1 NRR-PMDAPEm Resource From:
Feintuch, Karl Sent:
Monday, March 18, 2013 4:38 PM To:
Browning, Tony
Subject:
MF0460 - Duane Arnold - Adoption of TSTF-522 Request for Additional Information Attachments:
MF0460 (DA TSTF-522) RAI 2013-03-18.docx By application dated December 21, 2012, Agencywide Documents Access and Management System (ADAMS) Accession No. ML12356A184, NextEra Energy Duane Arnold, LLC (the licensee), requested changes to the Technical Specifications (TSs) for Duane Arnold Energy Center (DAEC).
The proposed amendment would modify the current DAEC TS requirement to operate the Standby Gas Treatment System for 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> on a frequency specified in the Surveillance Frequency Control Program in accordance with TSTF-522, Revision 0, "Revise Ventilation System Surveillance Requirements to Operate for 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> per Month."
In the course of their review, NRC staff has identified the need for a Request for Additional Information (RAI) to complete the review of the subject DAEC TS change. The RAI is attached.
Should you need clarification of the requested item please contact me. If no clarification is needed, please consider the draft item as firm. We would like a response to this item by April 18, 2013.
Karl Feintuch USNRC 301-415-3079
Hearing Identifier:
NRR_PMDA Email Number:
637 Mail Envelope Properties (Karl.Feintuch@nrc.gov20130318163800)
Subject:
MF0460 - Duane Arnold - Adoption of TSTF-522 Request for Additional Information Sent Date:
3/18/2013 4:38:11 PM Received Date:
3/18/2013 4:38:00 PM From:
Feintuch, Karl Created By:
Karl.Feintuch@nrc.gov Recipients:
"Browning, Tony" <Tony.Browning@nexteraenergy.com>
Tracking Status: None Post Office:
Files Size Date & Time MESSAGE 1073 3/18/2013 4:38:00 PM MF0460 (DA TSTF-522) RAI 2013-03-18.docx 20779 Options Priority:
Standard Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
Recipients Received:
DRAFT REQUEST FOR ADDITIONAL INFORMATION DUANE ARNOLD ENERGY CENTER LICENSE AMENDMENT REQUEST REGARDING ADOPTION OF TSFT-522 "REVISE VENTILATION SYSTEM SURVEILLANCE REQUIREMENTS TO OPERATE FOR 10 HOURS PER MONTH"
=
Background===
By application dated December 21, 2012, Agencywide Documents Access and Management System (ADAMS) Accession No. ML12356A184, NextEra Energy Duane Arnold, LLC (the licensee), requested changes to the Technical Specifications (TSs) for Duane Arnold Energy Center (DAEC). The proposed amendment would modify the current DAEC TS requirement to operate the Standby Gas Treatment System for 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> on a frequency specified in the Surveillance Frequency Control Program in accordance with TSTF-522, Revision 0, "Revise Ventilation System Surveillance Requirements to Operate for 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> per Month."
Regulatory Basis The regulatory requirements for design and testing of the subject systems are contained in Title 10 of the Code of Federal Regulations (10 CFR) Section 50.67 and Part 100, as well as Part 50, Appendix A, "General Design Criteria for Nuclear Power Plants," General Design Criteria 19, 41, 42, 43, and 61.
Request for Additional Information The Nuclear Regulatory Commission staff evaluated the licensees proposed change against the applicable regulatory guidance in Regulatory Guide (RG) 1.52, Revision 3, Design, Testing, and Maintenance Criteria for Post-Accident Engineered-Safety-Feature Atmosphere Cleanup System Air Filtration and Adsorbtion Units of Light-Water-Cooled Nuclear Power Plants, ADAMS Accession No. ML011710176, guidance in the Standard Technical Specification as modified by TSTF-522, and the regulatory requirements of 10 CFR 50.36.
Please discuss how RG1.52, Revision 3, is currently being implemented at Duane Arnold and identify any deviations taken from the guidance provided.