJintinn HPCII Cnnd.nentA Tank Suniv to HPCI Pumn Val, C-337

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 6 Status: F N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0006-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves C-338

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 7 Status:

Y-] N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0035-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves EauiDment Descriotion:

HPCI/ SuoDression Pool Suction Line Valve Project:

Dresden 3 SWEL Location (Bldg, Elev, Room/Area):

Reactor, 476.50 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Not Applicable

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable Not Applicable Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-339

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 7 Status: F N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0035-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

HPCI/ Suppression Pool Suction Line Valve Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

9.

Do attached lines have adequate flexibility to avoid damage?

Yes Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/1/2012 Evaluated by:

James Griffith Date:

9/30/2012 Michael Wodarcyk 9/30/2012 C-340

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 7 Status: Eli N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0035-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Equipment

Description:

HPCI/ Suppression Pool Suction Line Valve Photos C-341

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 7 Status: FIY-N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0035-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves C-342

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 7 Status: Eli N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0035-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves 120801-Dresden-3 Part 2 (2) 20120801-Dresden-3 Part 2 (3)

C-343

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 7 Status: F N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0035-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves C-344

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 7 of 7 Status:

Y N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0035-V20 Equipment Class:

(8) Motor-Operated and Solenoid-Operated Valves Pool 20120801-Dresden-3 Part 2 (9)

C-345

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 7 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0057-P30 Equipment Class:

(5) Horizontal Pumps Equipment

Description:

HPCI/ HPCI Turbine Cooling Water Pump Project:

Dresden 3 SWEL Location (Bldg, Elev, Room/Area):

Reactor, 476.50 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchoraaqe

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

Yes

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes Yes Yes Yes

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

C-346

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 7 Status: FY-] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0057-P30 Equipment Class:

(5) Horizontal Pumps Equipment

Description:

HPCI/ HPCI Turbine Cooling Water Pump Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Overhead light fixture with an open S-hook. Fixture has hard-wired cord and will not impact soft targets. Judged to be acceptable. See IR 1396017.

9.

Do attached lines have adequate flexibility to avoid damage?

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments SEWS Anchorage Notes:

Small horizontal Ingersoll pump. Bolted with three 7/8" diameter cast-in-place bolts per side.

Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/1/2012 Evaluated by:

  • '* James Griffith Date:

9/30/2012 Michael Wodarcyk 9/30/2012 C-347

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 7 Status: FJ N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0057-P30 Equipment Class:

(5) Horizontal Pumps Equipment

Description:

HPCI/ HPCI Turbine Cooling Water Pump 20120801-Dresden-3 Part 2 (102) 20120801-Dresden-3 Part 2 (103)

C-348

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 7 Status: FYI N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

Equipment Class:

D03-2301 -0057-P30 (5) Horizontal Pumps C-349

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 7 Status: r-i N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0057-P30 Equipment Class:

(5) Horizontal Pumps C-350

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 7 Status: F N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0057-P30 Equipment Class:

(5) Horizontal Pumps C-351

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 7 of 7 Status: EY N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2301-0057-P30 Equipment Class:

(5) Horizontal Pumps C-352

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 9 Status: F N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2302 ------

P30 Equipment Class:

(5) Horizontal Pumps Eauioment

Description:

HPCI/ HPCI Pump Project:

Dresden 3 SWEL Location (Bldg, Elev, Room/Area):

Reactor, 476.50 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findinqs. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

Yes

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Yes

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-353

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 9 Status: F-] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2302 ------

P30 Equipment Class:

(5) Horizontal Pumps Equipment

Description:

HPCI/ HPCI Pump Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments SEWS Anchorage Notes:

There are four 1" diameter cast-in-place bolts per side.

Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/1/2012 Evaluated by:

4'd James Griffith Date:

9/30/2012 Michael Wodarcyk 9/30/2012 C-354

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 9 Status: EZII N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2302-----P30 Equipment Class:

(5) Horizontal Pumps Eauipment

Description:

HPCI/ HPCI Pump Photos C-355

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 9 Status: E[I N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2302----P30 Equipment Class:

(5) Horizontal Pumps inment Derintionn HPCI/ HPCI Pumn C-356

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 9 Status: [Y N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2302-----P30 Equipment Class:

(5) Horizontal Pumps C-357

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 9 Status: F-1 N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2302----P30 Equipment Class:

(5) Horizontal Pumps C-358

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 7 of 9 Status: F N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2302----P30 Equipment Class:

(5) Horizontal Pumps C-359

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 8 of 9 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2302----.P30 Equipment Class:

(5) Horizontal Pumps nmpnt nDqrrotionn HPCI/ HPCI Pumo C-360

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 9 of 9 Status: F N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2302----P30 Equipment Class:

(5) Horizontal Pumps 201 20801-Dresden-3 Part 2 (44) 20120801-Dresden-3 Part 2 4)

C-361

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 6 Status: [T N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2320-GSCE-F05 Equipment Class:

(9) Fans Equipment

Description:

HPCI/ Gland Seal Condenser Exhaust Fan Project:

Dresden 3 SWEL Location (Bldg, Elev, Room/Area):

Reactor, 476.50 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

Yes

2.

Is the anchorage free of bent, broken, missing or loose hardware?

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Fan is mounted to condenser.

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Not Applicable Yes Yes C-362

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 6 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2320-GSCE-F05 Equipment Class:

(9) Fans Eauipment

Description:

HPCI/ Gland Seal Condenser Exhaust Fan Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Overhead light fixture with an open S-hook. Fixture has hard-wired cord and will not impact soft targets. Judged to be acceptable. See IR 1396017.

9.

Do attached lines have adequate flexibility to avoid damage?

Yes Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments SEWS Anchorage Notes:

Exhaust fan 2' long and 2' in diameter bolted to a bracket with four 1/2" bolts. The bracket is welded to the condeser with very long fillet welds.

Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/1/2012 Evaluated by:

1 41 James Griffith Date:

9/30/2012 Michael Wodarcyk 9/30/2012 C-363

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 6 Status: [Y N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2320-GSCE-F05 Equipment Class:

(9) Fans Equipment

Description:

HPCI/ Gland Seal Condenser Exhaust Fan Photos C-364

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 6 Status:

T N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2320-GSCE-F05 Equipment Class:

(9) Fans C-365

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 6 Status: rY-N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2320-GSCE-F05 Equipment Class:

(9) Fans C-366

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 6 Status: [Y] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2320-GSCE-F05 Equipment Class:

(9) Fans C-367

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet I of 9 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2380-----PSH Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Equipment

Description:

HPCI/ HPCI Turbine Pressure Switch High Project:

Dresden 3 SWEL Location (Bldg, Elev, Room/Area):

Reactor, 476.50 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-368

Dresden Generating Station Unit 3 12QO108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 9 Status:

Y N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2380 ------

PSH Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Eauipment

Description:

HPCI/ HPCI Turbine Pressure Switch High Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Overhead light fixture with an open S-hook. Fixture has hard-wired cord and will not impact soft targets. Judged to be acceptable. See IR 1396017.

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/1/2012 Item is mounted on rack 2203-29. Rack also braced to back wall.

Evaluated by:

James Griffith Date:

9/30/2012 Michael Wodarcyk 9/30/2012 C-369

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 9 Status: FY-] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2380----PSH Equipment Class:

(20) Instrumentation and Control Panels and Cabinets Eauipment

Description:

HPCI/ HPCI Turbine Pressure Switch High C-370

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 9 Status: rI N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2380---PSH Equipment Class:

(20) Instrumentation and Control Panels and Cabinets C-371

Dresden Generating Station Unit 3 12QO108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 9 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2380----PSH Equipment Class:

(20) Instrumentation and Control Panels and Cabinets C-372

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 9 Status: *'* N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2380--PSH Equipment Class:

(20) Instrumentation and Control Panels and Cabinets C-373

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 7 of 9 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2380---PSH Equipment Class:

(20) Instrumentation and Control Panels and Cabinets

  • rj C-374

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 8 of 9 Status: E[I N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2380---PSH Equipment Class:

(20) Instrumentation and Control Panels and Cabinets ment

Description:

HPCI/ HPCI Turbine Pressure Switch High C-375

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 9 of 9 Status: [-ý N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-2380----PSH Equipment Class:

(20) Instrumentation and Control Panels and Cabinets C-376

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 7 Status: F-] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-3903-----P30 Equipment Class:

(5) Horizontal Pumps Equipment

Description:

SERVICE WATER/ Diesel Generator Cooling Water Pump Project:

Dresden 3 SWEL Location (Bldg, Elev, Room/Area):

C. House, 490.67 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

Yes

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes Yes Minor shrinkage cracks in pedestal judged to be acceptable.

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Yes

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-377

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 7 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-3903-----P30 Equipment Class:

(5) Horizontal Pumps Equipment

Description:

SERVICE WATER/ Diesel Generator Cooling Water Pump Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Scaffold knuckle on existing support behaves as a correctly-oriented beam clamp, and is judged to be acceptable.

9.

Do attached lines have adequate flexibility to avoid damage?

Yes Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Abandoned adjacent pump missing nuts at anchor studs, but restrained against lateral movement by the studs. Pump judged to be acceptable.

Comments SEWS Anchorage Notes:

40 H.P. Pump anchored by 4 - 3/4" cast-in-place anchors.

Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/1/2012 Evaluated by:

A1

" 4'" James Griffith Date:

9/30/2012 Michael Wodarcyk 9/30/2012 C-378

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 7 Status: [Y] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-3903----P30 Equipment Class:

(5) Horizontal Pumps Equipment

Description:

SERVICE WATER/ Diesel Generator Cooling Water Pump Photos C-379

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 7 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-3903 ------

P30 Equipment Class:

(5) Horizontal Pumps C-380

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 7 Status: F N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-3903----P30 Equipment Class:

(5) Horizontal Pumps C-381

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 7 Status: [*

N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-3903----P30 Equipment Class:

(5) Horizontal Pumps C-382

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 7 of 7 Status: F N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-3903---P30 Equipment Class:

(5) Horizontal Pumps C-383

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 6 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-4600-B ---- T05 Equipment Class:

(12) Air Compressors Equipment

Description:

DIESEL GENERATOR/ Primary Gas Air Receiver Unit "Al" Project:

Dresden 3 SWEL Location (Bldg, Elev, Room/Area):

Turbine, 517.50 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

Yes of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes Minor shrinkage cracks in floorjudged acceptable.

5.

Is the anchorage configuration consistent with plant documentation? (Note:

Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

6.

Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?

C-384

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 6 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-4600-B ---- T05 Equipment Class:

(12) Air Compressors Equipment

Description:

DIESEL GENERATOR/ Pdmary Gas Air Receiver Unit "Al" Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Overhead light fixtures judged to be acceptable.

9.

Do attached lines have adequate flexibility to avoid damage?

Yes Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments SEWS Anchorage Notes:

Air Start skid anchored by 10 1/2" diameter concrete expansion anchors (5 per side).

Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 7/31/2012 Evaluated by:

" *" James Griffith Date:

9/30/2012 Michael Wodarcyk 9/30/2012 C-385

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 6 Status: [-1 N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-4600-B--T05 Equipment Class:

(12) Air Compressors Eauibment

Description:

DIESEL GENERATOR/ Primary Gas Air Receiver Unit "Al" C-386

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 6 Status: F-] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-4600-B--T05 Equipment Class:

(12) Air Compressors j

20120731-Dresden-3 244 C-387

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 6 Status: F N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-4600-B-T05 Equipment Class:

(12) Air Compressors C-388

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 6 Status: E7Y N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-4600-B--T05 Equipment Class:

(12) Air Compressors Frniinmrnt D).P.rintinn" DIEI::L *:FNFRATOR/ Primnarv raq Air Receiver Unit "AI" C-389

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 1 of 6 Status: FY-] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-5202----T05 Equipment Class:

(21) Tanks and Heat Exchangers Equipment

Description:

DIESEL GENERATOR/ Diesel Fuel Oil Storage Day Tank Project:

Dresden 3 SWEL Location (Bldg, Elev, Room/Area):

Turbine, 528.25 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

Yes

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes Minor shrinkage cracks in floor are judged to be acceptable.

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Yes

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-390

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 2 of 6 Status: F-ý N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-5202 ------

T05 Equipment Class:

(21) Tanks and Heat Exchangers Equipment

Description:

DIESEL GENERATOR/ Diesel Fuel Oil Storage Day Tank Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Adjacent masonry wall is safety-related.

9.

Do attached lines have adequate flexibility to avoid damage?

Yes Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments SEWS Anchorage Notes:

This 750 gal. capacity diesel fuel oil day tank is mounted on 2 saddles. Each saddle is anchored to 11" high concrete piers by 4 - 7/8" cast-in-place anchors.

Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 7/31/2012 Evaluated by:

James Griffith Date:

9/30/2012 Michael Wodarcyk 9/30/2012 C-391

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 3 of 6 Status: Fi'-

N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-5202----T05 Equipment Class:

(21) Tanks and Heat Exchangers Equipment

Description:

DIESEL GENERATOR/ Diesel Fuel Oil Storage Day Tank C-392

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 4 of 6 Status: [-ý N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

Equipment Class:

inmant fIoctrinfinn" D03-5202---T05 (21) Tanks and Heat Exchangers

/'I C-393

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 5 of 6 Status: [j N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-5202----T05 Equipment Class:

(21) Tanks and Heat Exchangers C-394

Dresden Generating Station Unit 3 12Q0108.30-R-002, Rev. 2 Correspondence No.: RS-12-167 Sheet 6 of 6 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

D03-5202----T05 Equipment Class:

(21) Tanks and Heat Exchangers EauiDment Descrgtion:

DIESEL GENERATOR/ Diesel Fuel Oil Storage Day Tank C-395