ATTACHMENT 3 DOSE ESTIMATES
Pen Ind Character/Loc.
Repair steps Time Dose mRem Repair Comments 64 1
Mark indication 6
420 Light Grinding 20 1400 Welding Supv Perform Visual 2
140 Remark Penetration and Clean 3
210 Enter/Exit All Jumps 94 6819 12:00 J-Weld 3/32" x 1/4" Linear Rejectable QC inspection @ 5X PT of area 20 1400 Light Grind to reduce to acceptable Weld over if depth required 64 2
Mark indication 0
0 Light Grinding 0
0 Welding Supv Perform Visual 2
140 Remark Penetration and Clean 3
210 12:00 J-Weld 1/16" x 1/16" Rounded Acceptable QC inspection @ 5X PT of area 1
70 Repaired incidently with #1 64 3
Mark indication 0
0 Light Grinding 15 1050 Welding Supv Perform Visual 2
140 Remark Penetration and Clean 3
210 11:00 1/16" x 1/2" Linear Rejectable QC inspection @ 5X PT of area 1
70 Light Grind to reduce to acceptable Weld over if depth required 64 4
Mark indication 0
0 Light Grinding 22 1540 Welding Supv Perform Visual 2
140 Remark Penetration and Clean 3
210 3:00 1/4" x 1/4" Rounded Rejectable QC inspection @ 5X PT of area 1
70 Light Grind to reduce to acceptable Weld over if depth required 64 5
Mark indication 0
0 Light Grinding 0
0 Welding Supv Perform Visual 0
0 Remark Penetration and Clean 3
210 3:00 1/8" x 1/8" Rounded Acceptable QC inspection @ 5X PT of area 1
70 Possibly will be Repaired incidently with #1 64 6
Mark indication 10 700 Light Grinding 15 1050 Welding Supv Perform Visual 2
140 Remark Penetration and Clean 3
210 2:00 1/8" x 1/2" Linear Rejectable QC inspection @ 5X PT of area 1
70 Light Grind to reduce to acceptable Weld over if depth required
Pen Ind Character/Loc.
Repair steps Time Dose mRem Repair Comments 64 7
Mark indication 0
0 Light Grinding 15 1050 Welding Supv Perform Visual 2
140 Remark Penetration and Clean 3
210 2:00 0
Rounded Rejectable QC inspection @ 5X PT of area 1
70 Light Grind to reduce to acceptable Weld over if depth required 64 8
Mark indication 0
0 Light Grinding 15 1050 Welding Supv Perform Visual 2
140 Remark Penetration and Clean 3
210 5:00 1/16" x 3/16" Linear Rejectable QC inspection @ 5X PT of area 1
70 Light Grind to reduce to acceptable Weld over if depth required 64 9
Mark indication 0
0 Light Grinding 10 700 Welding Supv Perform Visual 2
140 Remark Penetration and Clean 3
210 6:00 1/16" x 3/16" Linear Rejectable QC inspection @ 5X PT of area 1
70 Light Grind to reduce to acceptable Weld over if depth required 31 1
Mark indication 6
420 Light Grinding 15 1050 Welding Supv Perform Visual 2
140 Remark Penetration and Clean 3
210 11:00 1/8" x 3/8" Linear Rejectable QC inspection @ 5X PT of area 15.5 1085 Light Grind to reduce to acceptable Weld over if depth required 31 2
Mark indication 0
0 Light Grinding 15 1050 Welding Supv Perform Visual 2
140 Remark Penetration and Clean 3
210 1:00 1/16" x 1" Linear Rejectable QC inspection @ 5X PT of area 1
70 Light Grind to reduce to acceptable Weld over if depth required 31 3
Mark indication 0
0 Light Grinding 15 1050 Welding Supv Perform Visual 2
140 Remark Penetration and Clean 3
210 1:00 1/4" x 1/4" Rounded Rejectable QC inspection @ 5X PT of area 1
70 Light Grind to reduce to acceptable Weld over if depth required
Pen Ind Character/Loc.
Repair steps Time Dose mRem Repair Comments 31 4
Mark indication 0
0 Light Grinding 22 1540 Welding Supv Perform Visual 2
140 Remark Penetration and Clean 3
210 8:00 1/2" x 5/8" Rounded Rejectable QC inspection @ 5X PT of area 1
70 Local Excavate to reduce to acceptable Weld over if depth required Total REM 28..554 Assumptions:
Only covers penetration 64 and 31 Both options include grinding on 64-4 and 31-4 (pen-Indication)
Both options include weld repair (overlay) on all indications in 64 and 31 No extra time for chasing indications after grinding Actuals for dose used:
Dose at head 70 mrem/min Dose in and out 36 mrem/min Dose on turnovers.1 mrem/min
==
Conclusions:==
Relief request will yield a 7 REM savings for pen 64 and 31 MINIMUM Additional saving should be less for the remaining penetrations since we expect less indication repair.
Overall savings of approx 35% in dose.