Text
1 WBN2Public Resource From:
Poole, Justin Sent:
Friday, January 14, 2011 9:10 AM To:
McLellan, Thomas Cc:
WBN2HearingFile Resource
Subject:
FW: TVA letter to NRC_1-13-11_ASME Sec XI Code Request for PSI Activities Attachments:
1-13-11_ASME Sec XI Code Request for PSI Activities_Final.pdf The official version should be in ADAMS either later today or Tuesday.
JustinC.Poole ProjectManager NRR/DORL/LPWB U.S.NuclearRegulatoryCommission (301)4152048 email:Justin.Poole@nrc.gov From: Boyd, Desiree L [1]
Sent: Friday, January 14, 2011 8:52 AM To: Epperson, Dan; Poole, Justin; Raghavan, Rags; Milano, Patrick; Campbell, Stephen Cc: Crouch, William D; Hamill, Carol L; Boyd, Desiree L; Knuettel, Edward Terry
Subject:
TVA letter to NRC_1-13-11_ASME Sec XI Code Request for PSI Activities PleaseseeattachedTVAletterthatwassenttotheNRCtoday.
~*~*~*~*~*~*~*~*~*~*~*~*~*~*~
Désireé L. Boyd WBN2LicensingSupport SunTechnicalServices dlboyd@tva.gov 4233658764
~*~*~*~*~*~*~*~*~*~*~*~*~*~*~
Hearing Identifier:
Watts_Bar_2_Operating_LA_Public Email Number:
269 Mail Envelope Properties (19D990B45D535548840D1118C451C74D7B646AE410)
Subject:
FW: TVA letter to NRC_1-13-11_ASME Sec XI Code Request for PSI Activities Sent Date:
1/14/2011 9:09:58 AM Received Date:
1/14/2011 9:10:00 AM From:
Poole, Justin Created By:
Justin.Poole@nrc.gov Recipients:
"WBN2HearingFile Resource" <WBN2HearingFile.Resource@nrc.gov>
Tracking Status: None "McLellan, Thomas" <Thomas.McLellan@nrc.gov>
Tracking Status: None Post Office:
HQCLSTR02.nrc.gov Files Size Date & Time MESSAGE 881 1/14/2011 9:10:00 AM 1-13-11_ASME Sec XI Code Request for PSI Activities_Final.pdf 395046 Options Priority:
Standard Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
Recipients Received:
U.S. Nuclear Regulatory Commission Page 2 January 13, 2011
Enclosure:
Tennessee Valley Authority, Watts Bar Nuclear Plant (WBN) Unit 2, American Society of Mechanical Engineers (ASME)Section XI Request for Relief WBN-2/PSI-2 cc (Enclosure):
U. S. Nuclear Regulatory Commission Region II Marquis One Tower 245 Peachtree Center Ave., NE Suite 1200 Atlanta, Georgia 30303-1257 NRC Resident Inspector Unit 2 Watts Bar Nuclear Plant 1260 Nuclear Plant Road Spring City, Tennessee 37381
U.S. Nuclear Regulatory Commission Page 3 January 13, 2011 bcc (Enclosure):
Stephen Campbell U.S. Nuclear Regulatory Commission MS 08H4A One White Flint North 11555 Rockville Pike Rockville, Maryland 20852-2738 Charles Casto, Deputy Regional Administrator for Construction U. S. Nuclear Regulatory Commission Region II Marquis One Tower 245 Peachtree Center Ave., NE Suite 1200 Atlanta, Georgia 30303-1257
ENCLOSURE TENNESSEE VALLEY AUTHORITY WATTS BAR NUCLEAR PLANT (WBN) UNIT 2 AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) SECTION XI REQUEST FOR RELIEF WBN-2/PSI-2 TVA requests approval to use the alternative ASME Section XI Code year and addenda for the completion of WBN Unit 2. The alternate ASME Code for Preservice Inspection (PSI) activities is based on the ASME Section XI Edition and Addenda approved at the time construction was resumed on WBN Unit 2.
EXECUTIVE
SUMMARY
In accordance with 10 CFR 50.55a(a)(3)(i), TVA is requesting relief to utilize a later Code of Record for PSI activities during the completion of WBN Unit 2. Section 50.55a(g)(2) requires the PSI Code of Record to be based on the ASME Section XI Code in effect six months prior to the date of issue of the Construction Permit. Because the construction permit for WBN Unit 2, CPPR-92, is dated January 23, 1973, the applicable Code would be the 1971 Edition through Winter 1971 Addenda of ASME Section XI. Since 10 CFR 50.55a(g)(2) also allows the use of subsequent Code Editions/Addenda, which are incorporated by reference in 10 CFR 50.55a(b)(2), TVA identified the 2001 Edition through 2003 Addenda as the applicable Code of Record based on the date associated with resumption of construction activities.
SYSTEM/COMPONENTS FOR WHICH RELIEF IS REQUESTED:
ASME Code Class 1, 2, 3, IWF, and MC components including the applicable Examination Categories and Item Numbers.
APPLICABLE CODE EDITION AND ADDENDA FOR THE GIVEN EXAM:
The ASME Section XI Code Edition and Addenda Code of Record requested for the WBN Unit 2 construction completion project PSI is the 2001 Edition through 2003 Addenda, as amended by 10 CFR 50.55a and those Code Cases either approved for use by Regulatory Guide 1.147 and adopted by WBN Unit 2 or where specific relief has been granted by NRC.
REQUIREMENTS FROM WHICH RELIEF IS REQUESTED:
Permission is requested to adopt a later NRC-approved Code Edition and Addenda as provided in 10 CFR 50.55a(g)(2), in place of the Code of Record as determined by the date of the construction permit.
RELIEF REQUESTED:
Section 50.55a(g)(2) requires the PSI Code of Record to be based on the ASME Section XI Code in effect six months prior to the date of issue of the Construction Permit. Because the construction permit for WBN Unit 2, CPPR-92, is dated January 23, 1973, the applicable Code would be the 1971 Edition through Winter 1971 Addenda of ASME Section XI. Since 10 CFR 50.55a(g)(2) also allows the use of subsequent Code Editions/Addenda, which are incorporated by reference in 10 CFR 50.55a(b)(2), TVA identified the 2001 Edition through 2003 Addenda as E-1
ENCLOSURE TENNESSEE VALLEY AUTHORITY WATTS BAR NUCLEAR PLANT (WBN) UNIT 2 AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) SECTION XI REQUEST FOR RELIEF WBN-2/PSI-2 E-2 the applicable Code of record based on the date associated with resumption of construction activities.
BASIS FOR RELIEF:
Construction activities at WBN Unit 2 resumed approximately 35 years after the initial construction permit was issued. The 10 CFR 50.55a(g)(2) method for determining the PSI code of record requires the use of the 1971 Edition though Winter 1971 (71/W71) Addenda of ASME Section XI; however, the provision in 10 CFR 50.55a(g)(2) to allow the use of subsequent Code Editions/Addenda, which are incorporated by reference in 10 CFR 50.55a(b)(2), allows the use of a technically superior PSI Code of Record based on 30 years of ASME Code committee knowledge and revisions. For example, Class MC, metal containment, examination was not required in the 71/W71 Section XI code, but it is a requirement of Subsection IWE of the 2001 Edition through 2003 Addenda of ASME Section XI.
PROPOSED ALTERNATIVES:
Utilize the 2001 Edition through 2003 Addenda of ASME Section XI for WBN Unit 2 construction completion activities subject to the modifications and limitations imposed by 10 CFR 50.55a.
JUSTIFICATION FOR GRANTING RELIEF:
The 2001 Edition through 2003 Addenda of ASME Section XI was approved for use in 10 CFR 50.55a(b)(2), and 10 CFR 50.55a(g)(2) allows the use of subsequent Code Editions/Addenda that are incorporated by reference in 10 CFR 50.55a(b)(2). The version of 10 CFR 50.55a(b)(2) in place in 2008 states:
(2) As used in this section, references to Section XI of the ASME Boiler and Pressure Vessel Code refer to Section XI, and include the 1970 Edition through the 1976 Winter Addenda, and the 1977 Edition (Division 1) through the 2003 Addenda (Division 1)....
The 2001 Edition through 2003 Addenda of ASME Section XI incorporates 30 years of technical lessons learned when compared to the 1971 Edition through Winter 1971 Addenda of the ASME Section XI Code. Thus, the requested relief would permit use of the code that was current at the time construction activities resumed at WBN Unit 2.
IMPLEMENTATION SCHEDULE AND DURATION:
This relief will be utilized for the duration of PSI activities associated with the completion of WBN Unit 2.