SEntergy Entergy Nuclear Operations, Inc.
Pilgrim Nuclear Power Station 600 Rocky Hill Road Plymouth, MA 02360 Stephen J. Bethay Director, Nuclear Safety Assurance July 13, 2010 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555-0001
SUBJECT:
Entergy Nuclear Operations, Inc.
Pilgrim Nuclear Power Station Docket No. 50-293 License No. DPR-35
REFERENCE:
LETTER NUMBER:
Dear Sir or Madam,
Entergy Response to NRC Request for Additional Information Related to Pilgrim Relief Request (PRR)-20, Alternative Examination Requirements for Pilgrim Nozzle-to-Vessel Shell and Inner Radii Welds Using ASME Code Case N-702 and BWRVIP-108 (TAC NO. ME3290)
- 1.
Entergy Letter No. 2.10.004, Entergy Pilgrim Relief Request (PRR)-20, Alternative Examination Requirements for Pilgrim Nozzle-to-Vessel Shell and Inner Radii Welds Using ASME Code Case N-702 and BWRVIP-108dated February 1, 2010 2.10Q035,'
This letter dockets Entergy's response to an NRC Request for Additional Information (RAI) forwarded to Pilgrim's Licensing Staff by E-mail on May 19, 2010.
The Entergy response supports the Pilgrim Relief Request (PRR)-20, Alternative Examination Requirements for Pilgrim Nc~z~z e-to-Vessel Shell Welds and Nozzle Inner Radii using the requirements of American Society of Mechanical Engineers (ASME) Code Case N-702 and BWRVI P-108 provisions.
- i.
- ". :.i I. ' -
- o',.:. :'
.,J Vo 9
-Aew?
Entergy Nuclear Operations, Inc.
Pilgrim Nuclear Power Station Letter Number: 2.10.035 Page 2 The proposed alternative along with the attached prior examination's results provide an acceptable level of quality and safety because it follows the requirements of ASME Code N-702 and the NRC approved technical basis (BWRVIP -108) for the alternative examination described in Pilgrim Relief Request (PRR)-20 submitted as Reference 1.
There are no commitments made in this submittal.
If you have any questions, please call Mr. Joseph Lynch, Pilgrim Licensing Manager at 508-830-8403.
Sincerely, Ste eJ.ethay Director, Nuclear Safety ssurance SJB/wgl
Attachment:
Entergy Response to NRC Request for Additional Information Related to Pilgrim Relief Request PRR-20 (2 pages) cc:
Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Senior Resident Inspector Pilgrim Nuclear Power Station Mr. James S. Kim, Project Manager Plant Licensing Branch I-1 Division of Operator Reactor Licensing Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission One White Flint North 0-8C2 11555 Rockville Pike Rockville, MD 20852
Attachment to Entergy Letter Number 2.10.035 ENTERGY RESPONSE TO NRC REQUEST FOR ADDITIONAL INFORMATION RELATED TO PILGRIM RELIEF REQUEST PRR-20 (2 pages)
ENTERGY RESPONSE TO NRC REQUEST FOR ADDITIONAL INFORMATION REGARDING PILGRIM RELIEF REQUEST PRR-20
Reference:
Pilgrim PRR-20: Alternative Examination Requirements for Nozzle-to-Shell and Inner Radii Welds Using ASME Code Case N-702 and BWRVIP-108 (TAC NO. ME3290)
Dated, May 19, 2010 (By E-mail)
NRC Request:
Please provide a synopsis of what inspections have already been performed on the components for which this alternative is requested, including all indications that were found and how these indications were dispositioned.
Enterg¥/Pilqrim Response:
The following Table provides inspections that were performed on the RPV welds during refueling outages and the indications found during inspections.
('nmnnnant in1 DImr~ri ntinn Vi~rQ nf InQn~tinn It ITI Inrliratinn*
Yaars of Insnection ["In RPV-NI A-NV RPV-N1 A-NIR RPV-N1 B-NV RPV-N1 B-NIR RPV-N3A -NV RPV-N3A-NIR RPV-N3B-NV RPV-N3B-NIR RPV-N3C-NV RPV-N3C-NIR RPV-N3D-NV RPV-N3D-NIR RPVN6A-NV RPV-N6A-NIR 28" Recirc Outlet Nozzle to Vessel Weld 28" Recirc Outlet Nozzle to Inner Radius 28" Recirc Outlet Nozzle to Vessel Weld 28" Recirc Outlet Nozzle to Inner Radius 20" Main Steam Nozzle to Vessel Weld 20" Main Steam Nozzle to Inner Radius 20" Main Steam Nozzle to Vessel Weld 20" Main Steam Nozzle to Inner Radius 20" Main Steam Nozzle to Vessel Weld 20" Main Steam Nozzle to Inner Radius 20" Main Steam Nozzle to Vessel Weld 20" Main Steam Nozzle to Inner Radius 12" Core Spray Nozzle to Vessel Weld 12" Core Spray Nozzle to Inner Radius 1977,1983,1999,2009 1977,1983,1999,2009 1980,1995,2005 1980,1995,2005 1974,1983,1997,2007 1974,1983,1997,2007 1981,1987,1997,2007 1987,1997, 2007 1981,1987,1997,2007 1987,1997,2007 1974,1987,1997,2007 1974,1987,1997,2007 1981,1983,1987,1997,2007 1983,1987,1997,2007 NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI Page 1 of 2
ENTERGY RESPONSE TO NRC REQUEST FOR ADDITIONAL INFORMATION REGARDING PILGRIM RELIEF REQUEST PRR-20 RPV-N6B-NV RPV-N6B-NIR RPV-N7A-NV RPV-N7A-NIR RPV-N7B-NV RPV-N7B-NIR RPV-N8-NV RPV-N8-NIR RPV-N9A-NV RPV-N9A-NIR RPV-N9B-NV RPV-N9B-NIR OUTAGE 12" Core Spray Nozzle to Vessel Weld 12" Core Spray Nozzle to Inner Radius 9" Spare Instrumentation Nozzle to Vessel Weld 9" Spare Instrumentation Nozzle to Inner Radius 9" Spare Instrumentation Nozzle to Vessel Weld 9" Spare Instrumentation Nozzle to Inner Radius 6" Head Vent Nozzle to Vessel Weld 6" Head Vent Nozzle to Inner Radius 5" Jet Pump Instrumentation Nozzle to Vessel Weld 5" Jet Pump Instrumentation Nozzle to Inner Radius 5',' Jet Pump Instrumentation Nozzle to Vessel Weld 5" Jet Pump Instrumentation Nozzle to Inner Radius 1974,1991,2001 1974,1991, 2001 1974, 1995,2005 1974,1995, 2005 1974,1995,2005 1974,1995,2005 NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI 1993,2005 1993,2005 1987,1999,2009 1987,1999,2009 1974,1993,2003 1974,1993,2003 YEAR RFO #1 1974 RFO #2 1976 RFO #3 1977 RFO #4 1980 RFO #5 1981 RFO #6 1983 RFO #7 1987 RFO #8 1991 RFO #9 1993 RFO #10 1995 RFO #11 1997 RFO #12 1999 RFO #13 2001 RFO #14 2003 RFO #15 2005 RFO #16 2007 RFO #17 2009 NRI = NO RECORDABLE INDICATIONS Page 2 of 2