ULTRASONIC THICKNESS EXAMINATION RECORD ISI ID:

Y C,'

NDE Lab Station Unit Outage Order Procedure #

Rev.

Couplant Exam Date,.

Type Batch MISTRAS Salem 1

RFO# 20 60084266 IOU-AA-335-004 1

SONOTRACE 40 96243 4/20/2010 EXAMINATION AREA MATERIAL Component I.D.

System Location Fab. Isometric Elev.

(Type/Spec)

Dia. Size Component Type Surface Temp.

Aux Fd Water Bounding AF Yard N/A 100' P-1 4"

Pi e AMBIENT SEARCH UNIT DESCRIPTION EQUIPMENT WALL THICKNESS Size X

Y Brand Serial #

Size Frequency Instr. Brand/type Serial #

Nominal

.875 Nom.

T min.

1" 6

Panametric 636328 0.312 5mhz PANAMETRICS 071474104 0.337 0,295 0.278 D 790RL 37 DL I PLUS

'alibration Block # I S/N Calibration Block Temp.

AMBIENT Actual Effective Initial Final 0.250 0.250 0.250 0.250 CALIBRATION TIME 0.500 0.500 0.500 0.500 Initial Calibration 9:00 AM 0.750 0.750 0.750 0.750 Calibration Check N/A-1.000 1.000 1.000 1.000 Final Calibration Check 9:30 AM calibration Block # 2 S/N Calibration Block Temp..

Actual Effective Initial Final Thermometer Serial #

Cal. Due 217591 01113/11 Min.

Max.

LIMITATIONS: None File Name Thickness Thickness 0.077 is A4 reading.

Aux. Feed 0.077 @ A4 0.319 (

L2 COMMENTS: Readings taken in 1" grid pattern.

BoundingI Notified:

Technician: P. Mendonca Date: 04/20110 Cert. Exp.

3/6/11 SNT-TC-IA LEVEL II Eye Test Exp. 4/1/11 B. Montgomery Attachment AZ'x Yes No PSE&G Review: Adam Burke Date: 04/20/10 SNT-TC-1A LEVEL II Page 1 of 2

Unit:

Salem 1 RFO 20 Date:

04120/10 T-MIN= 0.278 87.5% Nom. Wall= 0.295 Nom. Wall = 0.337 iSI ID. Aux. Fd Bounding Component ID.

Aux. Feed Bounding Lowest Reading 0.077 Highest reading 0.319 Color Code:

0.000 to T-MIN

>87.5% Nom. Wall to Nom. Wall

>Nom. Wall 1

2 3

4 5

6 7

A 0.251 0.272 0.163 0.191 0.279 0.276 B

0.270 0.305 0.259 0.242 0.271 0:267 0.261 C

D E

0.318 0.242 0.279 0.255 0.253 0.258 0.258 0.245 0.257 0.255 0.243 0.141 0.250 0.287 0.244 0.247 0.279 0.256 0.256 0.256 0.256 F

0.272 0.283 0.277 0.258 0.274 0.284 0.278 G

0.293 0.277 0.168 0.281 0.303 0.305 0.302 H

0.278 0.256 0.258 0.301 0.296 0.295 0.300 I

J 0.261 0.255 0.245 0.267 0.243 0.254 0.272 0.269 0.269 0.265 0.274 0.264 0.274 0.268 K

0.250 0.256 0.227 0.233 0.229 0.234 0.239 L

M N

0.274 0.288 0.296 0.258 0.260 0.298 0.287 0.267 0.285 0.290 0.292 0.285 0.297 0.257 0.287 0.298 0.258 0.283 0.316 0.252