1 WBN2Public Resource From:
Crouch, William D [wdcrouch@tva.gov]
Sent:
Wednesday, July 28, 2010 5:09 PM To:
Lamb, John; Wiebe, Joel; Poole, Justin; Milano, Patrick Cc:
Arent, Gordon; Thompson, Jeffery S; Freeman, Edwin E; Pointer, Kenneth; Stephenson, Catherine L
Subject:
RE: For Your Action - Watts Bar Unit 2 - GL 1995-07 Inresponsetoyouremail(below)datedJuly8,2010,thebelowresponseisprovided.Ifyouhaveanyquestions,please givemeacall.Ifyouneedthesesubmittedformally,pleaseletmeknow.
William D. (Bill) Crouch (423)3652004WBN (256)7777676Cell
Question:Regarding Watts Bar Unit 2 response to GL 1995-07 for pressure locking/thermal binding, please:
- 1) Listthevalvesthatrequiremodifications:
Answer:The9507reviewofWBNUnit2GL8910motoroperatedvalveshasbeencompletedwiththefollowing conclusions.
Eleven valves identified for Disk Modification
- 1. 2-FCV-1-16
- 2. 2-FCV-63-8
- 3. 2-FCV-63-11
- 4. 2-FCV-63-156
- 5. 2-FCV-63-157
- 6. 2-FCV-74-1
- 7. 2-FCV-74-2
- 8. 2-FCV-74-8
- 9. 2-FCV-74-9
- 10. 2-FCV-74-33
- 11. 2-FCV-74-35 Seven valves identified for Valve Bonnet Modification
- 1. 2-FCV-63-72
- 2. 2-FCV-63-73
- 3. 2-FCV-63-172
- 4. 2-FCV-72-40
- 5. 2-FCV-72-41
- 6. 2-FCV-72-44
- 7. 2-FCV-72-45 Additionally,controlsforvalves2FCV722and39willbemodifiedtoaddatimedelaywhichwilleliminatethe potentialforpressurelocking,asisdonewithUnit1valves1FCV722and39.Notethisisacontrolsmodandnota valvemodification.
- 2) Listthevalvesthataremissing:
Answer:TherearenomissingGenericLetter9507valves.The20valvesidentifiedabovearecurrentlyinstalledinWBN Unit2.
2
- 3) HastherebeenanyplantmodificationsthathavechangedtheoriginalassessmentforWattsBarUnit1andthe impactonWattsBarUnit2?
Answer:Inadditiontothetimedelaychangesmentionedabove,thereare2otherUnit1valves1FCV6325and26, whicharebeingevaluatedforGL9507impactstoaddressnewinputparametersfromtheJOGTopicalReportMPR 2524A.Unit1hasinitiatedadesignchangetoaddressJOGpressurelockingandMOVrequirements.Thesechangeswill beevaluatedforimpacttotheequivalentUnit2valves2FCV6325and26.
From: Lamb, John [1]
Sent: Thursday, July 08, 2010 11:08 AM To: Crouch, William D; Arent, Gordon Cc: WBN2HearingFile Resource; Wiebe, Joel; Raghavan, Rags; Milano, Patrick; Haag, Robert; Campbell, Stephen
Subject:
For Your Action - Watts Bar Unit 2 - GL 1995-07 Importance: High
Bill & Gordon, Regarding Watts Bar Unit 2 response to GL 1995-07 for pressure locking/thermal binding, please
- 1. list the valves that require modifications,
- 2. list the valves that are missing, and
- 3. has there been any plant modifications that have changed the original assessment for Watts Bar Unit 1 and the impact on Watts Bar Unit 2?
Thanks.
John
Hearing Identifier:
Watts_Bar_2_Operating_LA_Public Email Number:
63 Mail Envelope Properties (B75BE6D61CDE4A468D264343045CAC4F062D4BE4)
Subject:
RE: For Your Action - Watts Bar Unit 2 - GL 1995-07 Sent Date:
7/28/2010 5:09:00 PM Received Date:
7/28/2010 5:09:19 PM From:
Crouch, William D Created By:
wdcrouch@tva.gov Recipients:
"Arent, Gordon" <garent@tva.gov>
Tracking Status: None "Thompson, Jeffery S" <jsthompson@tva.gov>
Tracking Status: None "Freeman, Edwin E" <eefreeman@tva.gov>
Tracking Status: None "Pointer, Kenneth" <kpointer@tva.gov>
Tracking Status: None "Stephenson, Catherine L" <clstephenson@tva.gov>
Tracking Status: None "Lamb, John" <John.Lamb@nrc.gov>
Tracking Status: None "Wiebe, Joel" <Joel.Wiebe@nrc.gov>
Tracking Status: None "Poole, Justin" <Justin.Poole@nrc.gov>
Tracking Status: None "Milano, Patrick" <Patrick.Milano@nrc.gov>
Tracking Status: None Post Office:
TVANUCXVS2.main.tva.gov Files Size Date & Time MESSAGE 2866 7/28/2010 5:09:19 PM Options Priority:
Standard Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
Recipients Received: