Attachment to E-mail Transmitting Draft RAI from Csgb MUR LAR (TAC Nos. ME3015 and ME3016.)
ML100630505
Person / Time
Site: Prairie Island  Xcel Energy icon.png
Issue date: 03/05/2010
From:
NRC/NRR/DCI
To:
Xcel Energy
beltz T, NRR/DORL/LPL3-1, 301-415-3049
Shared Package
ML100630504 List:
References
TAC ME3015, TAC ME3016
Download: ML100630505 (1)


Text

ADAMS Accession No.: ML100630505 REQUEST FOR ADDITIONAL INFORMATION Prairie Island Nuclear Generating Plant, Units 1 and 2 License Amendment Request dated December 28, 2009 for Measurement Uncertainty Recapture Power Uprate (MUR-PU)

Docket Nos. 50-282 and 50-306 TAC Nos. ME3015 and ME3016 Office of Nuclear Reactor Regulation Division of Component Integrity Steam Generator Tube Integrity and Chemical Engineering Branch Protective coating systems provide a means for protecting the surfaces of facilities and equipment from corrosion and radionuclide contamination. Additionally, coatings used inside containment should be suitable and stable under design-basis loss-of-coolant accident conditions. It is unclear to the staff whether the protective coatings used inside containment were evaluated under power uprate conditions.

1. Please discuss whether the protective coating systems used in the containment remain qualified under MUR-PU conditions. Specifically, please discuss whether the temperature, pressure, and irradiation of the coatings during the qualification testing bounds the anticipated MUR-PU conditions.