ML110620010

From kanterella
Jump to navigation Jump to search

E-mail: Point Beach Nuclear Plant, Units 1 and 2 - Draft Requests for Additional Information Cyber Security Plan License Amendment Request
ML110620010
Person / Time
Site: Point Beach  
Issue date: 03/01/2011
From: Beltz T
Plant Licensing Branch III
To: Jim Costedio
Point Beach
beltz T, NRR/DORL/LPL3-1, 301-415-3049
References
TAC ME4248, TAC ME4249
Download: ML110620010 (4)


Text

ADAMS Accession No. ML110620010 From:

Beltz, Terry Sent:

Tuesday, March 01, 2011 2:23 PM To:

'James.Costedio@nexteraenergy.com' Cc:

'Fritzie.Flentje@nexteraenergy.com'

Subject:

Point Beach Nuclear Plant, Units 1 and 2 - Draft Requests for Additional Information re: Cyber Security Plan (TAC Nos. ME4248 and ME4249)

Dear Mr. Costedio:

By letter dated July 8, 2010 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML101970011), as supplemented by letters dated September 28, 2010 (ADAMS Accession Nos. ML102720248), November 12, 2010 (ADAMS Accession No. ML103200079), and November 23, 2010 (ADAMS Accession No. ML103280366), NextEra Energy Point Beach, LLC (the licensee) submitted a request to amend the Renewed Facility Operating License Nos. DPR-24 and DPR-27 for the Point Beach Nuclear Plant, Units 1 and 2, respectively. The amendment request was based on a generic template developed by the Nuclear Energy Institute in concert with the industry. The proposed amendment includes three parts: the proposed PBNP Cyber Security Plan (CSP), an implementation schedule, and a proposed sentence to be added to the Renewed Facility Operating License Physical Protection license condition for NextEra Energy to fully implement and maintain in effect all provisions of the Commission-approved PBNP Cyber Security Plan as required by Title 10 of the Code of Federal Regulations (10 CFR) Section 73.54. Federal Register notice dated March 27, 2009, issued the final rule that amended 10 CFR Part 73.

The U.S. Nuclear Regulatory Commission (NRC) staff is reviewing the proposed CSP amendment request and the proposed CSP implementation schedule, and has determined that additional information is required to complete its technical review. In an effort to complete the review, the NRC staff has developed draft requests for additional information (RAIs). The draft RAIs are provided below:

RAI 1: Records Retention Title 10 of the Code of Federal Regulations (10 CFR) Paragraph 73.54(c)(2) requires licensees to design a cyber security program to ensure the capability to detect, respond to, and recover from cyber attacks. Furthermore, 10 CFR 73.54(e)(2)(i) requires licensees to maintain a cyber security plan that describes how the licensee will maintain the capability for timely detection and response to cyber attacks. The ability for a licensee to detect and respond to cyber attacks requires accurate and complete records and is further supported by 10 CFR 73.54(h), which states that the licensee shall retain all records and supporting technical documentation required to satisfy the requirements of 10 CFR Section 73.54 as a record until the Commission terminates the license for which the records were developed, and shall maintain superseded portions of these records for at least 3 years after the record is superseded, unless otherwise specified by the Commission.

The licensees Cyber Security Plan (CSP) in Section [4.13] states that Critical Digital Asset (CDA) audit records and audit data (e.g., operating system logs, network device logs) are retained for a period of time that is less than what is required by 10 CFR 73.54(h).

Explain the deviation from the 10 CFR 73.54(h) requirement to retain records and supporting technical documentation until the Commission terminates the license (or to maintain superseded portions of these records for at least 3 years) and how that meets the requirements of 10 CFR 73.54.

RAI 2: Implementation Schedule The regulation at 10 CFR 73.54, Protection of digital computer and communication systems and networks, requires licensees to submit a CSP that satisfies the requirements of this section for Commission review and approval. Furthermore, each submittal must include a proposed implementation schedule and the implementation of the licensees cyber security program must be consistent with the approved schedule. Paragraph 73.54(a) of 10 CFR requires licensees to provide high assurance that digital computer and communication systems and networks are adequately protected against cyber attacks, up to and including the design basis threat.

The completion of several key intermediate milestones (Items (a) through (g) below) would demonstrate progress toward meeting the requirements of 10 CFR 73.54. The Nuclear Regulatory Commission (NRC) staffs expectation is that the key intermediate milestones will be completed in a timely manner, but no later than December 31, 2012. The key CSP implementation milestones are as follows:

(a) Establish, train and qualify Cyber Security Assessment Team, as described in Section 3.1.2, Cyber Security Assessment Team, of the CSP.

(b) Identify Critical Systems and CDAs, as described in Section 3.1.3, Identification of Critical Digital Assets, of the CSP.

(c) Implement cyber security defense-in-depth architecture by installation of

[deterministic one-way] devices, as described in Section 4.3, Defense-In-Depth Protective Strategies of the CSP.

(d) Implement the management, operational and technical cyber security controls that address attacks promulgated by use of portable media, portable devices, and portable equipment as described in Appendix D Section 1.19 Access Control for Portable and Mobile Devices, of Nuclear Energy Institute (NEI) 08-09, Revision 6.

(e) Implement observation and identification of obvious cyber related tampering to existing insider mitigation rounds as described in Appendix E Section 4.3, Personnel Performing Maintenance and Testing Activities, and Appendix E Section 10.3, Baseline Configuration of NEI 08-09, Revision 6.

(f) Identify, document, and implement cyber security controls to physical security target set CDAs in accordance with Section 3.1.6, Mitigation of Vulnerabilities and Application of Cyber Security Controls, of the CSP.

(g) Ongoing monitoring and assessment activities will commence for those target set CDAs whose security controls have been implemented, as described in Section 4.4, Ongoing Monitoring and Assessment, of the CSP (h) Full implementation of the CSP for all safety, security, and emergency preparedness functions.

Provide a revised CSP implementation schedule that identifies the appropriate milestones, completion dates, supporting rationale, and level of detail to allow the NRC to evaluate the licensees proposed schedule and associated milestone dates which include the final completion date. It is the NRCs intention to develop a license condition incorporating your revised CSP implementation schedule containing the key milestone dates.

RAI 3: Scope of Systems Paragraph 73.54(a) of 10 CFR requires licensees to provide high assurance that digital computer and communication systems and networks are adequately protected against cyber attacks, up to and including the design basis threat as described in 10 CFR 73.1. In addition, 10 CFR 73.54(a)(1) states that the licensee shall protect digital computer and communication systems and networks associated with:

(i) Safety-related and important-to-safety functions; (ii) Security functions; (iii) Emergency preparedness functions, including offsite communications; and (iv) Support systems and equipment which, if compromised, would adversely impact safety, security, or emergency preparedness functions.

Subsequent to the issuance of the cyber security rule, the NRC stated that 10 CFR 73.54 should be interpreted to include structures, systems, and components (SSCs) in the balance of plant (BOP) that have a nexus to radiological health and safety (Agencywide Documents Access and Management System (ADAMS) Accession No. ML103490344, dated November 19, 2010). The SSCs in the BOP are those that could directly or indirectly affect reactivity of a nuclear power plant and could result in an unplanned reactor shutdown or transient and are therefore, within the scope of important-to-safety functions described in 10 CFR 73.54(a)(1). Furthermore, the NRC issued a letter to NEI dated January 5, 2011 (ADAMS Accession No. ML103550480) that provided licensees with additional guidance on one acceptable approach to comply with the Commissions policy determination.

Explain how the scoping of systems provided by the licensees CSP meets the requirements of 10 CFR 73.54 and the additional guidance provided by the NRC.

If your require additional clarification, the NRC staff can discuss the draft RAIs with your staff in a conference call or meeting prior to formal issuance. Among other things, the discussion will include how the NRC would formally issue these questions and how the licensee will respond to them. The NRC is requesting licensees to formally respond to the RAIs within 30 days.

The sole purpose of this e-mail and its attachment is to prepare you and others for the proposed conference call or meeting. This e-mail and its attachment do not convey a formal NRC staff position, and do not formally request for additional information.

Please don't hesitate to contact me if you have any questions or concerns.

Sincerely, Terry A. Beltz, Senior Project Manager Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation (301) 415-3049 Terry.Beltz@nrc.gov