ML111960511
ML111960511 | |
Person / Time | |
---|---|
Site: | Salem |
Issue date: | 07/15/2011 |
From: | Burritt A L Reactor Projects Branch 3 |
To: | |
Burritt A L RGN-I/DRP/PB3/610-337-5069 | |
References | |
PNO-I-11-002 | |
Download: ML111960511 (2) | |
Text
DCS No.: 05000311 Date: July 15, 2011 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE - PNO-I-11-002 This preliminary notification constitutes EARLY notice of events of POSSIBLE safety or public interest significance. Some of the information received may not yet be fully verified or evaluated by the Region Staff.
Facility Licensee Emergency Classification PSEG X Notification of Unusual Event Salem Generating Station _____ Alert Hancocks Bridge, NJ _____ Site Area Emergency Docket: 50-311 _____ General Emergency _____ Not Applicable
Subject:
SALEM GENERATING STATION NOTIFICATION OF UNUSUAL EVENT DUE TO REACTOR COOLANT SYSTEM LEAK GREATER THAN 10 GPM AND TECHNICAL SPECIFICATIONS REQUIRED SHUTDOWN Salem Generating Station Unit Two (Salem U2) declared an Unusual Event at 8:53 p.m. on July 14, 2011, based on a greater than 10 gpm leak that occurred during a monthly venting of Emergency Core Cooling System piping. The leak was observed in a safety relief valve line in the high head safety injection piping.
Operators successfully terminated the leak within several minutes by shutting the associated high head safety injection isolation valve. The licensee declared both trains of high head safety injection inoperable and entered both TS 3.0.3 and TS 3.5.2. Salem U2 has completed the required shutdown in accordance with TS 3.0.3 and TS 3.5.2. and is currently in Mode 5.
Salem U2 operators exited the Unusual Event on July 15 at 3:39 a.m. based on termination of the leak and necessary actions to assure the leak would remain isolated. Both trains of high head safety injection remain inoperable pending repairs to the relief valve line. Additional safety-related equipment was not adversely impacted during this event.
The NRC Resident Inspector responded to the site to monitor this event. The NRC will continue to evaluate the event. The NRC Region I Public Affairs Office is prepared to respond to media inquiries.
Region I received initial notification of this occurrence by telephone call from the licensee to the Headquarters Operations Officer at 9:50 p.m. The information presented herein has been discussed with PSEG and is current as of July 15, at 2:30 p.m.
This preliminary notification is issued for information only and no further action by the staff is anticipated.
ADAMS Accession Number: ML111960511
Contacts: Arthur Burritt (610) 337-5069 Arthur.burritt@nrc.gov
DISTRIBUTION (PN Recipient List) BY E-MAIL:
Chairman Jaczko Comm. Svinicki Comm. Magwood Comm. Apostolakis Comm. Ostendorff OIP OCA OGC OPA EDO OE NRR NMSS OIG SECY IRO RES ACRS FSME NSIR NRO PDR RSLO Regional Offices
BY FAX: DOT:Trans INPO NSAC RI Resident Office
- 1. NJ Dept of Environmental Protection Bureau of Nuclear Engineering ATTN: Patrick Mulligan FAX# : 609-984-7513
- 2. NJ Radiological Emergency Response Planning ATTN: Tom Scardino FAX# : 609-530-4593
- 3. Delaware Div of Natural Resources and Environmental Control ATTN: Dr. Harry Otto FAX# : 302-739-7864
- 4. Delaware Emergency Management Agency ATTN: Janet Chomiszak FAX# : 302-659-6855 Licensee: PSEG Salem Generating Station Region I Form 83 (Rev. Nov. 21, 2006)
ADAMS Accession Number: ML111960511
SUNSI Review Complete: ALB (Reviewer
=s Initials) DOCUMENT NAME: G:\DRP\PNS\PNO-I-11-002 Salem RCS Leak UE.DOC After declaring this document AAn Official Agency Record
@ it will be released to the Public.
To receive a copy of this document, indicate in the box:
" C" = Copy without attachment/enclosure " E" = Copy with attachment/enclosure " N" = No copy
OFFICE RI/DRP lhp RI/ORA RI/PAO RI/SLO RI/DRP RI/RA NAME ABurritt /alb RBarkley/rsb DScrenci/dps DTifft/dbt DRoberts/djr WDean/wmd DATE 07/15/11 07/15/11 07/15/11 07/15/11 07/15/11 07/15/11 OFFICIAL RECORD COPY