ML112410934

From kanterella
Jump to navigation Jump to search
Forwards Updated LER 80-011/01X-1
Date released: 01/17/2020 Download: ML112410934


Forwards Updated LER 80-011/01X-1
ML20003G624
Person / Time
Site: Duane Arnold NextEra Energy icon.png
Issue date: 04/24/1981
From: Mineck D
IES UTILITIES INC., (FORMERLY IOWA ELECTRIC LIGHT
To: KEPPLER J G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML20003G624 (1)
Updated LER 80-011/01X-1:on 800317,lower Crankshaft Main Thrust Bearing Found Wiped on Thrust & Journal Surfaces During Annual Insp of Standby Diesel Generator 1G-21.Caused by Startups W/Low Oil in Lube Oil Sump.Bearing Replaced
ML112410933
Person / Time
Site: Duane Arnold NextEra Energy icon.png
Issue date: 04/24/1981
From: Rager M
IES Utilities, (Formerly Iowa Electric Light & Power Co)
To:
NRC/OI/RGN-III/FO
References
Download: ML112410933 (5)