ML112410936

From kanterella
Jump to navigation Jump to search
Forwards Updated LER 80-012/01X-1
Date released: 01/17/2020 Download: ML112410936


Forwards Updated LER 80-012/01X-1
ML20003G634
Person / Time
Site: Duane Arnold NextEra Energy icon.png
Issue date: 04/24/1981
From: Mineck D
IES UTILITIES INC., (FORMERLY IOWA ELECTRIC LIGHT
To: KEPPLER J G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML20003G634 (1)
Updated LER 80-012/01X-1:on 800317,standby Diesel Generator 1G-31 Lower Crankshaft Thrust Bearing 13 Was Found Wiped on Journal Surface.Caused by Bearing/Crankshaft Clearance Out of Spec & Low Oil Sump Level.Sump Filled.Bearing Replaced
ML112410935
Person / Time
Site: Duane Arnold NextEra Energy icon.png
Issue date: 04/24/1981
From: Rager M
IES Utilities, (Formerly Iowa Electric Light & Power Co)
To:
NRC/OI/RGN-III/FO
References
Download: ML112410935 (4)