DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: LYJ N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 13-AB1,609, 4 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?

Yes

2.

Does anchorage of equipment in the area appear to be free of significant degraded conditions?

Yes

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

Yes

4.

Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Yes

5.

Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?

Yes

6.

Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?

Yes

7.

Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Yes D-54

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

I N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 13 -AB1,609, 4

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Evaluated by:

George G Thomas Neda Stoeva Date:

10/18/12 10/18/12 D-55

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: FY-] N U Area Walk-By Checklist (AWC)

I

-tafl; -

ln I

I lý M -

nnm /A 609,4 D-56

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: L-j N U Area Walk-By Checklist (AWC)

D-57

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: Lull N U Area Walk-By Checklist (AWC)

D-58

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

IYI N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 13-AB1. 609. 4 D-59

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y-] N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 14 - AB1, 587, 40 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
2.

Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

4.

Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Block wall with grate - OK per DWG 12-4026, Wall W-2

5.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?

De-pressurized well supported fire protection piping

6.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?

7.

Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Crane parked and locked with C-clamp D-60

DC Cook Unit I & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: LXII N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 14 - AB1,587, 40

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments George G Thomas Evaluated by:

Date:

10/18/12 8ýý4-Neda Stoeva 10/18/12 D-61

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: FI-Y I N U Area Walk-By Checklist (AWC)

D-62

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: El] N U Area Walk-By Checklist (AWC)

D-63

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y N U Area Walk-By Checklist (AWC)

I.

D-64

DC Cook Unit I & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: []

N U Area Walk-By Checklist (AWC)

D-65

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: EYI] N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 15-AB1, 587, 41 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
2.

Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

4.

Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Block wall with grate - OK per DWG 12-4026, Wall W-3

5.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?

De-pressurized well supported fire protection piping

6.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?

7.

Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Crane parked and locked with C-clamp D-66

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: [ZII N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 15-AB1,587,41

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Evaluated by:

George G Thomas Neda Stoeva Date:

10/18/12 10/18/12 D-67

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y-] N U Area Walk-By Checklist (AWC) rtjIOU I-Iz D-68

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: 1*] N U Area Walk-By Checklist (AWC)

II D-69

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: FY] N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 16 - AB1, 587, 43 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

Lack of thread engagement (minor) on pump as noted on 1-PP-26S

2.

Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

4.

Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Block wall with grate - OK per DWG 12-4026, Wall W-9

5.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?

6.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?

7.

Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

D-70

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: FYII N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 15-AB1,587, 41

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Evaluated by:

EaadyGeorge G Thomas Neda Stoeva Date:

10/18/12 10/18/12 D-71

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: j*] N U Area Walk-By Checklist (AWC)

D-72

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y N U Area Walk-By Checklist (AWC)

Area 15 -AB1, 587, 41 D-73

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: FY-] N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 17 -ABI, 573, 52 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
2.

Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

4.

Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Block wall with grate - OK per DWG 12-4025, Wall W-2

5.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?

6.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?

7.

Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

D-74

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

T N

U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 17 - ABI, 573, 52

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Evaluated by:

Evaluated by:

  • George G Thomas Neda Stoeva Date:

10/18/12 10/18/12 D-75 i

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: [iYi N U Area Walk-By Checklist (AWC)

D-76

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: F N U 1,573,52 Area Walk-By Checklist (AWC)

I r--fi-~

fIp~n IMt,, Dnnrmlh D-77

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: FYj] N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 18 - ABt, 573, 55 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?

Yes

2.

Does anchorage of equipment in the area appear to be free of significant degraded conditions?

Yes

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

Yes

4.

Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Block wall with grate - OK per DWG 12-4025, Wall W-4

5.

Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?

Yes Yes

6.

Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?

Yes

7.

Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Yes D-78

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

I N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 18 - AB1, 573, 55

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Evaluated by:

George G Thomas Neda Stoeva Date:

10/18/12 10/18/12 D-79

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: FTI N U

Area Walk-By Checklist (AWC)

I r

{ln II 11-,

LDrmA 18-AB1, 573, 55 D-80

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y-] N U Area Walk-By Checklist (AWC)

I neiatinn IPIrrin Pa Prnnmlb D-81

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: [I] N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 19 - AB1, 609, 6 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?

Yes

2.

Does anchorage of equipment in the area appear to be free of significant degraded conditions?

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

Yes Yes Yes

4.

Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

5.

Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?

Yes

6.

Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?

Yes

7.

Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Yes D-82

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: FI* N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 19 -AB1,609, 6

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Georqe G Thomas Evaluated by:

Date:

10/18/12 E Neda Stoeva 10/18/12 I *./ IU I I/.,,

I D-83

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y N U Area Walk-By Checklist (AWC)

D-84

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y N U Area Walk-By Checklist (AWC)

D-85

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y L-i U

Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 20 - AB2, 609, BY 1-PP-10W Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
2.

Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

Minor rust on 1-HE-15E south-east and south west bolts. 1-WFI-731-IN rack

- base plate has 4 bolts - I of which has no nut or room to put one on - OK approved as is by engineering under 5CRP DOC# 00-10940

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

4.

Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

5.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?

6.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?

7.

Does it appear that the area is free of potentially adverse seismic interactions No associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Fire extinguishers on short hooks - AR 2012-11669 was issued.

D-86

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y LjI U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 20 - AB2, 609, BY 1-PP-10W

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Sprinkler head near 20 PSI CA by 1-HE-15E - depressurized but fire piping &

sprinkler vibrate and could impact 20 PSI CA, possibly damage sprinkler head

- but OK because not charged Comments Evaluated by:

George G Thomas Neda Stoeva Date:

10/18/12 10/18/12 D-87

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y LN-I1 U Area Walk-By Checklist (AWC)

I nnotinn 1PItim Plaw RvNim/jl D-88

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y LI] U Area Walk-By Checklist (AWC)

D-89

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y ¶-N U

Area Walk-By Checklist (AWC)

Area 20 - AB2, 609, BY 1.

D-90

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y LEI U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 20 -AB2, 609, BY 1-PP-IOW D-91

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: LVii N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 21 -AB1, 633,633 WMO-715 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
2.

Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

Threads not fully engaged on supports for 1-WMO-711 and minor rust. OK by engineering - no DOC# on tag.

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

4.

Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

5.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?

6.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?

7.

Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

D-92

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: tE1 N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 21 - AB1, 633, 633 WMO-715

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Evaluated by:

Evaluated by:_

George G Thomas Neda Stoeva Date:

10/18/12 10/18/12 D-93

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: ELI N U Area Walk-By Checklist (AWC)

D-94

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: [fY N U Area Walk-By Checklist (AWC)

D-95

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: LI] N U

Area Walk-By Checklist (AWC)

D-96

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status: E[-I N U 1.633. 633 WMO-715 Area Walk-By Checklist (AWC)

Location (Bda.

pElev.

Room/A D-97

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y [_] U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 22 - AB2, 633, 633 by 12-HV-ACCP-3 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
2.

Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

4.

Does it appear that the area is free of potentially adverse seismic spatial No interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Fire extinguishers behind Concentrator 7 on semi-short hooks (longer than other areas) - AR 2012-11669 was issued.

5.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?

6.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?

7.

Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

D-98

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y L U

Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 22 - AB2, 633, 633 by 12-HV-ACCP-3

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Evaluated by:

George G Thomas Neda Stoeva Date:

10/18/12 10/18/12 D-99

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y L[- U Area Walk-By Checklist (AWC)

I npntinn (PirlI P Pnnm/Arn*I" Aron 99 - AP9 RA'A AAA hii 19-1-I-AC.f.P-.

I D-100

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y [*J] U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 23 - AB1, 587,121 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
2.

Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

4.

Does it appear that the area is free of potentially adverse seismic spatial No interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Fire extinguishers on short hooks - AR 2012-11669 was issued. Block wall -

OK per DWG 1-4033, Wall W-3 and Wall W-4

5.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?

6.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?

C02 fire protection

7.

Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

D-101 I

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y ¶1 U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 23 - AB1, 587,121

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Evaluated by:

George G Thomas L-AtJ)

Neda Stoeva Date:

10/18/12 10/18/12 D-102

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y [F-U Area Walk-By Checklist (AWC)

D-103

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y L-*I U Area Walk-By Checklist (AWC) 1,587, 121 D-104

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y FN] U Area Walk-By Checklist (AWC)

I nr^,tOfin 1PIr4,n IZ=lnl Dnnm/A D-105

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y LN U

Area Walk-By Checklist (AWC)

D-1 06

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y

] U Area Walk-By Checklist (AWC) 1,587,121 D-107

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y EiT] U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 24 -AB1, 587, 122 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
2.

Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

4.

Does it appear that the area is free of potentially adverse seismic spatial No interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Fire extinguishers on short hooks - AR 2012-11669 was issued. Block wall -

OK per DWG 1-4033, Wall W-1 and Wall W-2. Ceiling light rod hung above MCC on right side of door could swing but OK because there is a steel angle installed to prevent it from hitting MCC

5.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?

6.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?

7.

Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

D-1 08

DC Cook Unit I & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y LNI U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

Area 24-AB1, 587,122

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments George G Thomas Evaluated by:

Date:

10/18/12

  • _41-Neda Stoeva 10/18/12 D-109

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y L[-I U Area Walk-By Checklist (AWC)

D-110

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y [NI U

Area Walk-By Checklist (AWC)

Location Bid,Elev, Room/Area : Area 24 - A131 I D-111

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y FN] U Area Walk-By Checklist (AWC)

D-112

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y L-] U Area Walk-By Checklist (AWC)

D-113

DC Cook Unit 1 & Unit 2 SD-121023-001 Rev. 0, 11/05/12 Status:

Y r-]

U Area Walk-By Checklist (AWC) 24 - ABI, 587, D-114