MONTHYEARML15337A3522015-11-17017 November 2015 Official Exhibit - NYS000582-00-BD01 - Diagram of Strength Vs Amplitude by Dr. Richard T. Lahey ML15337A3372015-11-11011 November 2015 Official Exhibit - ENTR00726-00-BD01 - Track 2 Hearing Exhibit List ML15337A3322015-11-0505 November 2015 Official Exhibit - ENT000726-00-BD01 - Entergy Track 2 Hearing Exhibit List ML15337A3352015-11-0505 November 2015 Official Exhibit - RIVR14001-00-BD01 - Riverkeeper Tailored Track 2 Exhibit List ML15337A3362015-11-0505 November 2015 Official Exhibit - NRCR10001-00-BD01 - NRC Staff Track 2 Exhibit List ML15337A3332015-11-0404 November 2015 Official Exhibit - NYSR25001-00-BD01 - NYS Revised Tailored Exhibits List Relevant to Track 2 Contentions ML15337A3312015-11-0303 November 2015 Official Exhibit - NRC000230-00-BD01 - Corrections to Prefiled Testimony NRC000168 and NRC000197 ML15337A3262015-10-29029 October 2015 Official Exhibit - ENT000722-00-BD01 - Supplemental Testimony of Entergy Witnesses Nelson Azevedo, Timothy Griesbach & Randy Lott ML15337A3292015-10-29029 October 2015 Official Exhibit - ENTR16001-00-BD01 - Entergy Revised Exhibit List ML15337A3242015-09-23023 September 2015 Official Exhibit - NYS000576-00-BD01 - Pre-Filed Supplemental Testimony of Richard T. Lahey Re Contentions NYS-25, NYS-26B/RK-TC-1B & NYS-38/RK-TC-5 ML15337A3072015-09-0909 September 2015 Official Exhibit - NYS000573-PUB-00-BD01 - Supplemental Reply Statement of Position of the State of New York and Riverkeeper, Inc. in Support of Contention NYS-38/RK-TC-5 (Public, Redacted) (September 9, 2015) ML15337A2962015-09-0909 September 2015 Official Exhibit - NYS000570-PUB-00-BD01 - Supplemental Reply Statement of Position of the State of New York and Riverkeeper, Inc. in Support of Contention NYS-26B/RK-TC-1B (Public, Redacted) (September 9, 2015) ML15337A2832015-09-0909 September 2015 Official Exhibit - NYS000563-00-BD01 - Pressurized Water Reactor (PWR) Systems, USNRC Technical Training Center, Reactor Concepts Manual, Pages 4-1 to 4-28 ML15337A2952015-09-0909 September 2015 Official Exhibit - NYS000569-PUB-00-BD01 - Pre-filed Supplemental Reply Testimony of Richard T. Lahey, Jr. in Support of Contention NYS-26B/RK-TC-1B (Public, Redacted) (September 9, 2015) ML15337A2942015-09-0909 September 2015 Official Exhibit - NYS000568-PUB-00-BD01 - Supplemental Reply Statement of Position of the State of New York in Support of Contention NYS-25 (Public, Redacted) (September 9, 2015) ML15337A2932015-09-0909 September 2015 Official Exhibit - NYS000567-PUB-00-BD01 - Pre-filed Supplemental Reply Testimony of Richard T. Lahey, Jr. in Support of Contention NYS-25 (Public, Redacted) (September 9, 2015) ML15337A3042015-09-0909 September 2015 Official Exhibit - NYS000571-PUB-00-BD01 - Pre-filed Supplemental Reply Testimony of David J. Duquette in Support of Contention NYS-38/RK-TC-5 (Public, Redacted) (September 9, 2015) ML15337A2972015-09-0909 September 2015 Official Exhibit - RIV000164-00-BD01 - NUREG-1740, ACRS, Voltage-Based Alternative Repair Criteria: a Report to the Advisory Committee on Reactor Safeguards by the Ad Hoc Subcommittee on a Differing Professional Opinion (2001) ML15337A3062015-09-0909 September 2015 Official Exhibit - NYS000572-PUB-00-BD01 - Pre-filed Supplemental Reply Testimony of Richard T. Lahey, Jr. in Support of Contention NYS-38/RK-TC-5 (Public, Redacted) (September 9, 2015) ML15337A2822015-09-0909 September 2015 Official Exhibit - NYS000566-00-BD01 - Figure 1 for Supplemental Reply Testimony of Dr. Richard T. Lahey ML15337A3142015-09-0404 September 2015 Official Exhibit - ENTR00615-PUB-00-BD01 - Entergy'S Statement of Position Re Contention NYS-25 (Embrittlement) - Redacted ML15334A2842015-08-10010 August 2015 Official Exhibit - ENT000687-00-BD01 - NRC, Safety Evaluation Report, Topical Report on ASME Section III Piping and Component Fatigue Analysis Utilizing the Westems Computer Code (WCAP-17577, Revision 2) (Undated) ML15335A2932015-08-10010 August 2015 Official Exhibit - NRCR00104-00-BD01 - on Yee Statement of Professional Qualifications (Revised) ML15337A2642015-08-10010 August 2015 Official Exhibit - NRC000196-PUB-00-BD01 - NRC Staff'S Initial Statement of Position on Contention NYS-25 (Reactor Vessel Internals) ML15337A3192015-08-10010 August 2015 Official Exhibit - ENT000698-PUB-00-BD01 - Entergy'S Revised Statement of Position Regarding Contention NYS-38/RK-TC-5(Safety Commitments) (Aug. 10, 2015)Redacted ML15337A3202015-08-10010 August 2015 Official Exhibit - ENT000699-PUB-00-BD01 - Redacted Revised Testimony of Entergy Witnesses Nelson Azevedo, Robert Dolansky, Alan Cox, Jack Strosnider, Timothy Griesbach, Barry Gordon, Randy Lott, and Mark Gray Regarding Contention NYS-38/RK ML15337A3172015-08-10010 August 2015 Official Exhibit - ENT000678-PUB-00-BD01 - NL-07-140, Letter from F. Dacimo, Entergy, to NRC Document Control Desk, ?Reply to Request for Additional Information Regarding License Renewal Application? (Nov. 28, 2007)Redacted ML15337A2652015-08-10010 August 2015 Official Exhibit - NRC000197-PUB-00-BD01 - NRC Staff Testimony of Dr. Allen Hiser, Jeffrey Poehler, and Gary Stevens on NYS-25 and NYS-38/RK-TC-5 ML15337A2412015-08-10010 August 2015 Official Exhibit - NRCR00147-00-BD01 - NRC Staff'S Revised Statement of Position on State of New York and Riverkeeper'S Joint Contention NYS-38/RK-TC5 (Revised) ML15335A2902015-08-10010 August 2015 Official Exhibit - NRC000222-00-BD01 - IP3 FSAR Rev. 04 Chapter 3 (2011) (Excerpt) ML15334A2632015-08-10010 August 2015 Official Exhibit - ENT000648-00-BD01 - M. Mitchell, Chief, Vessels and Internals Integrity Branch, Response to Non-Concurrence Regarding Safety Evaluation for Topical Report MRP-227 Pressurized Water Reactor Internals Inspection and Evaluat ML15337A2622015-08-10010 August 2015 Official Exhibit - NRC000228-00-BD01 - Indian Point Unit 2 Technical Specifications 3.1.4 ML15337A2452015-08-10010 August 2015 Official Exhibit - NRC000227-00-BD01 - Gary Stevens Statement of Professional Qualifications ML15337A2632015-08-10010 August 2015 Official Exhibit - NRC000229-00-BD01 - Indian Point, Unit 3 Technical Specifications 3.1.4 ML15335A2192015-08-10010 August 2015 Official Exhibit - ENTR00031-00-BD01 - Curriculum Vitae of Alan B. Cox ML15335A2112015-08-10010 August 2015 Official Exhibit - ENTR20186-00-BD01 - Curriculum Vitae of Mark A. Gray ML15337A3162015-08-10010 August 2015 Official Exhibit - ENT000616-PUB-00-BD01 - Testimony of Entergy Witnesses Nelson F. Azevedo, Robert J. Dolansky, Alan B. Cox, Jack R. Strosnider, Timothy J. Griesbach, Randy G. Lott, and Mark A. Gray Regarding Contention NYS-25 (Embrittleme ML15337A2782015-08-10010 August 2015 Official Exhibit - NRC000168-PUB-00-BD01 - NRC Staff Testimony of Dr. Allen Hiser, Dr. Ching Ng, Mr. Gary Stevens, P.E., and Mr. on Yee, Concerning Contentions NYS-26B/RK-TC-1B and NYS-38/RK-TC-5 ML15337A2712015-08-10010 August 2015 Official Exhibit - NRC000223-00-BD01 - IP3 FSAR Rev. 04 Chapter 14 (2011) ML15337A2592015-08-10010 August 2015 Official Exhibit - NRC000224-00-BD01 - IP3 FSAR Rev. 04 Chapter 16 ML15337A2442015-08-10010 August 2015 Official Exhibit - NRCR00161-00-BD01 - NRC Staff Testimony of Dr. Allen L. Hiser and Mr. Kenneth J. Karwoski Concerning Portions of State of New York and Riverkeeper, Inc. Joint Contention NYS-38/RK-TC5 (Revised) ML15334A2822015-08-10010 August 2015 Official Exhibit - ENT000680-00-BD01 - Curriculum Vitae of Barry M. Gordon ML15335A2912015-08-10010 August 2015 Official Exhibit - NRCR00118-00-BD01 - Indian Point Unit 3 Technical Specifications (Excerpt) (Revised) ML15334A2282015-08-10010 August 2015 Official Exhibit - ENT000634-00-BD01 - Entergy, IP2, FSAR Update, Revision 25 (2014) (Excerpts) ML15335A2822015-08-10010 August 2015 Official Exhibit - NRC000220-00-BD01 - Pressurized Water Reactor Owners Group (PWROG) Presentation Slides, Industry and NRC Coordination Meeting Materials Programs Technical Exchange: Clevis Insert Bolt Update, (June 2014) ML15337A2692015-08-10010 August 2015 Official Exhibit - NRC000169-00-BD01 - NRC000169 - Indian Point, Unit 2 Technical Specifications (Excerpt) ML15337A2602015-08-10010 August 2015 Official Exhibit - NRC000226-00-BD01 - Jeffrey C. Poehler Statement of Professional Qualifications ML15335A2732015-08-10010 August 2015 Official Exhibit - NRC000183-00-BD01 - NRC Inspection Manual, Inspection Procedure 71013, Site Inspection for Plants with a Timely Renewal Application (Sept. 25, 2013) ML15335A2202015-08-10010 August 2015 Official Exhibit - ENTR00184-00-BD01 - Curriculum Vitae of Jack R. Strosnider ML15335A3012015-08-10010 August 2015 Official Exhibit - NRC000206-00-BD01 - Indian Point, Unit 2, Updated Final Safety Analysis Report (Ufsar), Rev. 25, Chapter 14 - Safety Analysis (2014) 2015-09-09
[Table view] |
Text
United States Nuclear Regulatory Commission Official Hearing Exhibit Entergy Nuclear Operations, Inc.
In the Matter of:
(Indian Point Nuclear Generating Units 2 and 3) v\.~P.P.EGV(.q;. ASLBP #: 07-858-03-LR-BD01 l~\"
Docket #: 05000247 l 05000286
< 0 Exhibit #: NRC000163-00-BD01 Identified: 10/15/2012
>- ~
~ Admitted: 10/15/2012 Withdrawn: NRC000163
~
..../~
i Rejected: Stricken:
" "***'" ..0' Other:
Submitted: August 23, 2012 Federal Register/Vol. 77, No. 149/Thursday, August 2, 2012/Notices 46127 NUCLEAR REGULATORY Document Room (PDR) reference staff at COMMISSION 1-800-397-4209, 301-415-4737, or by email to pdr.resource@nrc.gov. The
[NRC-2012-o055] ADAMS accession number for each document referenced in this document Interim Staff Guidance on Changes to (if that document is available in the Generic Aging Lessons Learned ADAMS) is provided the first time that (GALL) Report Revision 2 AMP XI.M41, a document is referenced. The LR-ISG-
"Buried and Underground Piping and 2011-03 is available under ADAMS Tanks" Accession No. ML12138A296 .
AGENCY: Nuclear Regulatory
- NRC's PDR: You may examine and Commission. purchase copies of public documents at ACTION: Interim staff guidance; issuance. the NRC's PDR, Room 01-F21, One White Flint North, 11555 Rockville
SUMMARY
- The U.S. Nuclear Regulatory Pike, Rockville, Maryland 20852.
Commission (NRC) is issuing the final
- NRC's Interim Staff Guidance Web License Renewal Interim Staff Guidance Site: LR-ISG documents are also (LR-ISG), LR-ISG-2011-03, "Changes available online under the "License to GALL Report Revision 2 Aging Renewal" heading at http://
Management Program (AMP) XLM41, www.nrc.gov/reading-rm/doc-
'Buried and Underground Piping and collections/#int.
Tanks'." This LR-ISG provides changes FOR FURTHER INFORMATION CONTACT:
to the recommendations in GALL Report Mr. William Holston, Division of Revision 2 AMP XLM41 based on the License Renewal, Office of Nuclear staff's review of several license renewal Reactor Regulation, U.S. Nuclear applications' buried and underground Regulatory Commission, Washington, piping and tanks AMPs and stakeholder DC 20555-0001; telephone: 301-415-input. The LR-ISG revises NRC staff 8573, or email:
recommended AMPs in NUREG-1801, William.Holston@nrc.gov.
Revision 2, "Generic Aging Lessons SUPPLEMENTARY INFORMATION:
Learned (GALL) Report," and the NRC staff's aging management review Background Information procedure and acceptance criteria The NRC issues LR-ISG to contained in NUREG-1800, Revision 2, communicate insights and lessons "Standard Review Plan for Review of learned and to address emergent issues License Renewal Applications for not covered in license renewal guidance Nuclear Power Plants" (SRP-LR). The documents. In this way, the NRC staff NRC published Revision 2 of the SRP- and stakeholders may use the guidance LR and GALL Report in December 2010, in an LR-ISG document until it is and they are available in the NRC's incorporated into a formal license Agencywide Documents Access and renewal guidance document revision.
Management System (ADAMS) under The NRC staff issues LR-ISG in Accession Nos. ML103490041 and accordance with the LR-ISG Process, ML103490036, respectively. Revision 2 (ADAMS Accession No.
ADDRESSES: Please refer to Docket ID ML100920158), for which a notice of NRC-2012-0055 when contacting the availability was published in the NRC about the availability of Federal Register on June 22, 2010 (75 information regarding this document. FR 35510).
You may access information related to The NRC staff developed LR-ISG-this document, which the NRC 2011-03 to (a) Include inspection possesses and are publicly available, recommendations for plants that will using any of the following methods: not utilize a cathodic protection system
- Federal Rulemaking Web site: Go to in the period of extended operation, (b) http://www.regulations.gov and search remove the recommendation to for Docket ID NRC-2012-0055. Address volumetrically inspect underground questions about NRC dockets to Carol piping to detect internal corrosion since Gallagher; telephone: 301-492-3668; other AMPs such as XLM 38 manage the email: Carol.Gallagher@nrc.gov. aging of internal surfaces of buried and
- NRC's Agencywide Documents underground piping and tanks, (c) base Access and Management System further increased inspection sample (ADAMS): You may access publicly sizes on an analysis of extent of cause available documents online in the NRC and extent of condition when adverse Library at http://www.nrc.gov/reading- conditions are detected in the initial rm/adams.html. To begin the search, and subsequent doubled sample size select "ADAMS Public Documents" and rather than continuing to double the then select "Begin Web-based ADAMS sample size, (d) add a recommendation Search." For problems with ADAMS, that where damage to the coating is please contact the NRC's Public significant and the damage was caused
46128 Federal Register/Vol. 77, No. 149/Thursday, August 2, 2012/Notices by non-conforming backfill, an extent of The LR-ISG is also not directed to condition evaluation should be licensees who already hold renewed conducted to ensure that the as-left operating or combined licenses.
condition of backfill in the vicinity of Dated at Rockville, Maryland, this 26th day observed damage will not lead to further ofJuly, 2012.
degradation, (e) add specific acceptance For the Nuclear Regulatory Commission.
criteria for cathodic protection surveys, Melanie A. Galloway, (f) add the specific preventive and mitigative actions utilized by the AMP Deputy Director, Division of License Renewal, Office of Nuclear Reactor Regulation.
in the Final Safety Analysis Report
[FR Doc. 2012-18862 Filed 8-1-12; 8;45 am]
Supplement description of the program as contained in the SRP-LR, (g) make BILLING CODE 7590-01-P miscellaneous and editorial changes, and (h) correct an internal conflict between AMP XLM41 and AMP XLM36, "External Surfaces Monitoring of Mechanical Components."
On March 9, 2012, (77 FR 14446) the NRC requested public comments on draft LR-ISG-2011-03 (ADAMS Accession No. MLl1244A058). By letter dated March 27, 2012, (ADAMS Accession No. ML12089A021), the Nuclear Energy Institute (NEI) requested a 14-day extension to the comment period. The NRC staff granted the NEI's requested as noticed on April 11, 2012 (77 FR 21813) and given that the comment period had closed on April 9, 2012, the comment period was reopened until April 20, 2012.
The NRC received external comments from Mr. Jon Cavello on April 1, 2012 (ADAMS Accession No. ML12094A367),
Mears Group on April 9, 2012 (ADAMS Accession No. ML12103A207), Det Norske Veritas (USA) Inc. on April 13, 2012 (ADAMS Accession No. ML12108A049), and NElon April 20, 2012 (ADAMS Accession No. ML12114A214). No other external comments were submitted. The NRC considered these comments in developing the final LR-ISG. Detailed responses to the comments can be found in Appendix G of the final LR-ISG.
The final LR-ISG-2011-03 is approved for NRC staff and stakeholder use and will be incorporated into NRC's next formal license renewal guidance document revision.
Backfitting and Issue Finality Issuance of this final LR-ISG does not constitute backfitting as defined in 10 CFR 50.109 (the Backfit Rule) and is not otherwise inconsistent with the issue finality provisions in Part 52, "Licenses, Certifications, and Approvals for Nuclear Power Plants," of 10 CFR. As discussed in the "Backfitting Discussion" section of final LR-ISG-2011-03, the LR-ISG is directed to holders of operating licenses or combined licenses who are currently in the license renewal process. The LR-ISG is not directed to holders of operating licenses or combined licenses until they apply for license renewal.