1 WBN2Public Resource From:
Poole, Justin Sent:
Thursday, June 07, 2012 4:29 PM To:
'garent@tva.gov' Cc:
Bryan, Robert H Jr; WBN2HearingFile Resource
Subject:
Request for Additional Information on Fire Protection
- Gordon, During the staffs review of Fire Protection, the following questions were raised which require a formal response. Given that your next submittal is in progress and is scheduled to be sent to the NRC by 6/28/12, a formal letter would not be practical so this email serves as a formal request for information from the NRC.
Please included this response as an enclosure to the planned Fire Protection Report submittal on 6/28/12. If you have any questions, please contact me. Thanks.
Justin C. Poole Sr. Project Manager NRR/DORL/LPWB U.S. Nuclear Regulatory Commission (301)415-2048 email: Justin.Poole@nrc.gov
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
- 1. Describe the actuation mechanisms for dampers and doors (within CO2 boundaries) that need to close when a CO2 system actuates (i.e., electro-thermal links, system pressure actuated mechanisms, etc.).
- 2. Do any of these dampers or doors rely solely on thermal links to close? If yes, justify the acceptability of this configuration.
Hearing Identifier:
Watts_Bar_2_Operating_LA_Public Email Number:
701 Mail Envelope Properties (19D990B45D535548840D1118C451C74DF1171E493D)
Subject:
Request for Additional Information on Fire Protection Sent Date:
6/7/2012 4:29:25 PM Received Date:
6/7/2012 4:29:21 PM From:
Poole, Justin Created By:
Justin.Poole@nrc.gov Recipients:
"Bryan, Robert H Jr" <rhbryan@tva.gov>
Tracking Status: None "WBN2HearingFile Resource" <WBN2HearingFile.Resource@nrc.gov>
Tracking Status: None
"'garent@tva.gov'" <garent@tva.gov>
Tracking Status: None Post Office:
HQCLSTR02.nrc.gov Files Size Date & Time MESSAGE 1053 6/7/2012 4:29:21 PM Options Priority:
Standard Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
Recipients Received: