,<:r Energy$er.dces Report of Nondestructive Examination Visible, Solvent Removable Liquid Penetrant Examination Page 1 of4 Client:
Exelon (PO # 00000828, Release 00473)
Project No.:
Line/Drawing No.:
N/A (Exelon Relief Request 13R-19)
Weldlltem No:
901 348 Report No.: __
....::...90'0-1,;;3",,4-=;8--,;0.... 4 _
RVHP # 64 Date:
4-06-11 Part Shape / Size:
--'-P"'en"'e:.:t::.:ra::.:t"'io::n:...S"'4'---____ ____
Material Type:
AS SS CladdingiER 309UERNiCrFe-7A Time:
1300 NDE Procedure :
GOP-9.7 Rev.
13 Acceptance Standard:
Appendix A Sec 1.0 & 2.0 Surface Finish:
As Welded/ground Material Thickness:
Approx. O. 200" Stage of Fabrication:
Final PT of J-Weld/Pen 0.0. Overlay Joint Design:
J-Weld/Pen.OD Overlay TYPE II VISIBLE PENETRANT EXAMINATION, METHOD C SOLVENT REMOVABLE Cleaner:
SKC-S Penetrant:
SKL-SP1 Developer:
SKD-S2 Penetrant Application :
Brush Batch No:
10F16K Batch No:
09K02K Batch No:
09L05K Penetrant Removal:
0 1}' Wipe/Solvent Wipe Post-Type of Preclean Penetrant removal Developing Lighting Light B152FC Dry Time:
8Min.
Dwell Time:
15 Min.
Dry Time 7 Min.
Time:
17 Min.
Equipment Flashlight Intensity A150FC Part Cal. Due Light Meter Cal. Due Temperature:
75 OF Thermometer No:
OTC-135 Date:
9-25-11 No:
OLM-15 Dale:
9-15-1 1 IND.
Distance from A R NO:
Zero Dimensions TYPE C E C J 1
12:00 (J-Weld) 3/32" X 1/4" Linear X
2 12:00 (J-Weld) 1116" X 1116" Rounded X
Sketch: See pages 2 through 4 3
11:00 1/16" X 1/2 "
Linear X Comments: B= Before Testing A = After Testing 4
3:00 1/4" X 1/4" Rounded X Note # 1: The only relevant indications on the J-Weld surface overlay surface were 5
3:00 1/8" X 1/8" Rounded X
indications# 1 and 2 located @ 12:00.
Note # 2:There were a couple of areas located @ approximately 2:30that were 6
2:00 118" X y,-
Linear X considered cleaning issues and will need to be re-examined after repair.
7 2:00 1/8" X )1,"
Rounded X
8&9 5:00 & 6:00 1/16" X 3/16" Linear X
Weld / Item is o Acceptable IZI Rejectable Examiner: K~Q~
~4?~evel :
Date
-L~--"-=""'--'C;-
"""'f-~-=-H--":'------ Level: :tJ{: Date:
Reviewer:
Chent
_-,4/",0",6:..;/1,-,1_
Reviewer:
'1/0,,/((
~~~NII
___________ Date: