U.S. NUCLEAR REGULATORY COMMISSION August 2012 OFFICE OF NUCLEAR REGULATORY RESEARCH Division 1 DRAFT REGULATORY GUIDE

Contact:

K. Sturzebecher (301) 251-7494 This regulatory guide is being issued in draft form to involve the public in the early stages of the development of a regulatory position in this area. It has not received final staff review or approval and does not represent an official NRC final staff position.

Public comments are being solicited on this draft guide (including any implementation schedule) and its associated regulatory analysis or value/impact statement. Comments should be accompanied by appropriate supporting data. Written comments may be submitted to the Rules, Announcements, and Directives Branch, Office of Administration, U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001; submitted through the NRCs interactive rulemaking Web page at http://www.nrc.gov; or faxed to (301) 492-3446. Copies of comments received may be examined at the NRCs Public Document Room, 11555 Rockville Pike, Rockville, MD. Comments will be most helpful if received by November 23, 2012.

Electronic copies of this draft regulatory guide are available through the NRCs interactive rulemaking Web page (see above); the NRCs public Web site under Draft Regulatory Guides in the Regulatory Guides document collection of the NRCs Electronic Reading Room at http://www.nrc.gov/reading-rm/doc-collections/; and the NRCs Agencywide Documents Access and Management System (ADAMS) at http://www.nrc.gov/reading-rm/adams.html, under Accession No. ML103080963. The regulatory analysis may be found in ADAMS under Accession No. ML103080966.

DRAFT REGULATORY GUIDE DG-1209 (Proposed Revision 1 of Regulatory Guide 1.172, dated September 1997)

SOFTWARE REQUIREMENT SPECIFICATIONS FOR DIGITAL COMPUTER SOFTWARE AND COMPLEX ELECTRONICS USED IN SAFETY SYSTEMS OF NUCLEAR POWER PLANTS A. INTRODUCTION This guide describes a method that the staff of the U.S. Nuclear Regulatory Commission (NRC) considers acceptable for use in complying with NRC regulations on software requirement specifications (SRSs) for digital computer software used in the safety systems of nuclear power plants.

The regulatory framework that the NRC has established for nuclear power plants consists of a number of regulations and supporting guidelines applicable to the SRSs for digital computer software.

Title 10, of the Code of Federal Regulations, Part 50, Domestic Licensing of Production and Utilization Facilities (10 CFR Part 50) (Ref. 1), Appendix A, General Design Criteria for Nuclear Power Plants, General Design Criterion (GDC) 1, requires, in part, that systems and components be designed, tested, and inspected to quality standards commensurate with the safety function to be performed, while the nuclear power unit licensee maintain, or control the maintenance of, appropriate records on the design and testing of systems and components important to safety throughout the life of the unit. Appendix B, Quality Assurance Criteria for Nuclear Power Plants and Fuel Reprocessing Plants, to 10 CFR Part 50 describes criteria that a quality assurance program must meet for systems and components that prevent or mitigate the consequences of postulated accidents. In addition to the systems and components that directly prevent or mitigate the consequences of postulated accidents, the Appendix B criteria also apply to all activities, including design, purchasing, installation, testing, operation, maintenance, or modification, that affect the safety-related functions of systems and components.

In 10 CFR 50.55a(a)(1), the NRC requires, in part, that systems and components be designed, fabricated, erected, tested, and inspected to quality standards commensurate with the safety function to be performed. 10 CFR 50.55a(h) require licensees to satisfy the criteria for reactor protection systems in Institute of Electrical and Electronics Engineers (IEEE) Standard (Std.) 603-1991, IEEE Standard

DG-1209, Page 2 Criteria for Safety Systems for Nuclear Power Generating Stations, issued 1991 (including a correction sheet dated January 30, 1995) (Ref. 2), or in IEEE Std. 279-1971, Criteria for Protection Systems for Nuclear Power Generating Stations, issued 1971 (Ref. 3). These criteria shall be part of the evaluation of the recognized quality codes and standards selected for their applicability, adequacy, and sufficiency and shall be supplemented or modified as needed to assure a quality product and that it will perform the required safety function. The guidance for safety system equipment employing digital computers and programs or firmware requires the use of a quality standard for the development of software and firmware requirement specifications.

This regulatory guide endorses IEEE Std. 830-1998, IEEE Recommended Practice for Software Requirements Specifications, issued in 1998 and reaffirmed in 2009 (Ref. 4), with the exceptions stated in the regulatory positions. IEEE Std. 830-1998 describes methods that the NRC staff considers acceptable for use in complying with the NRC regulations for achieving high functional reliability and design quality in software used in safety systems.1 In particular, the methods are consistent with the previously cited GDC and the criteria for quality assurance programs in Appendix B to 10 CFR Part 50 as they apply to the development of SRSs. The criteria of Appendix A and Appendix B to 10 CFR Part 50 apply to systems and related quality standards and quality assurance processes as well as the software elements of those systems.

The NRC issues regulatory guides to describe to the public methods that the staff considers acceptable for use in implementing specific parts of the agencys regulations, to explain techniques that the staff uses in evaluating specific problems or postulated accidents, and to provide guidance to applicants. However regulatory guides are not substitutes for regulations and compliance with them is not required. The information provided by this regulatory guide is also in the Standard Review Plan, NUREG-0800, Standard Review Plan for the Review of Safety Analysis Reports for Nuclear Power Plants: LWR Edition, Chapter 7, Instrumentation and Controls, (Ref. 5). The NRC staff uses the NRC Standard Review Plan to review 10 CFR Part 50 and 10 CFR Part 52, Licenses, Certifications, and Approvals for Nuclear Power Plants, (Ref. 6) license applications.

This regulatory guide contains information collection requirements covered by 10 CFR Part 50 that the Office of Management and Budget (OMB) approved under OMB control number 3150-0011.

The NRC may neither conduct nor sponsor, and a person is not required to respond to, an information collection request or requirement unless the requesting document displays a currently valid OMB control number. This regulatory guide is a rule as designated in the Congressional Review Act (5 U.S.C. 801-808). However, OMB has not found it to be a major rule as designated in the Congressional Review Act.

B. DISCUSSION

=

Background===

The use of industry consensus standards, such as IEEE standards is part of an overall approach to meeting the requirements of 10 CFR Part 50 when developing safety systems for nuclear power plants. A licensees compliance with these standards does not guarantee that it will meet regulatory requirements.

However, the licensees compliance with these standards does ensure that it will incorporate practices accepted within various technical communities into the development and quality assurance processes used 1

The term safety systems is synonymous with safety-related systems. The GDC of Appendix A to 10 CFR Part 50 cover systems, structures, and components important to safety. However, the scope of this regulatory guide is limited to safety systems, which are a subset of systems important to safety.

DG-1209, Page 3 to design safety systems. These practices are based on past experience and represent industry consensus on approaches used for the development of such systems.

Several criteria in Appendix A to 10 CFR Part 50 describe functions that are part of the design bases of nuclear power plants and that would be included in the SRSs of any digital computer software that is part of the basic components that perform these functions. These listed criteria include part of GDC requirements such as: GDC 1, Quality Standards and Records, GDC 12, Suppression of Reactor Power Oscillations, GDC 13, Instrumentation and Control, GDC 19, Control Room, GDC 20, Protection System Functions, GDC 22, Protection System Independence, GDC 23, Protection System Failure Modes, GDC 24, Separation of Protection and Control Systems, GDC 25, Protection System Requirements for Reactivity Control Malfunctions, and GDC 28, Reactivity Limits.

In addition to the criteria of Appendix A, this regulatory guide refers to software incorporated into the instrumentation and control systems covered by Appendix B to 10 CFR Part 50 as safety system software. The SRS is an essential part of the record of the design of safety system software. Software requirements are associated with the system requirements allocated to software subsystems and serve as the design bases for the software under development. Therefore, SRSs are a crucial design input to the remainder of the software development process. SRSs should exhibit characteristics such as correctness and completeness that will facilitate the implementation of a carefully planned and controlled software development process. Appendix B to 10 CFR Part 50 provides quality assurance criteria that the design documentation for nuclear reactor safety systems must meet through design control measures. Criterion III, Design Control, of Appendix B requires licensees to develop these control measures for design documentation and identification and the control of design interfaces and measures for verifying or checking the adequacy of the design.

Description of Change The original version of this regulatory guide endorsed IEEE Std. 830-1993. There are only minor changes between IEEE Std. 830-1998 and the original 1993 version. This version of Regulatory Guide 1.172 endorses IEEE Std. 830-1998, specifically addresses Annex B, and corrects three other perspectives associated with the software attributes of an SRS. The addressed areas are: the enhancements in Security, Unambiguity and the deleting an existing regulatory guide section called Nonapplicability.

The original regulatory guide contained a section called Nonapplicability, which has been removed from this version, because of the changes in the way software is viewed and documented. All subjects associated with the development of safety system are applicable for review. Within this same venue is a new section to this regulatory guide called Unambiguity. This subject in IEEE 830-1998 is important because of the way digital systems interact with a variety of associated software products. As full or partial digital systems are introduced into the nuclear power designs the clarity of the SRS becomes extremely important. This is also the case where associated features during the design phase must be identified, as stated in RG 1.170, Software Test Documentation for Digital Computer Software Used in Safety Systems of Nuclear Power Plants, (Ref. 7).

The NRC staff recognizes that security features or mechanisms can also play a critical role in supporting software security at higher levels of assurance. IEEE Std. 830-1998 supports this by identifying security as a specific attribute and project objective found in the SRS requirements of the safety software. Subclause 5.3.6.3 of IEEE Std. 830-1998 is not endorsed in this regulatory guide as having sufficient details for protecting software. To meet criteria of IEEE Std. 603-1991 and 10 CFR 50, the development of digital safety system software requires a secure development and operational

DG-1209, Page 4 environment (SDOE) be provided, Regulatory Guide 1.152, provides specific guidance concerning the establishment of SDOEs.

Applicants should be aware that other NRC requirements and guidance may lead to specific cyber security controls during the software development process and /or the inclusion of security features in or around digital safety systems. However, a licensees adherence to the provisions of 10 CFR 73.54, Protection of Digital Computer and Communication Systems and Networks, (Ref. 8) will be evaluated per regulatory programs specific to that regulation and in accordance with the applicant's NRC-approved cyber security plan. IEEE Std. 830-1998 is not endorsed in this regulatory guide as being appropriate for compliance with 10 CFR 73.54.

Related Guidance IEEE Std. 830-1998, a consensus standard on software engineering, describes the current practice for writing SRSs for a wide variety of systems. While this standard is not specifically aimed at safety applications, it does, however, provide guidance on the development of SRSs that will exhibit characteristics important in the development of safety system software. This guidance is consistent with the NRCs goals of promoting high functional reliability and design quality in software used in safety systems.

Other standards that mention SRSs but do not provide detailed guidance for writing them include:

IEEE Std. 7-4.3.2-2003, IEEE Standard Criteria for Digital Computers in Safety Systems of Nuclear Power Generating Stations, issued 2003 (Ref. 9), identifies unambiguous software requirements as a prerequisite for high-quality software development. Regulatory Guide 1.152, Criteria for Use of Computers in Safety Systems of Nuclear Power Plants (Ref. 10), endorses this standard.

IEEE Std. 1012-2004, IEEE Standard for Software Verification and Validation, issued 2004 (Ref. 11), also identifies unambiguous software requirements as a prerequisite for verification and validation. Regulatory Guide 1.168, Verification, Validation, Reviews, and Audits for Digital Computer Software Used in Safety Systems of Nuclear Power Plants (Ref. 12), endorses this standard.

IEEE Std. 1074-2006, IEEE Standard for Developing a Software Life Cycle Process, issued 2006 (Ref. 13), describes SRSs as an essential input at the beginning of a software development life cycle. Regulatory Guide 1.173, Developing Software Life Cycle Processes for Digital Computer Software Used in Safety Systems of Nuclear Power Plants (Ref. 14), endorses this standard.

The correct, complete, well-written, and unambiguous software requirements are essential inputs to the main design and verification processes that the NRC considers necessary to produce safety-related software products. To assist in this effort there are other NRC documents available. (See NUREG/CR-6101, Software Reliability and Safety in Nuclear Reactor Protection Systems, issued November 1993 (Ref. 15), and NUREG/CR-6263, High Integrity Software for Nuclear Power Plants: Candidate Guidelines, Technical Basis, and Research Needs, issued June 1995 (Ref. 16))

The software development process has several supporting regulatory guides to promote high functional reliability and design quality in the software used in safety systems. These guides include the following:

DG-1209, Page 5

a.

Regulatory Guide 1.168, Verification, Validation, Reviews, and Audits for Digital Computer Software Used in Safety Systems of Nuclear Power Plants,

b.

Regulatory Guide 1.169, Configuration Management Plans for Digital Computer Software Used in Safety Systems of Nuclear Power Plants (Ref. 17),

c.

Regulatory Guide 1.170, Software Test Documentation for Digital Computer Software Used in Safety Systems of Nuclear Power Plants,

d.

Regulatory Guide 1.171, Software Unit Testing for Digital Computer Software Used in Safety Systems of Nuclear Power Plants (Ref. 18), and

e.

Regulatory Guide 1.173, Developing Software Life-Cycle Processes for Digital Computer Software Used in Safety Systems of Nuclear Power Plants.

This regulatory guide is based on standards and describes methods acceptable for any safety system software and discusses the required SRS activities. The applicant or licensee determines how the required activities will be implemented.

Other Codes and Standards This regulatory guide endorses the use of one or more voluntary consensus codes or standards developed by external organizations. These codes or standards may contain references to other codes or standards. These references should be considered individually. If a referenced standard has been incorporated separately into NRC regulations, licensees and applicants must comply with that standard as set forth in the regulation. If the referenced standard has been endorsed in a regulatory guide, the standard constitutes a method acceptable to the NRC staff for meeting a regulatory requirement as described in the specific regulatory guide. If a referenced standard has been neither incorporated into NRC regulations nor endorsed in a regulatory guide, licensees and applicants may consider and use the information in the referenced standard, if appropriately justified and consistent with current regulatory practice.

Harmonization with International Standards This regulatory guide endorses, in whole or in part, multiple international consensus standards produced by international organizations such as the Institute of Electrical and Electronic Engineers (IEEE).

The IEEE is a non-profit professional association dedicated to advancing technological innovation and excellence. It has more than 400,000 members in more than 160 countries and produces 30 percent of the world's literature in the electrical and electronics engineering and computer science fields including multiple tutorials and standards produced by its standardization committees.

Endorsement, in whole or in part, of multiple international standards reduces the need for the development of unique NRC standards and is consistent with the agency goal of improved harmonization with international organizations.

DG-1209, Page 6 C. STAFF REGULATORY GUIDANCE IEEE Std. 830-1998 provides an approach that the NRC staff considers acceptable for meeting the requirements in 10 CFR Part 50 on the preparation of SRSs for safety system software with the exceptions and additions listed in these regulatory positions. In this section of the guide, the cited criterion refers to Appendix A or B to 10 CFR Part 50 unless otherwise noted.

1.

Definitions Clause 3 of IEEE Std. 830-1998 refers to IEEE Std. 610.12-1990, IEEE Standard Glossary of Software Engineering Terminology, issued 1990 (Ref. 19), for the definitions of technical terms. These definitions are acceptable with the following clarifications and additions:

a.

Baseline. Meaning No. 1 of baseline in IEEE Std. 610.12-1990 must be used in IEEE Std. 830-1998. Formal review and agreement is considered to mean that responsible management has reviewed and approved a baseline.

b.

Interface. All four variations of the definition of interface in IEEE Std. 610.12-1990 must be used in IEEE Std. 830-1998, depending on the context. Meaning No. 1, a shared boundary across which information is passed, is interpreted broadly, according to Criterion III of Appendix B to 10 CFR Part 50, to include design interfaces between participating design organizations.

2.

Software Requirement Specifications Clause 4.3 of IEEE Std. 830-1998 defines a set of characteristics of an acceptable SRS. The first sentence of this clause should be modified to read, An SRS must be. The licensee or applicant should provide the following clarifications and additional information for this set of characteristics for safety system software:

a.

Traceability and Accuracy. When the licensee or applicant uses specifications or representation tools for requirements, as described in Subclauses 4.3.2.2 and 4.3.2.3 of IEEE Std. 830-1998, traceability must be maintained between these representations and the natural language descriptions of the software requirements that are derived from system requirements and system safety analyses to meet the requirements in GDC 1 of Appendix A to 10 CFR Part 50.

b.

Completeness. For safety system software, the description of functional requirements should specify how functions are initiated and terminated and should specify the system status at termination. The licensee or applicant should provide the accuracy requirements, including units, error bounds, data type, and data size, for each input and output variable. The licensee or applicant should fully describe the variables that are controlled or monitored in the physical environment and should describe expressly prohibited functions.

Timing information is particularly important in specifying software requirements for safety system software. The licensee or applicant should identify the functions with timing constraints and provide criteria for each mode of operation. Timing requirements should be deterministic and specified for both normal and anticipated failure conditions.

DG-1209, Page 7

c.

Consistency. Subclause 4.3.4 of IEEE Std. 830-1998 restricts the term consistency to mean internal consistency, noting that an external inconsistency is actually an incorrect specification of a requirement. The NRC uses the term in this regulatory guide to mean both internal and external consistency. External consistency implies that the SRS is consistent with associated software products and system products such as safety system requirements and design. Internal consistency means that no requirement in the requirements specification conflicts with any other requirement in the specification.

d.

Ranking for Importance or Stability. For safety system software, this characteristic means that software requirements important to safety must be identified as such in the SRS. Criterion 20 of Appendix A, among others, describes the function that reactor protection systems must perform. Subclause 4.3.5.2 of IEEE Std. 830-1998 suggests three degrees of necessity for requirements: (1) essential, (2) conditional, and (3) optional. As used in IEEE Std. 830-1998, the terms conditional and optional refer to requirements that are not necessary for the acceptability of the software. For safety system software, unnecessary requirements should not be imposed. There may be documented variations in essential requirements, but the SRSs need to link the variations either to site and equipment variations or to specific plant design bases and regulatory provisions.

e.

Verifiability. Subclause 4.3.6 of IEEE Std. 830-1998 recommends the removal or revision of unverifiable requirements. The NRC believes that all requirements should be verifiable and should be modified or restated as necessary to allow for the verification of each one.

f.

Modifiability. This term is closely related to the style (form, structure, and modularity),

readability, and understandability of the SRS. With respect to these characteristics, precise definitions of technical terms must be available either in the SRS itself or in a glossary.

g.

Traceability. In accordance with GDC 1 of Appendix A to 10 CFR Part 50 and as described in Subclause 4.3.8 of IEEE Std. 830-1998, each identifiable requirement in an SRS must be backward traceable to a higher level requirements specification and ultimately to the system licensing (e.g., regulatory requirements that it satisfies) and the design bases (e.g., IEEE 603-1991 Clause 4). Each identifiable requirement should be written so that it can also be forward traceable to subsequent design outputs (e.g., from SRS to software design and from software design to SRS).

Forward traceability to all documents derived from the SRS includes verification and validation materials. For example, a forward trace should exist from each requirement in the SRS to the specific inspections, analyses, or tests used to confirm that the requirement has been met.

h.

Unambiguity. Subclause 4.3.2 of IEEE Std. 830-1998 states that an SRS is unambiguous if, and only if, every requirement has only one interpretation. Software products and system products are generally derived from software requirements. The relationships established between software requirements and the products that they are used to create should be unambiguous.

DG-1209, Page 8

3.

Change Control in Software Requirement Specifications Subclause 4.5(b) of IEEE Std. 830-1998 recommends that SRSs be baselined and subject to a formal process for the control of changes. Although the licensee or applicant should meet this recommendation directly through a change control procedure unique to IEEE Std. 830-1998, it may also meet it by placing the SRS under a general software configuration management program as a configuration item. Regulatory Guide 1.169 discusses software configuration management and endorses IEEE Std. 828-2005, IEEE Standard for Software Configuration Management Plans, issued 2005 (Ref. 20).

4.

Incomplete Software Requirement Specifications Entry Any entry in an SRS that is incomplete (i.e., uses to be determined or TBD), as described in Subclause 4.3.3.1 of IEEE Std. 830-1998, must describe the applicable design bases and commitments to standards or regulations that govern the final determination of the requirement entry.

5.

Design-Specific Issues Subclause 4.7 of IEEE Std. 830-1998 recommends that design-specific issues, such as module partitioning, function allocation, and information flow, be omitted from SRSs. Subclause 4.7.1 of IEEE Std. 830-1998 states some exceptions to this policy, including reasons of security or safety. When specific design techniques or features, such as independence, separation, diversity, and defense in depth, are required by the safety system design bases or by regulation, they are an appropriate part of an SRS and should be described therein.

6.

Software Attributes Subclause 5.3.6 of IEEE Std. 830-1998 lists software attributes that can serve as requirements.

The following attributes are particularly of interest for safety system software:

a.

Safety. Software requirements important to safety are derived from system requirements and safety analyses and should be identified as such in the SRS. These requirements should include considerations based on the safety analysis report and on abnormal conditions and events as described in IEEE Std. 7-4.3.2-2003, which Regulatory Guide 1.152 endorses.

b.

Secure Analysis. IEEE Std. 830-1998, Subclause 5.3.6.3 Security is not endorsed as having sufficient detail to define specific factors for security attributes along with requirements that are applicable to the SRS. The requirements approach to include a security attribute is useful for the licensee or applicant, however an analysis of specific factors for the SRS can be found in other available guidance. The development of digital safety system software requires a SDOE be provided. Regulatory Guide 1.152, Criteria for Use of Computers in Safety Systems in Nuclear Power Plants, provides specific guidance related to the establishment of SDOE. The SDOE guidance can provide the needed attributes for the SRS.

c.

Robustness. The licensee or applicant should specify the software requirements for fault tolerance and failure modes, derived either from a consideration of system-level hazards analyses or from software internals, for each operating mode. The licensee or applicant should fully specify software behavior in the presence of unexpected, incorrect, anomalous, and improper (1) input, (2) hardware behavior, or (3) software behavior, and

DG-1209, Page 9 should provide software requirements necessary to respond to both hardware and software failures, including the requirements for analysis of, and recovery from, computer system failures. The licensee or applicant should also specify the requirements for online inservice testing and diagnostics.

6.

Annexes IEEE Std. 830-1998 contains the following two informative annexes. These appendixes are listed here as sources of information; they have not received regulatory endorsement unless otherwise noted:

Because the NRC has not endorsed Annex A, SRS Templates, licensees may only use it as an example. Directions on how to use an outline from Annex A, such as those directions found in Clause 5.3.7 of IEEE Std. 830-1998, may be taken as advisory only.

Annex B, Guidelines for Compliance with IEEE/EIA 12207.1-1997, describes the relationship of IEEE Std. 830-1998 to IEEE/Electronic Industries Association (EIA)

Std. 12207.1-1997, Industry Implementation of International Standard ISO/IEC 12207:

1995 (ISO/IEC 12207) Standard for Information Technology-Software Life Cycle Processes-Life Cycle Data, issued April 1998 (Ref. 21). The NRC does not endorse this annex because the agency does not endorse IEEE/EIA Std. 12207.1-1997.

D. IMPLEMENTATION The purpose of this section is to provide information on how applicants and licensees2 may use this guide and information regarding the NRCs plans for using this regulatory guide. In addition, it describes how the NRC staff complies with the Backfit Rule (10 CFR 50.109) and any applicable finality provisions in 10 CFR Part 52.

Use by Applicants and Licensees Applicants and licensees may voluntarily3 use the guidance in this document to demonstrate compliance with the underlying NRC regulations. Methods or solutions that differ from those described in this regulatory guide may be deemed acceptable if they provide sufficient basis and information for the NRC staff to verify that the proposed alternative demonstrates compliance with the appropriate NRC regulations. Current licensees may continue to use guidance the NRC found acceptable for complying with the identified regulations as long as their current licensing basis remains unchanged.

Licensees may use the information in this regulatory guide for actions which do not require NRC review and approval such as changes to a facility design under 10 CFR 50.59. Licensees may use the information in this regulatory guide or applicable parts to resolve regulatory or inspection issues.

This regulatory guide is not being imposed upon current licensees and may be voluntarily used by existing licensees.

2 In this section, licensees refers to licensees of nuclear power plants under 10 CFR Parts 50 and 52; and the term applicants, refers to applicants for licenses and permits for (or relating to) nuclear power plants under 10 CFR Parts 50 and 52, and applicants for standard design approvals and standard design certifications under 10 CFR Part 52.

3 In this section, voluntary and voluntarily means that the licensee is seeking the action of its own accord, without the force of a legally binding requirement or an NRC representation of further licensing or enforcement action.

DG-1209, Page 10 If a licensee believes that the NRC is either using this regulatory guide or requesting or requiring the licensee to implement the methods or processes in this regulatory guide in a manner inconsistent with the discussion in this Implementation section, then the licensee may file a backfit appeal with the NRC in accordance with the guidance in NUREG-1409 and NRC Management Directive 8.4.

Use by NRC Staff During regulatory discussions on plant specific operational issues, the staff may discuss with licensees various actions consistent with staff positions in this regulatory guide, as one acceptable means of meeting the underlying NRC regulatory requirement. Such discussions would not ordinarily be considered backfitting even if prior versions of this regulatory guide are part of the licensing basis of the facility. However, unless this regulatory guide is part of the licensing basis for a facility, the staff may not represent to the licensee that the licensees failure to comply with the positions in this regulatory guide constitutes a violation.

If an existing licensee voluntarily seeks a license amendment or change and (1) the NRC staffs consideration of the request involves a regulatory issue directly relevant to this new or revised regulatory guide and (2) the specific subject matter of this regulatory guide is an essential consideration in the staffs determination of the acceptability of the licensees request, then the staff may request that the licensee either follow the guidance in this regulatory guide or provide an equivalent alternative process that demonstrates compliance with the underlying NRC regulatory requirements. This is not considered backfitting as defined in 10 CFR 50.109(a)(1) or a violation of any of the issue finality provisions in 10 CFR Part 52.

The NRC staff does not intend or approve any imposition or backfitting of the guidance in this regulatory guide. The NRC staff does not expect any existing licensee to use or commit to using the guidance in this regulatory guide, unless the licensee makes a change to its licensing basis. The NRC staff does not expect or plan to request licensees to voluntarily adopt this regulatory guide to resolve a generic regulatory issue. The NRC staff does not expect or plan to initiate NRC regulatory action which would require the use of this regulatory guide. Examples of such unplanned NRC regulatory actions include issuance of an order requiring the use of the regulatory guide, requests for information under 10 CFR 50.54(f) as to whether a licensee intends to commit to use of this regulatory guide, generic communication, or promulgation of a rule requiring the use of this regulatory guide without further backfit consideration.

Additionally, an existing applicant may be required to adhere to new rules, orders, or guidance if 10 CFR 50.109(a)(3) applies.

DG-1209, Page 11 REFERENCES4

1.

Code of Federal Regulations (CFR), Title 10, Energy, Part 50, Domestic Licensing of Production and Utilization Facilities.

2.

Institute of Electrical and Electronic Engineers (IEEE), Std. 603-1991, IEEE Standard Criteria for Safety Systems for Nuclear Power Generating Stations, IEEE, Piscataway, NJ, 1991 (including a correction sheet dated January 30, 1995).5

3.

IEEE Std. 279-1971, Criteria for Protection Systems for Nuclear Power Generating Stations, IEEE, Piscataway, NJ, 1971.

4.

IEEE Std. 830-1998, IEEE Recommended Practice for Software Requirements Specifications, IEEE, Piscataway, NJ, 1998.

5.

U.S. Nuclear Regulatory Commission (NRC), NUREG-0800, Standard Review Plan for the Review of Safety Analysis Reports for Nuclear Power Plants: LWR Edition, Chapter 7, Instrumentation and Controls, NRC, Washington, DC, March 2007.

6.

CFR, Title 10, Energy, Part 52, Licenses, Certifications, and Approvals for Nuclear Power Plants, NRC, Washington, DC.

7.

NRC, Regulatory Guide 1.170, Software Test Documentation for Digital Computer Software Used in Safety Systems of Nuclear Power Plants, U.S. Nuclear Regulatory Commission, Washington, DC.

8.

CFR, Title 10, Energy, Part 73, Section 54, Protection of Digital Computer and Communication Systems and Networks.

9.

IEEE Std. 7-4.3.2, IEEE Standard Criteria for Digital Computers in Safety Systems of Nuclear Power Generating Stations, IEEE, Piscataway, NJ, 2003.

10.

NRC, Regulatory Guide 1.152, Criteria for Use of Computers in Safety Systems of Nuclear Power Plants, NRC, Washington, DC.

11.

IEEE Std. 1012-2004, IEEE Standard for Software Verification and Validation, IEEE, Piscataway, NJ, 2004.

12.

NRC, Regulatory Guide 1.168, Verification, Validation, Reviews, and Audits for Digital Computer Software Used in Safety Systems of Nuclear Power Plants, NRC, Washington, DC.

4 Publicly available NRC published documents are available electronically through the Electronic Reading Room on the NRCs public Web site at http://www.nrc.gov/reading-rm/doc-collections/. The documents can also be viewed online or printed for a fee in the NRCs Public Document Room (PDR) at 11555 Rockville Pike, Rockville, MD; the mailing address is USNRC PDR, Washington, DC 20555; telephone 301-415-4737 or 800-397-4209; fax 301-415-3548; and e-mail pdr.resource@nrc.gov.

5 Copies of IEEE documents may be purchased from the Institute of Electrical and Electronics Engineers Service Center, 445 Hoes Lane, P.O. Box 1331, Piscataway, NJ 08855 or through the IEEEs public Web site at http://www.ieee.org/publications_standards/index.html.

DG-1209, Page 12

13.

IEEE Std. 1074-2006, IEEE Standard for Developing a Software Life Cycle Process, IEEE, Piscataway, NJ, 2006.

14.

NRC, Regulatory Guide 1.173, Developing Software Life Cycle Processes for Digital Computer Software Used in Safety Systems of Nuclear Power Plants, NRC, Washington, DC.

15.

NRC, NUREG/CR-6101, Software Reliability and Safety in Nuclear Reactor Protection Systems, U.S. Nuclear Regulatory Commission, Washington, DC, November 1993.

(ADAMS Accession No. ML072750055)

16.

NRC, NUREG/CR-6263, High Integrity Software for Nuclear Power Plants: Candidate Guidelines, Technical Basis, and Research Needs, U.S. Nuclear Regulatory Commission, Washington, DC, June 1995. (ADAMS Accession No. ML063470590, ML063470593, and ML063600344)

17.

NRC, Regulatory Guide 1.169, Configuration Management Plans for Digital Computer Software Used in Safety Systems of Nuclear Power Plants, NRC, Washington, DC.

18.

NRC, Regulatory Guide 1.171, Software Unit Testing for Digital Computer Software Used in Safety Systems of Nuclear Power Plants, NRC, Washington, DC.

19.

IEEE Std. 610.12-1990, IEEE Standard Glossary of Software Engineering Terminology, IEEE, Piscataway, NJ, 1990.

20.

IEEE Std. 828-2005, IEEE Standard for Software Configuration Management Plans, IEEE, Piscataway, NJ, 2005.

21.

Institute of Electrical and Electronics Engineers and Electronic Industries Association (IEEE/EIA) Std. 12207.1-1997, Industry Implementation of International Standard ISO/IEC 12207: 1995. (ISO/IEC 12207) Standard for Information Technology-Software Life Cycle Processes-Life Cycle Data, IEEE, Piscataway, NJ, and EIA, Engineering Department, April 1998.6 6

Copies of International Organization for Standardization (ISO) documents may be obtained by writing to the International Organization for Standardization, 1, ch. de la Voie-Creuse, CP 56, CH-1211 Geneva 20, Switzerland, Telephone: +41 22 749 01 11, Fax: +41 22 749 09 47, by E-mail at sales@iso.org, or on-line at the ISO Store Web site: http://www.iso.org/iso/store.htm.