'FDominion Dominion Energy Kewaunee, Inc.
N490 Hwy 42, Kewaunee, WI 54216 Web Address: www.dom.com JAN 19 2010 ATTN: Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555-0001 Serial No.10-035 LIC/NW/RO Docket No.: 50-305 License No.: DPR-43 DOMINION ENERGY KEWAUNEE, INC.
KEWAUNEE POWER STATION CORE OPERATING LIMITS REPORT CYCLE 30 REVISION 2 Pursuant to Kewaunee Power Station (KPS) Technical Specification (TS) 6.9.a.4.D, enclosed is a copy of the KPS Technical Requirements Manual Section 2.1, Kewaunee Power Station Core Operating Limits Report Cycle 30, Revision 2.
If you have questions or require additional information, please feel free to contact Mr.
Jack Gadzala at 920-388-8604.
Very truly yours, Mich AelJ. Wilson Director Safety and Licensing Kewaunee Power Station Commitments made by this letter: NONE Enclosure
- 1. KPS Technical Requirements Manual Section 2.1, Kewaunee Power Station Core Operating Limits Report Cycle 30, Revision 2.
A
Serial No.10-035 Page 2 of 2 cc:
Regional Administrator, Region III U. S. Nuclear Regulatory Commission 2443 Warrenville Road Suite 210 Lisle, IL 60532-4352 Mr. P. S. Tam Sr. Project Manager U.S. Nuclear Regulatory Commission One White Flint North, Mail Stop 08-H4A 11555 Rockville Pike Rockville, MD 20852-2738 NRC Senior Resident Inspector Kewaunee Power Station
TRM 2.1 Kewaunee Power Station CORE OPERATING LIMITS REPORT (COLR)
CYCLE 30 REVISION 2 I
Approved FSRC Chairman
/,-//,
Mtg.#
Table of Contents I
Section Title Page
1.0 INTRODUCTION
...................................................... 1 2.0 OPERATING LIM ITS..................................................................................................
2 2.1 Reactor Core Safety Limits 2
2.2 Shutdown Margin (SDM )................................................................................
2 2.3 Moderator Temperature Coefficient...............................................................
2 2.4 Shutdown Bank Insertion Limit.....................................................................
2 2.5 Control Bank Insertion Limits.........................................................................
2 2.6 Nuclear Heat Flux Hot Channel Limits (FoN(Z))............................................... 3 2.7 Nuclear Enthalpy Rise Hot Channel Factor (FAHN).............................................
4 2.8 Axial Flux Difference (AFD)............................................................................
4 2.9 Overtem perature AT Setpoint.......................................................................
4 2.10 Overpower AT Setpoint....................................................................................
5 2.11 RCS Pressure, Temperature, and Flow Departure From Nucleate Boiling (DNB) Limits........................................................................
5 2.12 Refueling Boron Concentration.........................................................................
5
3.0 REFERENCES
6
List of Figures Figure Title Page
- 1.
Reactor Core Safety Limits Curve (1772 MW t)...........................................................
8
- 2.
Required Shutdown Margin vs. Boron Concentration.................................................. 9
- 3.
Hot Channel Factor Normalized Operating Envelope (K(z)).....................................
10
- 4.
Control Bank Insertion Limits....................................................................................
11
- 5.
N(Z) Values (Top and Bottom 9% excluded)............................................................
12
- 6.
Penalty Factor, Fp, for FQN(Z)..................................................................................
16
- 7.
Axial Flux Difference Target Band.............................................................................
17 Ji
KEWAUNEE POWER STATION TECHNICAL REQUIREMENTS MANUAL TRM 2.1 Revision 2 I
CORE OPERATING LIMITS REPORT CYCLE 30
1.0 INTRODUCTION
This Core Operating Limits Report (COLR) for Kewaunee Unit I Cycle 30 has been prepared in accordance with the requirements of Kewaunee Technical Specification 6.9.a.4.
A cross reference between the COLR section and the KPS Technical Specifications' affected by this report is given below:
COLR Section
-I-2.1 Reactor Core Safety Limit 2.2 3.10.a Shutdown Margin 2.3 3.1.f.3 Moderator Temperature Coefficient (MTC) 2.4 3.10.d. 1 Shutdown Bank Insertion Limits 2.5 3.10.d.2 Control Bank Insertion Limits 2.6 3.10.b. 1.A Heat Flux Hot Channel Factor Limits 3.10.b.5
.(FQ"(Z))
3.10.b.6.C.i 2.7 3.10.b. 1.B Nuclear Enthalpy Rise Hot Channel Factor Limits (FAnN) 2.8 3.10.b.8 Axial Flux Difference (AFD) Target Band 2.9 2.3.a.3.A Overtemperature AT Setpoint 2.10 2.3.a.3.B Overpower AT Setpoint 2.11 3.10.k RCS Pressure, Temperature and Flow 3.10.1 Departure from Nucleate Boiling (DNB) 3.10.m.1 Limits 2.12 3.8.a.5 Refueling Boron Concentration Figure 1 2.1 Reactor Core Safety Limits (1772 MWt)
Figure 2 3.1 O.a Required Shutdown Margin Figure 3 K(Z) Normalized Operating Envelope Figure 4 3.10.d.2 Control Bank Insertion Limits Figure 5 N(Z) Values (Top. and Bottom 9% excluded)
Figure 6 Penalty Factor, Fp, for FQN(Z)
Figure 7 3.10.b.8.A Axial Flux Difference Envelope Cycle 30 Page I of 17 Revision 2
KEWAUNEE POWER STATION TRM 2.1 TECHNICAL REQUIREMENTS MANUAL Revision 2 CORE OPERATING LIMITS REPORT CYCLE 30 2.0 OPERATING LIMITS The cycle-specific parameter limits for the specifications listed in Section 1.0 are presented in the following subsections.
These limits have been developed using the NRC-approved methodologies specified in Technical Specification 6.9.a.4.
2.1 Reactor Core Safety Limits (TS 2.1.a)
The combination of rated power level, coolant pressure, and coolant temperature shall not exceed the limits shown in COLR Figure 1 (1772 MWt). The safety limit is exceeded if the point defined by the combination of Reactor Coolant System average temperature and power level is at any time above the appropriate pressure line.
2.2 Shutdown Margin (TS 3.10.a)
When the reactor is subcritical prior to reactor startup, the SHUTDOWN margin shall be at least that shown in COLR Figure 2.
2.3 Moderator Temperature Coefficient (TS 3.1.f.3) 2.3.1 When the reactor is critical and *60% of RATED POWER, the moderator temperature coefficient shall be <5.0 pcm!°F, except during LOW POWER PHYSICS TESTING.
When the reactor is > 60% RATED POWER, the moderator temperature coefficient shall be zero or negative.
2.3.2 The reactor will have a moderator temperature coefficient no less negative than -8 pcm/'F for 95% of the cycle time at full power.
2.4 Shutdown Bank Insertion Limits (TS 3.10.d. 1)
The shutdown banks shall be fully withdrawn (229 steps) when the reactor is critical or approaching criticality.
2.5 Control Bank Insertion Limits (TS 3.1O.d.2)
The control banks shall be limited in physical insertion as shown in COLR Figure 4.
Cycle 30 Page 2 of 17 Revision 2
KEWAUNEE POWER STATION TRM 2.1 TECHNICAL REQUIREMENTS MANUAL Revision 2 CORE OPERATING LIMITS REPORT CYCLE 30 2.6 Nuclear Heat Flux Hot Channel Factor (F0N(Z)) (TS 3.10.b.l.A, 3.10.b.5, and 3.10.b.6.C.i) 2.6.1 FQN(Z) Limits for Fuel FQN(Z)*1.03*"1.05 CFQ *K(Z)forP>0.5
[422 V+]
P F, (Z)* 1.03 *1.05<C K(Z)for PC< 0.5
[422 V+]
0.5 Where
P is the fraction of full power at which the core is OPERATING K(Z) is the function given in Figure 3 Z
is the core height location for the FQ of interest CFQ
= 2.50 2.6.2 The measured FQN(Z) hot channel factors under equilibrium conditions shall satisfy the following relationship for the central axial 80% of the core for fuel:
Foj (Z)* 1.03* 1.05* N(Z)* Fp <_ CFQ
- K(Z)
[422 V+]
P Where:
P is the fraction of full power at which the core is OPERATING K(Z) is the function given in Figure 3 Z
is the core height location for the FQ of interest CFQ equals 2.50 Fp is the penalty factor described in 2.6.3 N(Z) is a cycle-specific non-equilibrium multiplier on FQN(Z) to account for power distribution transients during normal operation, provided in Figure 5.
FQN(Z) is a measured FQ distribution obtained during the target flux determination The N(z) decks are generated for normal operation flux maps that are typically taken at full power, ARO. Additional N(z) decks may be generated, if necessaty, consistent with the methodology described in Reference 1.
2.6.3 The penalty factor of 1.0 shall be used for TS 3.10.b.6.A and TS 3.10.b.6.B.
The penalty factor provided in COLR Figure 6 shall be used for TS 3.1O.b.6.C.i.
The penalty factor for all burnups outside the range of Figure 6 shall be 1.02.
Cycle 30 Page 3 of 17 Revision 2
KEWAUNEE POWER STATION TRM 2.1 TECHNICAL REQUIREMENTS MANUAL Revision 2 CORE OPERATING LIMITS REPORT CYCLE 30 2.7 Nuclear Enthalpy Rise Hot Channel Factor Limits (FU&)
(TS 3.10.b.1 B)
F
- "1.04* CFDH*[I + PFDH(l-P)]
[422 V+]
Where:
P is the fraction of full power at which the core is OPERATING CFDH = 1.70 PFDH = 0.3 2.8 Axial Flux Difference (AFD) Target Band (TS 3.10.b.8)
The Axial Flux Difference (AFD) acceptable operation limits are provided in COLR Figure 7.
2.9 Overtemperature AT Setpoint (TS 2.3.a.3.A)
AT<AT0 K,-K 2 *1(T-Ts)
-+K3*(P-P')-A(A' 1+ -r2s ATo Indicated AT at RATED POWER, %
T Average temperature, OF T'
- 5 573.0 OF P
= Pressurizer Pressure, psig P'
=
2235 psig K,
_* 1.195 K2
=
0.015/ 0F K3
= 0.00072/psig Tl
- 30 seconds T2 4 seconds fi(AI) = An even function of the indicated difference between top and bottom detectors of the power range nuclear ion chambers. Selected gains are based on measured instrument response during plant startup tests, where qt and qb are the percent power in the top and bottom halves of the core respectively and qt + qb is total core power in percent RATED POWER, such that (a) For qt - qb within -15, +6 %, fi(AI) = 0 (b) For each percent that the magnitude of qt - qb exceeds +6%, the AT trip setpoint shall be automatically reduced by an equivalent of 1.51% of RATED POWER.
(c) For each percent that the magnitude of qt - qb exceeds -15%, the AT trip setpoint shall be automatically reduced by an equivalent of 3.78% of RATED POWER.
Cycle 30 Page 4 of 17 Revision 2
KEWAUNEE POWER STATION TRM 2.1 TECHNICAL REQUIREMENTS MANUAL Revision 2 CORE OPERATING LIMITS REPORT CYCLE 30 2.10 Overpower AT Setpoint (TS 2.3.a.3.B)
AT*< ATO *K 4 -K 5 V3s 1*TK
- (T1T'f(M)
ATo
=
Indicated AT at RATED POWER, %
T
= Average temperature, OF T)
_<Eý 573.0 OF K4
< 1.095 K5 0 0.0275/°F for increasing T
=> 0 for decreasing T K6 0 0.00103/°F for T > T'
>0 forT <T' 3
>_ 10 seconds f2(Al) =
0 for all Al 2.11 RCS Pressure, Temperature and Flow Departure from Nucleate Boiling (DNB) Limits (TS 3.10.k, 3.10.1, and 3.10.m.1) 2.11.1 During steady state power operation, Tavg shall be < 576.7 °F for control board indication or < 576.5 °F for computer indication.
2.11.2 During steady state power operation, pressurizer pressure shall be > 2217 psig for control board indication or > 2219 psig for computer indication.
2.11.3 During steady state power operation, reactor coolant total flow rate shall be >_ 186,000 gpm.
2.12 Refueling Boron Concentration (TS 3.8.a.5)
When there is fuel in the reactor, a minimum boron concentration of 2500 ppm and a shutdown margin of >_ 5% Ak/k shall be maintained in the Reactor Coolant System during reactor vessel head removal or while loading and unloading fuel from the reactor.
Cycle 30 Page 5 of 17 Revision 2
KEWAUNEE POWER STATION TRM 2.1 TECHNICAL REQUIREMENTS MANUAL Revision 2 CORE OPERATING LIMITS REPORT CYCLE 30 3.0 References
- 1. Topical Report DOM-NAF-5-A, "Application of Dominion Nuclear Core Design and Safety Analysis Methods to the Kewaunee Power Station (KPS)," dated July, 2006.
Methodology for:
TS 2.1 - Reactor Core Safety Limits; TS 3.10.a-Shutdown Margin; TS 3.1.f.3 - Moderator Temperature Coefficient; TS 3.10.d.1 - Shutdown Bank Insertion Limits; TS 3.10.d.2 - Control Bank Insertion Limits; TS 3.10.b. 1.A, 3.10.b.5, and 3.10.b.6.C.i - Heat Flux Hot Channel Factor Limits (FQN(Z));
TS 3.1 O.b. 1.B Nuclear Enthalpy Rise Hot Channel Factor Limits (FAH*);
TS 3.10.b.8 - Axial Flux Difference (AFD) Target Band; TS 3.10.k, 3.10.1 and 3.1O.m. I - RCS Pressure, Temperature and Flow Departure from Nucleate Boiling (DNB) Limits; TS 3.8.a.5 - Refueling Boron Concentration
- 2. Kewaunee Nuclear Power Plant - Review for Kewaunee Reload Safety Evaluation Methods Topical Report WPSRSEM-NP-A, Revision 3 (TAC No. MB0306) dated September 10, 2001.
Methodology for:
- 3. S.M. Bajorek, et al., WCAP-12945-P-A (Proprietary), Westinghouse Code Qualification Document for Best-Estimate Loss-of-Coolant Accident Analysis, Volume 1, Rev. 2, and Volume II-V, Rev. 1 March 1998.
Methodology for:
TS 3.10.b.1.A, 3.10.b.5, and 3.10.b.6.C.i - Heat Flux Hot Channel Factor Limits (FQN(Z))
TS 3. 10.b. 1.B Nuclear Enthalpy Rise Hot Channel Factor Limits (FAHN);
- 4. N. Lee, et al., "Westinghouse Small Break ECCS Evaluation Model Using the NOTRUMP Code," WCAP-10054-P-A, dated August 1985.
Methodology for:
TS 3.10.b.1.A, 3.10.b.5, and 3.10.b.6.C.i - Heat Flux Hot Channel Factor Limits (FQN(Z))
- 5. C. M. Thompson, et al., "Addendum to the Westinghouse Small Break ECCS Evaluation Model Using the NOTRUMP Code: Safety Injection into the Broken Loop and the COSI Condensation Model," WCAP-10054-P-A, Addendum 2, Revision 1, dated July 1997.
Methodology for:
TS 3.10.b.I.A, 3.10.b.5, and 3.10.b.6.C.i - Heat Flux Hot Channel Factor Limits (FQN(Z))
Cycle 30 Page 6 of 17 Revision 2
KEWAUNEE POWER STATION TRM 2.1 TECHNICAL REQUIREMENTS MANUAL Revision 2 CORE OPERATING LIMITS REPORT CYCLE 30
- 6. WCAP-9272-P-A, "Westinghouse Reload Safety Evaluation Methodology," July 1985.
(Westinghouse Proprietary,)
Methodology for:
TS 2.1 - Reactor Core Safety Limits; TS 3.1.f.3 - Moderator Temperature Coefficient;
- 7. WCAP-8745-P-A, Design Bases for the Thermal Overtemperature AT and Thermal Overpower AT trip functions, September 1986.
Methodology for:
TS 2.3.a.3.A - Overtemperature AT Setpoint; TS 2.3.a.3.B - Overpower AT Setpoint
- 8. S. I. Dederer, et al., WCAP-14449-P-A, Application of Best Estimate Large-Break LOCA Methodology to Westinghouse POWs with Upper Plenum Injection, Rev. 1, October 1999.
Methodology for:
TS 3.10.b. 1.A, 3.10.b.5, and 3.1O.b.6.C.i - Heat Flux Hot Channel Factor Limits (FQN(Z))
TS 3.10.b.1.B Nuclear Enthalpy Rise Hot Channel Factor Limits (FnHN);
- 9. WCAP-12610-P-A, "VANTAGE+ Fuel Assembly Reference Core Report," April 1995.
(Westinghouse Proprietary)
Methodology for:
TS 3.10.b.L.A, 3.10.b.5, and 3.1O.b.6.C.i - Heat Flux Hot Channel Factor Limits (FQN(Z))
- 10. CENP-397-P-A, "Improved Flow Measurement Accuracy Using Cross Flow Ultrasonic Flow Measurement Technology," Rev. 1, May 2000.
Methodology for:
TS 2.3.a.3.A - Overtemperature AT Setpoint; TS 2.3.a.3.B - Overpower AT Setpoint Cycle 30 Page 7 of 17 Revision 2
KEWAUNEE POWER STATION TECHNICAL REQUIREMENTS MANUAL CORE OPERATING LIMITS REPORT CYCLE 30 TRM 2.1 Revision 2 Figure 1 Reactor Core Safety Limits Curve (1772 Mwt)
(Cores Containing 422V+ fuel)
(TS 2.1.a) 665 U-0_
645 4-.
L.
E 0 625 Ct-0O 605 L-0OC.
a) 585 565 0
20 40 60 80 100 Core Power (percent of 1772 MWt) 120 Cycle 30 Page 8 of 17 Revision 2
KEWAUNEE POWER STATION TECHNICAL REQUIREMENTS MANUAL TRM 2.1 Revision 2 CORE OPERATING LIMITS REPORT CYCLE 30 Figure 2 Required Shutdown Margin vs. Boron Concentration (TS 3.10.a) 1700 1600 1554 1500 1400 1300 1200 1100 1000
- 0. "*ý 900 o
800
- 3 Cr 700 6O00 500 400 300 200 100 0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 Full Power Equilibrium Boron Concentration (ppm)
Cycle 30 Page 9 of 17 Revision 2
KEWAUONEE POWER STATION TECHNICAL REQUIREMENTS MANUAL TRM 2.1 Revision 2 CORE OPERATING LIMITS REPORT CYCLE 30 Figure 3 Hot Channel Factor Normalized Operating Envelope (K(Z))
N 1.2 1.1 1
0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0
(0,1.0)
(6,11.0) 4,T -rT-T.
1 T
.T.T.T.r.T.T
~
(12,1.0) 0 1
2 3
4 5
6 7
8 9
10 11 Core Height (ft) 12 Cycle 30 Page 10 of 1.7 Revision 2
KEWAUNEE POWER STATION TECHNICAL REQUIREMENTS MANUAL CORE OPERATING LIMITS REPORT CYCLE 30 TRM 2.1 Revision 2 Figure 4 Control Bank Insertion Linmits (TS 3.10.d.2) 240 220 200 180 160 140 120 CL 0
100 m
CU 0
80 60
-£60 40 20 0
Fully w/d Position 229 steps I
1 I (14.34%, 229)
(66.25%, 229) 4 BANKB B
(.%,(100.0%,
185)
_BIANK C
A BANK D (0.0%, 68)
(23.8%,0) 0 10 20 30 40 50 60 70 Percent of Rated Thermal Power 80 90 100 Note: The Rod Bank Insertion Limits are based on a control bank tip-to-tip distance of 126 steps.
Cycle 30 Page 11 of 17 Revision 2
KEWAUNEE POWER STATION TECHNICAL REQUIREMENTS MANUAL CORE OPERATING LIMITS REPORT CYCLE 30 TRM 2.1 Revision 2 Figure 5 N(Z) Values' I Height I
Burnun (MWD/MTU)
Node (FEET) 0 to 1000 1000 to 3000 3000 to 5000 5000 to 7000 7000 to 9000 9000 to 11000 AO = 0.50%
AO = -1.2%
AO = -2.4%
AO = -2.8%
AO = -2.6%
AO = -2.4%
Top 7
10.8 1.092 1.127 1.147 1.147 1.146 1.123 8
10.6 1.090 1.126 1.143 1.143 1.141 1.127 9
10.4 1.090 1.124 1.139 1.139 1.138 1.133 10 10.2 1.090 1.122 1.136 1.135 1.138 1.138 II.
10.0 1.091 1121 1.132 1.133 1.141 1.142 12 9.8 1.094 1.119 1.127 1.130 1.144 1.145 13 9.6 1.098 1.117 1.123 1.129 1.147 1.147 14 9.4 1.100 1.113 1.116 1.127 1.147 1.147 15 9.2 1.102 1.113 1.115 1.128 1.148 1.148 16 9.0 1.106 1.121 1.121 1.133 1.145 1.145 17 8.8 1.112 1.132 1.132 1.142 1.147 1.147 18 8.6 1.120 1.140 1.140 1.151 1.156 1.159 19 8.4 1.127 1.146 1.146 1.160 1.169.
1.174 20 8.2 1.132 1.150 1.150 1.168 1.179 1.184 21 8.0 1.135
.1.152 1.152 1.173 1.188 1.193 22 7.8 1.136 1.153 1.153 1.178 1.195 1.203 23 7.6 1.135 1.152 1.152 1.180 1.201 1.210 24 7.4 1.132 1.149 1.149 1.180 1.204 1.217 25 7.2 1.130 1.148 1.147 1.181 1.206 1.221 26 7.0 L.127 1.145 1.144 1.181 1.207 1.223 27 6.8 1.121 1.137 1.141 1.174 1.204 1.226 28 6.6 1.113 1.125 1.136 1.164 1.198 1.227 29 6.4 1.108 1.118 1.132 1.159 1.195 1.227 30 6.2 1.104 1.112 1.127 1.156 1.192 1.223 31 6.0 1.099 1.104 1.123 1.153 1.189 1.220 32 5.8 1.093 1.096 1.118 1.149 1.183 1.212 33 5.6 1.082 1.085 1.110 1.144 1.175 1.203 34 5.4 1.075 1.079 1.104 1.135 1.166 1.192 35 5.2 1.073 1.077 1.101 1.124 1.160 1.183 36 5.0 1.076 1.079 1.102 1.114 1.156 1.174 37 4.8 1.079 1.080 1.103 L.107 1.153 1.166 38 4.6 1.090 1.090 1.103 1.104 1.152 1.158 39 4.4 1.104 1.104 1.103 1.102 1.149 1.150 40 4.2 1.111 1.111 1.102 1.102 1.144 1.143 41 4.0 1.111 1.111 1.101 1.101 1.138 1.137 42 3.8 1.115 1.115 1.101 1.098 1.131 1.131 43 3.6
- 1. 124 1.124 1.104 1.096 1.124 1.123 44 3.4 1.134 1.134 1.108 1.093 1.115 1.115 45 3.2 1.145 1.145 1.116 1.096 1.105 1.105 46 3.0 1.156 1.156 1.125 1.101 1.094 1.093 47 2.8 1.166 1.166 1.136 1.110 1.085 1.085 48 2.6 1.175 1.176 1.145 1.116 1.076 1.080 S49 2.4 1.186 1.186 1.156 1.126 1.075 1.081 50 2.2 1.200 1.199 1.169 1.138 1.078 1.684 Cycle 30 Page 12 of 17 Revision 2
KEWAUNEE POWER STATION TECHNICAL REQUIREMENTS MANUAL CORE OPERATING LIMITS REPORT CYCLE 30 TRM 2.1 Revision 2 Figure 5 (continued)
N(Z) Values I
-I Height Bumup (MWDIMTU) 0 to 1000 1000 to 3000 3000 to 5000 5000 to 7000 7000 to 9000 9000 to 11000 (FEET)
AO =0.50%
AO= -1.2%
AO = -2.4%
AO = -2,8%
AO = -2.6%
AO = -2.4%
51 2.0 1.210 1.207 1.178 1.146 1L082 1.088 52 1.8 1.214 1.211 1.181 1.149 1.082 1.088 53 1.6 1.218 1.214 1.185 1.151 1.084 1.089 54 1.4 1.225 1.221 1.191 1.157 1.086 1.091 55 1.2 1.232 1.226 1.197 1.162 1.088 1.094 Bottom
- 1) Excludes top and bottom 9%
These decks were generated for normal operation flux maps that are typically taken at full power ARO. Additional N(z) decks may be generated, if necessary, consistent with the methodology described in Reference 1.
Cycle 30 Page 13 of 17 Revision 2
KEWAUNEE POWER STATION TECHNICAL REQUIREMENTS MANUAL CORE OPERATING LIMITS REPORT CYCLE 30 TRM 2.1 Revision 2 Figure 5 (continued)
N(Z) ValuesI Height Bumup (MWD/MTU) 1 11000 to 13000 13000to 15000 15000 to 17000 17000to EOR Node (FEET)
AO = -2.2%
AO = -2.1%
AO = -2.2%
AO = -2.2%
Top 7
10.8 1.103 1.102 1.096 1.099 8
10.6 1.101 1.102 1.099 1.098 9
10.4 1.100 1.106 1.105 1.097 10 10.2 1.098 1.111 1.112 1.096 11 10.0 1.097 1.117 1.117 1.096 12 9.8 1.101 1.120 1.120 1.098 13 9.6 1.109 1.121 1.121 1.105 14 9.4 1.113 1.123 1.123 1.110 15 92 1.119 1.127
,1.127 1.119 16 9.0 1.130 1.130 1.128 1.126 17 8.8 1.146 1.138 1.134 1.139 18 8.6 1.161 1.148 1.146 1.157 19 8.4 1.174 1.159 1.159 1.176 20 8.2 1.185 1.167 1.166 1.189 21 8.0 1.194 1.175 1.175 1.200 22 7.8 1.203 1.182 1.187 1.212 23 7.6 1.210 1.187 1.199 1.221 24 7.4 1.217 1.190 1.208 1.228 25 7.2 1.221 1.192 1.215 1.232 26 7.0 1.223 1.194 1.218 1.234 27 6.8 1.226 1.197 1.225 1.237 28 6.6 1.227 1.203 1.232 1.241 29 6.4 1.227 1.208 1.235 1.243 30 6.2 1.223 1.211 1.233 1.241 31 6.0 1.219 1.213 1.233 1.241 32 5.8 1.213 1.210 1.229 1.237 33 5.6 1.209 1.210 1.225 1.233 34 5.4 1.204 1.205 1.217 1.224 35 5.2 1.198 1.199 1.206 1.212 36 5.0 1.190 1.191 1.199 1.205 37 4.8 1.182 1.182 1.198 1.203 38 4.6 1.170 1.170 1.191 1.194 39 4.4 1.156 1.156 1.177 1.178 40 4.2 1.144 1.144 1.167 1.167 41 4.0 1.136 1.136 1.162 1.161 42 3.8 1.129 1.129 1.155 1.155 43 3.6 1.122 1.122 1.146 1.146 44 3.4 1.113 1.113 1.134 1.134 45 3.2 1.103 1.105 1.121 1.121 46 3.0 1.090 1.095 1.105 1.105 47 2.8 1.083 1.090 1.096 1.096 48 2.6 1.081 1.086 1.092 1.092 49 2.4 1.085
.1.088 1.095 1.095 50.
.2......1.088 1.092 1.097 1.097 Cycle 30 Page 14 of 17 Revision 2
KEWAUNEE POWER STATION TECHNICAL REQUIREMENTS MANUAL CORE OPERATING LIMITS REPORT CYCLE 30 TRM 2.1 Revision 2 Figure 5 (continued)
N(Z) Values 1 Height Bumup (MWDJMTLJ)
Height Bumup (MWD/MTLJ) 11000 to 13000 13000 to 15000 15000to 17000 17000 to EOR Node (FEET)
AO = -2.2%
AO = -2.1%
AO = -2.2%
AO = -2.2%
51 2.0 1.092 1.098 1.101 1.102 52 1.8 1.092 1.102 1.103 1.104 53 1.6 1.093 1.106 1.106 1.106 54 1.4 1.095 1.110 1.110 1.106 55 1.2 1.097 1.115 1.115 1.107 Bottom
- 1) Excludes top and bottom 9%
These decks were generated for normal ope/ation flux maps that are typically taken at full power ARO. Additional N(z) decks may be generated, if necessary, consistent with the methodology described in Reference 1.
Cycle 30 Page 15 of 172 Revision 2
KEWAUNEE POWER STATION TRM 2.1 TECHNICAL REQUIREMENTS MANUAL Revision 2 CORE OPERATING LIMITS REPORT CYCLE 30 Figure 6 Penalty Factor, Fp, for FQN(Z)
Cycle Burnup Penalty Factor (MWD/MTU)
Fp 150 1.02 18,700 1.02 Note: Linear interpolation is adequate for intermediate cycle burnups.
All cycle bumups outside the range of the table shall use a penalty factor, Fp, of 1.02. Refer to TS 3.10.b.6.C.i.
Cycle 30 Paae 16 of 17 Revision 2
KEWAUNEE POWER STATION TECHNICAL REQUIREMENTS MANUAL CORE OPERATING LIMITS REPORT CYCLE 30 TRM 2.1 Revision 2 Figure 7 Axial Flux Difference Target Band (3.10.b.8.A) 110 100 90 0
0 80 E
0 0
a.
60 50 40
-40
-30
-20
-10 0
10 Axial Flux Difference (% Delta-I) 20 30 40 Note: This figure represents the Relaxed Power Distribution Control (RPDC) band used in safety analyses; it may be administratively tightened depending on in-core flux map results. Refer to Figure RD 11.4. lof the Reactor Data Manual.
Cycle 30 Page 17 of 17 Revision 2