RAI to S.K. Gambhir Request for Additional Information for the Review of the Columbia Generating Station License Renewal Application
ML102230369
Person / Time
Site: Columbia 
Issue date: 08/16/2010
From: Gettys E
License Renewal Projects Branch 1
To: Gambhir S
Energy Northwest
Gettys E, NRR/DLR, 415-4029
References
Download: ML102230369 (6)


Text

'<:.p..fI REGU V\\.

(</

~..::;

.1'0 UNITED STATES

,JJ,

/$1,.<.

I-C'l NUCLEAR REGULATORY COMMISSION

<t 0

~

/. ;s:

WASHINGTON, D.C. 20555-0001 o

I))

,(

'?

~

'</~

i, O.e:-

August 16,2010 I")

~

        • it Mr. S.K. Gambhir Vice President Technical Services Columbia Generating Station Energy Northwest MD PE04 P.O. Box 968 Richland, WA 99352-0968

SUBJECT:

REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW OF THE COLUMBIA GENERATING STATION LICENSE RENEWAL APPLICATION

Dear Mr. Gambhir:

By letter dated January 19, 2010, Energy Northwest submitted an application pursuant to Title 10 of the Code of Federal Regulations Part 54 (10 CFR Part 54), to renew operating license NPF-21 for Columbia Generating Station, for review by the U.S. Nuclear Regulatory Commission (NRC or the staff). The staff is reviewing the information contained in the license renewal application and has identified, in the enclosure, areas where additional information is needed to complete the review. Further requests for additional information may be issued in the future.

Items in the enclosure were discussed with Abbas Mostala and a mutually agreeable date for the response is within 30 days from the date of this letter. If you have any questions, please contact me at 301-415-4029 or bye-mail at evelyn.gettys@nrc.gov.

Sincerely, f~b~8 Evelyn Gettys, Project Manager Projects Branch 1 Division of License Renewal Office of Nuclear Reactor Regulation Docket No. 50-397

Enclosure:

As stated cc w/encl: Distribution via Listserv

COLUMBIA GENERATING STATION LICENSE RENEWAL APPLICATION REQUEST FOR ADDITIONAL INFORMATION RAI B.2.28-2

Background:

The Generic Aging Lessons Learned (GALL) Report X1. M17 establishes that for monitoring and trending of piping systems susceptible to flow-accelerated corrosion (FAC), a predictive code should be used to predict component degradation. In license renewal application (LRA)

Section 8.2.28, the applicant states that an enhancement to the FAC Program includes adding gray cast iron as a material identified as susceptible to FAC. The applicant further states that the guidance and recommendations of Electric Power Research Institute (EPRI) NSAC*202L will be utilized to ensure that the integrity of piping systems susceptible to FAC is maintained.

EPRI NSAC-202L, Rev 3, recommends using CHECWORKS as a tool to predict and monitor the wear rate in piping systems susceptible to FAC but it is modeled for carbon and low alloy steel piping.

Issue:

The LRA does not contain information regarding the method that will be used to monitor or inspect the gray cast iron components for FAC.

Reguest:

Please discuss how monitoring and inspection of gray cast iron susceptible to FAC will be performed to ensure that structural integrity will be maintained.

RAI3.6-1

Background:

Standard Review Plan (SRP) Table 3.6.1, Item Number 3.6.1-9, credits the GALL Report aging management program (AMP) XI.S6, Structures Monitoring Program to manage the aging effect/mechanism loss of material due to general corrosion for metal-enclosed bus enclosure assemblies.

ENCLOSURE

- 2 Issue:

In LRA Table 3.6.2-1, the applicant references Item 3.6.1-9 and generic note A, and credits the Structures Monitoring Program to manage aging for metal-enclosed bus enclosure assemblies.

However, the discussion of the Structures Monitoring Program in Appendix B of the LRA does not indicate that the metal-enclosed bus enclosure assemblies are within the scope of the Structures Monitoring Program.

Request:

Confirm that the scope of Structures Monitoring Program includes the metal-enclosed bus enclosure assemblies, and revise the scope of Structure Monitoring Program as appropriate.

RAI3.6*2

Background:

In LRA Table 3.6.2-1, under component/commodity group, "Uninsulated Ground Conductors and Connections," the applicant indicated that there are no aging effects requiring management for the metallic components of uninsulated ground conductors and connections.

Issue:

The LRA did not provide technical justification of how uninsulated ground conductors and connections are not subject to aging degradation such as loss of material due to general corrosion in soil environment.

Request:

Provide a detail technical justification as to why uninsulated ground conductors are not subject to any aging degradation.

RAI3.6-3

Background:

GALL Report, Vol. 2, Rev. 1, Item VI.A-8, "Fuse Holders (Not Part of a Larger Assembly; Metallic Clamp)," identifies the aging effect and aging mechanism as fatigue, ohmic heating, thermal cycling, electrical transients, frequent manipulation, vibration, chemical contamination, corrosion and oxidation. The associated AMP XI.E5, "Fuse Holders," states that fuse holders within the scope of license renewal should be tested to provide an indication of the condition of the metallic clamps of fuse holders. In Table 3.6.1, under Item 3.6.1-06 of the LRA, the applicant indicates that the aging effects detailed in NUREG-1801 are not applicable for this item.

- 3 Issue:

In LRA Appendix B, Table B-1, the applicant stated that Fuse Holder Program is not credited for license renewal. Table 3.6.2-1, under Fuse Holder Metallic Clamp component type, also states that these aging effects are not applicable at Columbia Generating Station. The applicant does not provide a detailed evaluation for each aging effect identified in GALL Report and AMP XI.E5.

Request:

Provide a detailed evaluation that addresses the aging effecVmechanisms identified in GALL Report, Vol. 2, Revision 1, and Item VI.A-8 that supports the conclusions made in LRA Table 3.6.1, Item 3.6.1-06.

. ML102230369 OFFICE LA:DLR PM:RPB1:DLR BC: RPB1:DLR PM:RPB1 :DLR NAME IKing EGettys BPham EGettys DATE 08/11/10 08/12110 08/16/10 08/16/10

Letter to S.K. Gambhir from Evelyn Gettys dated August 16, 2010

SUBJECT:

REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW OF THE COLUMBIA GENERATING STATION LICENSE RENEWAL APPLICATION DISTRIBUTION:

HARDCOPY:

DLRRF E-MAIL:

PUBLIC RidsNrrDlr Resource RidsNrrDlrRpb1 Resource RidsNrrDlrRpb2 Resource RidsNrrDlrRarb Resource RidsNrrDlrRapb Resource RidsNrrDlrRasb Resource RidsNrrDlrRerb Resource RidsNrrDlrRpob Resource EGettys DDoyle FLyon WWalker, RIV RCohen, RIV LSubin,OGC