Letter Sequence Response to RAI |
---|
|
|
MONTHYEARNOC-AE-08002366, License Amendment Request for Deviation from Fire Protection Program Requirements2009-02-0303 February 2009 License Amendment Request for Deviation from Fire Protection Program Requirements Project stage: Request ML0908907692009-03-30030 March 2009 Acceptance Review Email, License Amendment Request, Revise Facility Operating Licenses, Deviation from Fire Protection Program Requirements for Fire Area 27 Project stage: Acceptance Review ML0915507632009-06-0404 June 2009 Acceptance Review Email, License Amendment Request to Revise Operating Licenses, Deviation from Fire Protection Program Requirements Project stage: Acceptance Review ML0926403712009-09-0404 September 2009 Email Request for Additional Information, License Amendment Request, Deviation from Fire Protection Program Requirements for Fire Area 27 (TAC ME0824 and ME0825) and Fire Area 31 Project stage: RAI ML0933505372009-11-20020 November 2009 Project, Units 1 & 2, Response to Request for Additional Information Regarding License Amendment Requests for Deviation from Fire Protection Program Requirements Project stage: Response to RAI NOC-AE-09002489, Response to Request for Additional Information Regarding License Amendment Requests for Deviation from Fire Protection Program Requirements2009-11-20020 November 2009 Response to Request for Additional Information Regarding License Amendment Requests for Deviation from Fire Protection Program Requirements Project stage: Response to RAI ML1002801712010-01-20020 January 2010 Response to Request for Additional Information Regarding Proposed Amendments for Deviation from Fire Protection Program Requirements Project stage: Response to RAI NOC-AE-10002513, Supplement 1 to Response to Request for Additional Information Regarding License Amendment Requests for Deviation from Fire Protection Program Requirements2010-02-0101 February 2010 Supplement 1 to Response to Request for Additional Information Regarding License Amendment Requests for Deviation from Fire Protection Program Requirements Project stage: Supplement ML1007800752010-03-31031 March 2010 Issuance of Amendment Nos. 193 and 181, Revise License Condition E, Deviation from Fire Protection Program Requirements for Fire Areas 27 and 31 Project stage: Approval 2009-06-04
[Table View] |
|
---|
Category:Letter
MONTHYEARML24304B0512024-10-30030 October 2024 Cycle 26 Core Operating Limits Report IR 05000498/20244022024-10-23023 October 2024 Security Baseline Inspection Report 05000498/2024402 and 05000499/2024402 05000499/LER-2024-003, Containment Isolation Valve Inoperable Resulting in Condition Prohibited by Technical Specification and Prevention of Fulfillment of Safety Function2024-10-22022 October 2024 Containment Isolation Valve Inoperable Resulting in Condition Prohibited by Technical Specification and Prevention of Fulfillment of Safety Function ML24295A0772024-10-21021 October 2024 Licensed Operator Positive Fitness-for-Duty Test 05000499/LER-2024-002, Two Control Room Envelope HVAC Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function2024-10-17017 October 2024 Two Control Room Envelope HVAC Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function ML24290A1162024-10-16016 October 2024 Change to South Texas Project Electric Generating Station (STPEGS) Emergency Plan ML24255A0322024-09-30030 September 2024 The Associated Independent Spent Fuel Storage Installation - Notice of Consideration of Approval of Direct Transfer of Licenses and Opportunity to Request a Hearing (EPID L-2024-LLM-0002) - Letter ML24269A1762024-09-25025 September 2024 Tpdes Permit Renewal Application WQ0001 908000 05000498/LER-2024-004, Loss of Offsite Power Resulting in Unit 1 Automatic Reactor Trip and Actuation of Emergency Diesel Generators and Auxiliary Feedwater Pumps2024-09-19019 September 2024 Loss of Offsite Power Resulting in Unit 1 Automatic Reactor Trip and Actuation of Emergency Diesel Generators and Auxiliary Feedwater Pumps ML24271A3022024-09-18018 September 2024 STP-2024-09 Post-Exam Comments - Redacted ML24274A0902024-09-16016 September 2024 Written Response - EA-24-026 STP Operator - Redacted ML24250A1882024-09-11011 September 2024 Request for Information for an NRC Post-Approval Site Inspection for License Renewal 05000499/LER-2024-001-01, Supplement to Automatic Reactor Trip and Actuation of Two of Three Emergency Diesel Generators2024-08-29029 August 2024 Supplement to Automatic Reactor Trip and Actuation of Two of Three Emergency Diesel Generators IR 05000498/20240052024-08-22022 August 2024 Updated Inspection Plan for South Texas Project Electric Generating Station, Units 1 and 2 (Report 05000498/2024005 and 05000499/2024005) IR 05000498/20240022024-08-0909 August 2024 Integrated Inspection Report 05000498/2024002 and 05000499/2024002 IR 05000498/20240102024-08-0808 August 2024 Biennial Problem Identification and Resolution Inspection Report 05000498/2024010 and 05000499/2024010 ML24218A1462024-07-26026 July 2024 2. EPA Comments on South Texas Project Exemption Ea/Fonsi ML24207A1782024-07-25025 July 2024 Licensed Operator Positive Fitness-For-Duty Test 05000499/LER-2024-001, Automatic Reactor Trip and Actuation of Two of Three Emergency Diesel Generators2024-07-0202 July 2024 Automatic Reactor Trip and Actuation of Two of Three Emergency Diesel Generators 05000498/LER-2024-003, Condition Prohibited by Technical Specifications and Potential Loss of Safety Function Due to Inoperable Low Head Safety Injection Pump2024-07-0101 July 2024 Condition Prohibited by Technical Specifications and Potential Loss of Safety Function Due to Inoperable Low Head Safety Injection Pump 05000498/LER-2024-002-01, Two Essential Chilled Water Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function2024-06-27027 June 2024 Two Essential Chilled Water Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function 05000498/LER-2023-003-01, Two Essential Chilled Water Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function2024-06-19019 June 2024 Two Essential Chilled Water Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function ML24141A0482024-05-17017 May 2024 EN 56958_1 Ametek Solidstate Controls, Inc ML24137A0882024-05-15015 May 2024 Operator Licensinq Examination Schedule Revision 3 ML24136A2872024-05-15015 May 2024 Submittal of 2024 Nrc/Fema Evaluated Exercise Scenario Manual ML24136A2842024-05-15015 May 2024 Independent Spent Fuel Storage Installation Supplement to Request for Exemption from Various Part 72 Regulations Resulting from Fuel Basket Design Control Compliance ML24130A2712024-05-0909 May 2024 Re Two Essential Chilled Water Trains Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function ML24128A1572024-05-0707 May 2024 Independent Spent Fuel Storage Installation Request for Exemption from Various Part 72 Regulations Resulting from Fuel Basket Design Control Compliance IR 05000498/20240012024-05-0606 May 2024 Integrated Inspection Report 05000498/2024001 & 05000499/2024001 ML24120A3762024-04-29029 April 2024 Annual Dose Report for 2023 ML24116A3032024-04-25025 April 2024 Operations Quality Assurance Plan Condition Adverse to Quality Definition Change Resulting in a Reduction in Commitment ML24116A2282024-04-25025 April 2024 Annual Environmental Operating Report 05000498/LER-2023-004-01, Condition Prohibited by Technical Specifications Due to Inoperable Train of Essential Chilled Water2024-04-25025 April 2024 Condition Prohibited by Technical Specifications Due to Inoperable Train of Essential Chilled Water ML24117A1602024-04-24024 April 2024 2023 Radioactive Effluent Release Report ML24102A2452024-04-23023 April 2024 Exemption from Select Requirements of 10 CFR Part 73 (EPID L-2023-LLE-0046 (Security Notifications, Reports, and Recordkeeping and Suspicious Activity Reporting)) ML24113A3122024-04-22022 April 2024 Cycle 24 Core Operating Limits Report ML24097A0072024-04-0606 April 2024 Relief Request Number RR-ENG-4-07 – Request for an Alternative to ASME Code Case N-729-6 for Reactor Vessel Head Penetration 75 05000498/LER-2024-001, Re Two Steam Generator Power Operated Relief Valves (Porvs) Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function2024-04-0101 April 2024 Re Two Steam Generator Power Operated Relief Valves (Porvs) Inoperable Resulting in a Condition That Could Have Prevented Fulfillment of a Safety Function ML24088A3022024-03-28028 March 2024 Financial Assurance for Decommissioning - 2024 Update ML24081A3972024-03-21021 March 2024 Response to Request for Additional Information for Request for Exemption from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation ML24080A2902024-03-19019 March 2024 Nuclear Liability Certificates of Insurance NOC-AE-240040, Nuclear Liability Certificates of Insurance2024-03-19019 March 2024 Nuclear Liability Certificates of Insurance ML24066A2002024-03-0606 March 2024 10 CFR 50.46 Thirty-Day Report of Significant ECCS Model Changes ML24079A1312024-03-0505 March 2024 Nuclear Insurance Protection ML24060A1742024-02-28028 February 2024 Submittal of Annual Fitness for Duty Performance Report for 2023 IR 05000498/20230062024-02-28028 February 2024 Annual Assessment Letter for South Texas Project Electric Generating Station, Units 1 and 2 (Report 05000498/2023006 and 05000499/2023006) IR 05000498/20240132024-02-27027 February 2024 Design Basis Assurance Inspection (Programs) Commercial Grade Dedication IR 05000498/2024013 and 05000499/2024013 ML24022A2252024-02-20020 February 2024 Issuance of Amendment Nos. 227 and 212 to Authorize the Revision of the Alternative Source Term Dose Calculation ML24050A0082024-02-19019 February 2024 Evidence of Financial Protection ML24045A0922024-02-16016 February 2024 Response to STP FOF Move Letter (2024) 2024-09-30
[Table view] |
Text
Nuclear Operating Company South Tewas ProjectElectric GeneratingStation P.O Box 289 Wadsworth. Teras77483 A/ -
January 20, 2010 NOC-AE- 10002505 10CFR50.90 U. S. Nuclear Regulatory Commission Attention: Document Control Desk One White Flint North 11555 Rockville Pike Rockville, MD 20852 South Texas Project Units 1 and 2 Docket Nos. STN 50-498, STN 50-499 Response to Request for Additional Information Regarding Proposed Amendments for Deviation from Fire Protection Program Requirements (TAC Nos. ME0824, ME0825, ME1389, ME1390)
References:
- 1. Letter from G. T. Powell, STPNOC, to NRC Document Control Desk dated February 3, 2009, "License Amendment Request for Deviation from Fire Protection Program Requirements" (NOC-AE-08002366) (ML090410486)
- 2. Letter from G. T. Powell, STPNOC, to NRC Document Control Desk dated March 3, 2009, "License Amendment Request for Deviation from Fire Protection Program Requirements (Fire Area 27)" (NOC-AE-09002395)
(ML090680781)
In the referenced letters, STP Nuclear Operating Company (STPNOC) submitted license amendment requests for deviation from the South Texas Project Fire Protection Program requirements. This submittal responds to NRC questions regarding these requests received by electronic mail on January 7, 2010.
STPNOC previously responded to the NRC questions by electronic mail on January 11, 2010.
This letter provides additional clarification and thus supersedes the response provided via electronic mail.
There are no new commitments in this submittal.
STI: 32599100
NOE-AE- 10002505 Page 2 If you have any questions, please call Ken Taplett at 361-972-8416 or me at 361-972-7566.
I declare under penalty of perjury that the foregoing is true and correct.
Executed on /1-61-Z,/01 Date G. T. Powell Vice President, Engineering
Attachment:
STPNOC Response to Request for Additional Information STI:32599100
NOE-AE- 10002505 Page 3 cc:
(paper copy) (electronic copy)
Regional Administrator, Region IV A. H. Gutterman, Esquire U. S. Nuclear Regulatory Commission Morgan, Lewis & Bockius LLP 612 East Lamar Blvd, Suite 400 Arlington, Texas 76011-4125 Mohan C. Thadani U. S. Nuclear Regulatory Commission Mohan C. Thadani Kevin Howell Senior Project Manager Catherine Callaway U.S. Nuclear Regulatory Commission Jim von Suskil One White Flint North (MS 8B1A) NRG South Texas LP 11555 Rockville Pike Rockville, MD 20852 Ed Alarcon Senior Resident Inspector J. J. Nesrsta U. S. Nuclear Regulatory Commission R. K. Temple P. 0. Box 289, Mail Code: MN1 16 Kevin Pollo Wadsworth, TX 77483 City Public Service C. M. Canady Jon C. Wood City of Austin Cox Smith Matthews Electric Utility Department 721 Barton Springs Road C. Mele Austin, TX 78704 City of Austin Richard A. Ratliff Texas Department of State Health Services Alice Rogers Texas Department of State Health Services
Attachment NOC-AE- 10002505 Page 1 of 2 STPNOC RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION South Texas Project (STP)
Units I & 2 Docket Nos. STN 50-498, STN 50-499 Response to Request for Additional Information (RAI)
Regarding License Amendment Requests for Deviation from Fire Protection Program Requirements (TAC Nos. ME0824, ME0825, ME1389, ME1390)
Note: The licensee's RAI response to which the NRC refers in the following RAI was submitted by STPNOC to the NRC Document Control Desk on November 20, 2009. (NOC-AE-09002489)
(ML093350537)
NRC RAI The STP Fire Hazards Analysis Report, Amendment 16, page 3.10-4 (ML083260175) appears to include generic deviations from fire codes, but nothing specific to fire areas 27 and 31.
Can you please confirm that this was intended?
The NRC staff is concerned that if this is what the licensee intended, it was not what the staff approved in Supplemental Safety Evaluation Report (SSER) 3, as stated in the licensee's RAI response. In SSER 3, the staff accepted deviations from full suppression due to 3-hour fire barriers. So the staff is unclear what suppression is installed in the fire areas, especially the fire area with partial suppression.
What we need to know is if there is sprinkler protection in the areas where a fire is capable of damaging redundant trains. It appears from the paper work that this is the case, but we need confirmation.
Please provide your response at your earliest convenience.
STPNOC Response The deviations from the National Fire Protection Association code in Section 3.10.4 of the STP Fire Hazards Analysis Report (FHAR), which includes Amendment 16, page 3.10-4, are applicable to all fire areas in the STP Fire Protection Program. Deviations from the STP Fire Protection Program for specific fire areas are documented under the analysis of each fire area.
The analysis of each fire area is located throughout Section 3 of the STP FHAR.
During the initial licensing process, STP acknowledges that the staff approved the STP Fire Protection Program for certain fire areas (including Fire Area 27) that did not have full
Attachment NOC-AE-10002505 Page 2 of 2 suppression because the circuits required for safe shutdown were1 protected by 3-hour fire barriers.
The following discussion regarding if there is sprinkler protection in the areas where a fire is capable of damaging redundant trains is consistent with the information previously provided in References 1 and 2 in the cover letter to this Attachment.
In Fire Area 27, the cables for the two redundant volume control tank outlet motor-operated valves and the cables for the two redundant charging pump suction valves from the refueling water storage tank meet III.G.2 circuit separation criteria with the exception of Fire Zone Z127 where the cables are located adjacent to one another. The cabling for Train B Charging Pump discharge valve CV-MOV-8377B is also located in Fire Zone Z127. There is no sprinkler protection in this fire zone. Fire Zone Z 127 has very few combustibles, such that the loading has a fire severity of 0.33 minutes. The fire zone boundaries within Fire Area 27 are heavy concrete.
Most zone boundaries contain 3-hour rated fire doors. The fire zone door between Fire Zone Z127 and Fire Zone Z138 is not fire rated but is of heavy steel construction. These features provide significant obstructions that will inhibit zone-to-zone fire propagation. In conclusion, a fire is not capable of damaging circuits for the credited train in Fire Zone Z127.
The circuitry for the air-operated solenoid valves to operate Seal Water Injection Valve CV-HCV-0218 is located in Fire Area 27, specifically Fire Zones Z138 and Z139. Ceiling mounted area coverage automatic wet pipe sprinkler systems are installed in Fire Zones Z138 and Z 139. Again, most zone boundaries in Fire Area 27 contain 3-hour rated fire doors. An exception is a fire door to a stairwell that is a 2-hour rated boundary. These features provide significant obstructions that will inhibit zone-to-zone fire propagation. Thus, there is sprinkler protection in the fire zones where a fire is capable of damaging the circuitry to the air-operated solenoid valves operating the valve credited in the safe shutdown train.
SSER 3 addressed six fire areas, including Fire Area 27, which did not have full area suppression in accordance with Section III.G of Appendix R. Fire Area 31 was not one of these fire areas.
Fire Area 31 has area wide suppression as previously stated in the Licensee Amendment Request that is the subject of this request for additional information.
In 1998, STP completed removing the 3-hour fire wrap barriers (i.e., Thermo'-lag) from circuits and cabling (including those in Fire Area 27) because the qualification of Thermo-lag came into question. STP approved the change based on an evaluation performed pursuant to 10 CFR 50.59. The evaluation concluded that the ability of the plant to achieve post fire safe shutdown utilizing a single train of equipment is assured because a redundant pathway of systems and components necessary to achieve and maintain safe shutdown will remain available following a fire in any fire area. As the result of more recent NRC generic communications stating that the use of manual actions in lieu of meeting circuit separation requirements is an adverse change, STP submitted License Amendment Requests (referenced in the cover letter to this Attachment) for approval to credit the use of manual actions in lieu of meeting circuit separation requirements.