ML102070347

From kanterella
Jump to navigation Jump to search
Email from Chou, Rich to Franke, Mark; Cc Sykes, Marvin; Ninh, Son; Khanna, Meena; Morriessey, Thomas; Reyes, Rogerio; Lake, Louis; Chou, Rich; FW: Crystal River Containment Wall Opening Core Boring Pictures
ML102070347
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 11/05/2009
From: Chou R
NRC/RGN-II
To: Mark Franke
NRC/RGN-II
References
FOIA/PA-2010-0116
Download: ML102070347 (2)


Text

Sykes, Marvin From:

Chou, Rich PI-Sent:

Thursday, November 05, 2009 1:46 PM To:

Franke, Mark Cc:

Sykes, Marvin; Ninh, Son; Khanna, Meena; Morrissey, Thomas; Reyes, Rogerio; Lake, Louis; Chou, Rich

Subject:

FW: Crystal River Containment Wall Opening Core Boring Pictures Attachments:

100_0428.jpg; 100 0429.jpg; 100_0430.jpg; 100 0431.jpg; 100 0432.jpg-.

Mark:

Pictures from left to right:

1. Top hole at right opening wall 2. Bottom hole at the right opening wall 3. Top hole at the left opening wall 4. Bottom hole at the left opening wall 5. No. 5 hole perpendicular to the wall at the left side During the observation of Steam Generators OSG-A and OSG-B moved out, I noticed that there were 5-2" diameter holes drilled for core boring. Two holes were on each side of opening at 2 ft. from the bottom of the opening for the first hole and secon hole was about 18 inches above the first hole.

Theose four holes were drilled parallel to hoop tendons and were about 14 inches from the liner plate in the good concrete, no cracked area from each side of the cut area. Those 4 holes were about 14 inches deep. The no. 5 hole was about 2 ft. from the left edge of the opening and 2 ft from the bottom of the opening and was drilled perpendicular to the wall.

This hole was about 10 to 12 inches deep and drilled to the cacked or delamination line. The outside face of the delamination was removed by the sample. The inside face of the delamination is still intact.

Based on my observation of the 4 holes parallel to the hoop tendons, the cut area was fresh, same texture, uniform grey color, and fine particle.

The No. 5 hole can be seen to have rough surface, fine bubble, different colors with some dark color, aged color, and total different texture from the other 4 holes. There is evidence that the delamination was not created recently by the hydraulic demolition or unbalanced tendon stress due to some tendon stresses nearby were not released. The delamination was existed since the construction, due to the incomplete curing, and applied tension forces too early.

There is also strongly to suggest that inadequate design without the radial rebars.

The containment wall delamination should be discovered during the extent of condition of the containment dome delamination. They were related since the original construction.

From: Reyes, Rogerio Sent: Thursday, November 05, 2009 12:38 PM To: Chou, Rich

Subject:

Your pictures J. Rogerio Reyes, P.E.

U.S. Nuclear Regulatory Commission Resident Inspector Crystal River Nuclear Power Plant