ML110040854
ML110040854 | |
Person / Time | |
---|---|
Site: | Bellefonte ![]() |
Issue date: | 12/22/2010 |
From: | Arent G Tennessee Valley Authority |
To: | Document Control Desk, Office of New Reactors |
Spink T | |
References | |
BELLEFONTE.P02.NP, BELLEFONTE.P02.NP.3, TENNVALLEY, TENNVALLEY.SUBMISSION.6, +reviewedmmc1 | |
Download: ML110040854 (1) | |
Similar Documents at Bellefonte | |
---|---|
Category:Final Safety Analysis Report (FSAR)
MONTHYEARML1100406312010-12-22022 December 2010
[Table view]Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-214 ML1100405742010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-276 ML1100405752010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-277 ML1100405762010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-278 ML1100405772010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-279 ML1100405782010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-280 ML1100405792010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-281 ML1100405802010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-282 ML1100405812010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-283 ML1100405822010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-284 ML1100405832010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-285 ML1100405842010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-286 ML1100405852010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-287 ML1100405862010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-288 ML1100405872010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-289 ML1100405892010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-290 ML1100405902010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-291 ML1100405912010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-292 ML1100405922010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-293 ML1100405932010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-294 ML1100405942010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-295 ML1100405952010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-296 ML1100405962010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-297 ML1100405972010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-298 ML1100405982010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-299 ML1100405992010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-300 ML1100406002010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-301 ML1100406012010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-302 ML1100406022010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-303 ML1100406042010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-201 ML1100406052010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-202 ML1100406072010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-203 ML1100406082010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-204 ML1100406092010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-205 ML1100406102010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-206 ML1100406112010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-207 ML1100406122010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-208 ML1100406132010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.2-202 ML1100406142010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.2-203 ML1100406162010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.2-204 ML1100406172010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-201 ML1100406182010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-202 ML1100406192010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-203 ML1100406202010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-204 ML1100406212010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-205 ML1100406222010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-206 ML1100406232010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-207 ML1100406252010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-208 ML1100406262010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-209 ML1100406272010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-210 2010-12-22 Category:License-Application for Combined License (COLA) MONTHYEARML1100406312010-12-22022 December 2010
[Table view]Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-214 ML1100405742010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-276 ML1100405752010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-277 ML1100405762010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-278 ML1100405772010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-279 ML1100405782010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-280 ML1100405792010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-281 ML1100405802010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-282 ML1100405812010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-283 ML1100405822010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-284 ML1100405832010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-285 ML1100405842010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-286 ML1100405852010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-287 ML1100405862010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-288 ML1100405872010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-289 ML1100405892010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-290 ML1100405902010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-291 ML1100405912010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-292 ML1100405922010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-293 ML1100405932010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-294 ML1100405942010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-295 ML1100405952010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-296 ML1100405962010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-297 ML1100405972010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-298 ML1100405982010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-299 ML1100405992010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-300 ML1100406002010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-301 ML1100406012010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-302 ML1100406022010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.3-303 ML1100406042010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-201 ML1100406052010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-202 ML1100406072010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-203 ML1100406082010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-204 ML1100406092010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-205 ML1100406102010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-206 ML1100406112010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-207 ML1100406122010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.1-208 ML1100406132010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.2-202 ML1100406142010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.2-203 ML1100406162010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.2-204 ML1100406172010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-201 ML1100406182010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-202 ML1100406192010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-203 ML1100406202010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-204 ML1100406212010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-205 ML1100406222010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-206 ML1100406232010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-207 ML1100406252010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-208 ML1100406262010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-209 ML1100406272010-12-22022 December 2010 Bellefonte Units 3 & 4 Cola (Final Safety Analysis Report), Rev. 3 - FSAR Chapter 02 Figure 2.4.3-210 2010-12-22 |
Text
Bellefonte Nuclear Plant, Units 3 & 4 COL Application Part 2, FSAR 100 Class I Fill Properties Fines Content >30% and PI >30. (Not Liquefiable 90 according to Regulatory Guide 1.198.)
Fines Content >30% and classified as Clay 80 (CL-CH) by USCS. Also Water Content is <80% of LL. (Not liquefiable according to Regulatory 70 Guide 1.198, and Seed et al. 2003). e Lin Silt with PI>20 and LL>50. (Not liquefiable U-Pl (Plasticity Index) 60 according to Seed et al. 2003).
ine 50 A-L CH 40 MH 30 CL 20 Zone B: Test if WC > 0.85 (LL) 10 7 Zone A: Potentially Liquefiable if WC > 0.8 (LL)
CL-ML 0
0 10 20 30 40 50 60 70 80 90 100 Screening Method is Applicable Modified from Seed et al. 2003 (Reference 454) for Samples With: LL (Liquid Limit)
(a) FC > 20% if PI > 12%
(b) FC > 35% if PI < 12%
FIGURE 2.5-359 BLN COL 2.5-9 Plasticity Index vs. Liquid Limit Liquefaction Assessment Rev 0