Startup Test Activity Reduction (STAR) Summary Report
ML092580092
Person / Time
Site: San Onofre 
(NPF-015)
Issue date: 09/09/2009
From: Scherer A
Southern California Edison Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML092580092 (3)


Text

SOUTHERN CALIFORNIA A. Edward Scherer EDirector F

1________

Nuclear Regulatory Affairs An EDISON INTERNATIONAL Company September 9, 2009 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001

Subject:

San Onofre Nuclear Generating Station, Unit 3 (SONGS-3)

Docket No. 50-362 License No. NPF-15 Startup Test Activity Reduction (STAR) Summary Report

REFERENCE:

1.

WCAP-16011-P-A, Revision 0, "Startup Test Activity Reduction Program," February 2005 2.. SCE-9801-P-A, Reload Analysis Methodology for the San Onofre Nuclear Generating Station Units 2 and 3 [Reload Topical Report],

June 1999

Dear Sir or Madam:

SONGS-3 Cycle 15 achieved initial criticality on December 15, 2008. Following that criticality, Southern California Edison (SCE) applied the methodology presented in the Westinghouse Owner's Group (WOG) Startup Test Activity Reduction (STAR) Program (Reference 1) to eliminate Control Element Assembly (CEA) group worth testing from the Low Power Physics Testing (LPPT) program.

Three conditions and limitations were included in the NRC Safety Evaluation (SE) of Reference 1:

1. The STAR program is applicable only to the participating plants as defined in Table 3-1 of the topical report.
2. Should any of the STAR test results fall outside of the test criteria, either ascertain that the safety analysis and STAR applicability requirements are satisfied, or discontinue use of the STAR program for that fuel cycle.
3. Each licensee using STAR is required to submit a summary report following the first application, whether successful or not, of STAR to its plant. The report should (a) identify the core design method used, (b) compare the measured and calculated values and the differences between these values to the corresponding core design method uncertainties and (c) show compliance with the STAR applicability requirements. If the application of STAR is unsuccessful, identify the reasons why the STAR application failed.

P.O. Box 128 San Clemente, CA 92674

Document Control Desk September 9, 2009 The purpose of this letter is to provide San Onofre Nuclear Generating Station (SONGS) compliance with these conditions and limitations.

Condition/Limitation 1 is validated by Table 3-1 of Reference 1, which lists SONGS-3 as a participating plant; therefore, the STAR Program may be applied to the SONGS-3 Cycle 15 reload core.

Condition/Limitation 2: The SONGS-3 tests were within acceptable criteria; therefore this condition/limitation does not apply. Test results are provided in Attachment 1 of the Enclosure (see below).

Condition/Limitation 3 requirements are met by the Enclosure, "SONGS-3 Cycle 15 STAR Program Implementation Summary Report." The Westinghouse ROCS computer program and Studsvik SIMULATE-3 (SIM-3) computer program were used for the core design and startup physics test predictions of SONGS-3 Cycle 15, consistent with Reference 2. The measured test results for all the required STAR tests in Table 3-3 of Reference 1 were within the test criteria. Where applicable, the differences between the measured and calculated values and the core design method uncertainties were all within the core design method uncertainties. The STAR applicability requirements were all validated to be met.

SONGS Technical Specification Surveillance Requirement (SR) 3.1.4.1, "Verify MTC

[Moderator Temperature Coefficient] within the upper limit [prior to entering Mode 1 after each fuel loading]," was not changed prior to SONGS-3 Cycle 15 initial criticality; therefore, SR 3.1.4.1 was performed consistent with previous cycles.

SONGS implemented the STAR program in accordance with Reference 1 Appendix G Attachment A, "Implementation of the STAR Program." The application of STAR to SONGS-3 Cycle 15 was considered successful.

This letter does not contain any NRC commitments. If you have any questions or require additional information, please contact Linda Conklin at 949-368-9443.

Sincerely,

Document Control Desk September 9, 2009

Enclosure:

as stated cc:

E. E. Collins, Regional Administrator, NRC Region IV R. Hall, NRC Project Manager, San Onofre Units 2 and 3 G. G. Warnick, NRC Senior Resident Inspector, San Onofre Units 2 and 3