Fm 5.2 Exhibit 1 Petrographic Studies of Concrete for Construction Engineering Consultants
ML102870199
Person / Time
Site: Crystal River 
Issue date: 09/20/2010
From: Erlin B
Erlin, Hime Associates
To:
Office of Information Services
References
FOIA/PA-2010-0116
Download: ML102870199 (3)


Text

-FM 5.2 Exhibit 1 ATT.ACIIMENV "C

2 ERLIN, HIME ASSOCIATES MATERIALS AND CONCRETE CONSULTANTS

  • i'eKIC "dOULEVARD 43121 272.7730 ILLINOIS 60062 PETROGRAPHIC STUDIES OF CONCRETE FOR CONSTRUCTION ENGINEERING CONSULTANTS

.5 5

SUMMARY

AND DISCUSSION

  • The specimen represented air-entrained concrete.

made with crushed fossiliferous coarse aggre-gate and&siliceoius fine aggregate and a low water-cement. ratio paste.

There was no evidence that the aggregates had. been either chemically or physically unsound.

The specimen was from an area where fractures had existed for a period of time and where moisture had been present.

That was demon-strated by secondary deposits on fracture surfaces.

The specimen was relatively small.

Larger specimens fr.om different areas of the struc-ture would be desirable for examination in order to obtain a better representation of the concrete.

INTRODUCTION Reported herein are the results of petrographic studies of a concrete fragment submitted by J.

Artuso of Con-strud'tion Engineering Consultants.

The specimen is from the dome of the containment structure of the Florida Power Corporation,Crystal River, Unit.III.

.,Requested by Mr. Artuso were petrographic studies for evaluating the specimen, and particularly for evidence of features, that would cause volume instability.

C-12

FM 3.1 Exhibit 1 ERLIN, HIME ASSOCIATES MAkTERIALS AN0 CONCRETE CONSULTANTS STUDIES-Specimen -

The specimen was an elongated fragment having nominal lateral dimensions of 5 inches, and a maximum thickness of about 3/4 inch.

All surfaces were fracture surfices. except for a shallow channel about 3/32 inch wide and 1/8 inch deep.

The channel appears to be the terminal area of a saw cut.

Petrographic Studies - Coarse aggregate of the specimen was a buff to light brown, fine-grained, fossiliferous limestone having a maximum nominal size of 3/4 inch.

The fine aggregate was a siliceous sand composed prin-cipally of quartz.

The aggregates were not partichiarly well graded, as evidenced by deficiencies of the finer sizes of the coarseaggregate and the coarser sizes of the fine aggregate.

There was no evidence that the aggregates had been chemically or physically unsound.

Particular attention was directed to alkali-silica reactivity with respect to the coarse aggregate because a similar type of aggregate does contain a highly reactive variety of chert.

Neither the chert nor the product of the reaction of the chert with alkalies (alkali7-silica gel) was present..

Paste of the specimen was medium dark grey, firm, and contained abundant residual and relict cement. The quality of the paste reflects a low wate+/--cement ratio.

Air occurred as small, discrete, spherical voids that bccasionally were very slightly distorted, and as coarser irregularly shaped voids.

The spherical voids are characteristic of entrained air voids; the irregularly shaped voids.,. of entrapped air.

The air content of the specimen is estimated to be 52 percent and the parameters of the'air-void system are judged to be effective for protecting critically saturated concrete exposed to cyclic freezing.

On one of the lateral surfaces were secondary deposits composed of tufts of fine acicularett~ringitfj (3CaO6 A120 3 "3CaSO4 '31H 20), and calcite ( 6aCO3 ). [Ett4giti was also present as tufts in some air void,'just below the fracture surface.

The fragment was not uniformly thick; it tapered to a knife-like edge.

Along that edge, were fine fractures c-13

t.

FM 3.1 Exhibit 1 ERLIN, HIME ASSOCIATES MATERIALS AND CONCRETE CONSULTANTS oriented subparallel to the long axis of the fragment.

The fractures transected coarse aggregate particles.

On.

those fracture s-urfaces were secondary deposits similar to those described above.

The secondary compounds demonstrate that the fragment was from an area where fractures present for.a period of time had been exposed to moisture.

May 10, 1976 Erlin, Hime Associates, Inc.

by Bernard Erlin, President Petrographer

.C-1 C-"