ML092580081
| ML092580081 | |
| Person / Time | |
|---|---|
| Site: | Mcguire, Palo Verde, McGuire |
| Issue date: | 09/09/2009 |
| From: | Stepantschenko P Engine Systems |
| To: | Office of Nuclear Reactor Regulation |
| References | |
| 45335 | |
| Download: ML092580081 (7) | |
Text
0910912009 U.S. Nuclear Regulatory Commission Operations Center Event Report Paze I General Information or Other (PAR)
Event#
45335 Rep Org: ENGINE SYSTEMS, INC Notification Date / Time: 09/09/2009 14:50 (EDT)
Supplier: ENGINE SYSTEMS, INC Event Date / Time: 08/14/2009 (EDT)
Last Modification: 09/09/2009 Region:
1 Docket #:
City: ROCKY MOUNT Agreement State:
Yes County:
License #:
State: NC NRC Notified by: PAUL STEPANTSCHENK Notifications: ALAN BLAMEY R2DO HQ Ops Officer: STEVE SANDIN DAVID PROULX R4DO Emergency Class: NON EMERGENCY PART 21 COORDINATOR NRR 10 CFR Section:
21.21 UNSPECIFIED PARAGRAPH PART 21 INVOLVING WOODWARD GOVERNORS USING UNAPPROVED SUPPLIER INTEGRATED CIRCUITS The following information was provided via fax:
"COMPONENT: Woodward 2301A and DRU with unapproved supplier IC P/N: 9903-303, 9903-337, 9903-444 &
9903-470 "DISCUSSION: Engine Systems Inc. (ESI) began a 10CFR21 evaluation on 8/14/09 to evaluate the use of an integrated circuit (IC) used in some 2301A and DRU controls. The suspect IC was obtained byWoodward from an unapproved supplier. The evaluation was concluded on 09/08/09 and was determined to be a reportable defect as defined by 10CFR21.
"On 8/14/09, Woodward confirmed that they had shipped ESI a total of thirty-four (34) 2301A and DRU controls with nuclear part numbers that contained an IC (Woodward P/N 1688-767) from a suspect lot. The lot was dated 12/12/08 and was received by Woodward from an unapproved supplier. Eight (8) of the 34 controls were subsequently shipped by ESI to nuclear customers (2 domestic plants and 3 foreign plants) before the issue was identified. To date, no operability issues have been reported or observed with 2301A and DRU controls containing the suspect IC.
"In the DRU, the IC is used in the raise-lower circuit and in the ramp time circuit (the ramp time circuit controls the ramp rate of the DRU). The DRU is primarily used as the speed reference input signal to the 2301A and provides remote speed adjustment for the 2301A (similar to the function of a motor operated potentiometer - MOP). In some applications, the DRU has also been used as a replacement for the voltage regulator MOP; in this case, the DRU provides the voltage adjustment signal to the voltage regulator. Failure of this IC could impact speed (frequency) control (and in some cases voltage control) of the EDG.
0910912009 U.S. Nuclear Regulatory Commission Operations Center Event Report Paw 2 General Information or Other (PAR)
Event#
45335 "In the 2301A, the IC is used in the start fuel limit circuit and in the speed signal input (magnetic pickup) circuit. The 2301A is the electronic governor used on many EDG's. It provides speed and/or load control of the diesel engine by communicating with the governor/actuator mounted on the diesel engine. Failure of this IC could impact speed (frequency) control of the EDG.
"AFFECTED USERS: Thirty-four (34) controls were shipped to ESI containing IC's from the suspect lot. Twenty-six (26) of the suspect controls were in ESI inventory and have been returned to Woodward to have the suspect IC replaced. ESI shipped eight (8) controls with suspect IC's to nuclear customers as safety related items as identified in the tables below.
"LISTING OF WOODWARD CONTROLS SHIPPED WITH SUSPECT IC's - (DOMESTIC PLANTS)
McGuire - P/N # 9903-337, Customer PO # 00114776 Palo Verde - P/N # 9903-470 and # 9903-444, Customer PO # 500529186 "LISTING OF WOODWARD CONTROLS SHIPPED WITH SUSPECT IC's - (FOREIGN PLANTS)
Korea-KHNP - P/N # 9903-470, Customer PO # K080553241 Almaraz - P/N # 9903-470 and # 9903-337, Customer PO # 2009/015 - ER09AT06805MA KRSKO - P/N # 9903-303, Customer PO # NEK-10271/309 "CORRECTIVE ACTION: The controls listed in the tables above should-be returned to Engine Systems Inc. to have the suspect IC replaced as soon as possible. Contact ESI's Customer Service department with the part number and serial number of the control to be returned.
09-09--Og;O2:45PM;
- 252-446-3830 1/
5 ESI ENGINE SYSTEMS, INC 1
1220 S. Washington St., Rocky Mount, NC 2780 P.O. Box 1928, Rocky Mount, NC 27802-1928 1
Telephone: 252/977-2720 Fax: 252/446-1134 TELEFAX Date:
Company:
Fax Number:
Verification No.:
Reference:
From:
Page:
September 9, 2009 NRC Operations Center 301/816-5151 301/816-5100 Report No. 10CFR21-0097, Rev. 0 Paul Stepantschenko 1 of 5
Dear Sir:
Following this cover is a copy of our report 1 OCFR21-0097, Rev.0, for a 1 OCFR21 reportable notification about a Woodward 2301 A and DRU with unapproved supplier IC, P/N: 9903-303, 9903-337, 9903-444 and 9903-470.
A copy of this report is also being mailed to the NRC Document Control Desk and to our affected nuclear customers.
Should you have questions, please let us know.
Sincerely, ENGINE SYSTEMS, INC.
Paul Stepantschenko Quality Assurance Manager Quality Performance With Pride
09-09--09;02:45PM;
- 252-446-3830 2/
5 U-. ENGINE SYSTEMS, INC.
175 Freight Road, Rocky Mount, NC 27804 Telephone: 252/977-2720 Fax: 252/446-1134 Report No. 10CFR21-0097 Rev. 0:
09/09/09 10CFR21 REPORTING OF DEFECTS AND NON-COMPLIANCE COMPONENT:
SYSTEM:
CONCLUSION:
Woodward 2301A and DRU.with unapproved supplier IC P/N: 9903-303, 9903-337, 9903-444 & 9903-470 Emergency Diesel Generator - governor system Reportablein accordance with 10CFR21.
Prepared By:
Reviewed By:
7*
Engineering Manager Date: _______
Date:
Quality Assurance Manager Quality Performance With Pride
09-09-09;02:45PM;
- 252-446-3830 3/
5 Report No.
10CFR21-0097 Record of Revisions Page:
1 of 1 REV DATE PAGE I DESCRIPTION 0
09/09/09 Initial issue.
09-09-09; 02:
45PM;
- 252-446-3830 4/
6 Report No.
10CFR21-0097 Revision:
0 Date:
09/09/09 Page:
1 of 2 COMPONENT:
Woodward 2301A and DRU with unapproved supplier IC P/N: 9903-303, 9903-337, 9903-444 & 9903-470 DISCUSSION:
Engine Systems Inc. (ESI) began a 10CFR21 evaluation on 8/14/09 to evaluate the use of an
,integrated circuit (IC) used in some 2301A and DRU controls. The suspect IC was obtained by Woodward from an unapproved supplier. The evaluation was concluded on 09/08/09 and was determined to be a reportable defect as defined by 100FR21.
On 8/14/09, Woodward confirmed that they had shipped ESI a total of thirty-four (34) 2301A and DRU controls with nuclear part numbers that contained an IC (Woodward P/N 1688-767) from a suspect lot. The lot was dated 12/12/08 and was received by Woodward from an unapproved supplier. Eight (8) of the 34 controls were subsequently shipped by ESI to nuclear customers (2 domestic plants and 3 foreign plants) before the issue was identified. To date, no operability issues have been reported or observed with 2301A and DRU controls containing the suspect IC.
In the DRU, the IC is used in the raise-lower circuit and in the ramp time circuit (the ramp time circuit controls the ramp rate of the DRU). The DRU is primarily'used as the speed reference input signal to the 2301A and provides remote speed adjustment for the 2301A (similar to the function of a motor operated potentiometer - MOP).
In some applications, the DRU has also been used as a replacement for the voltage regulator MOP; in this case, the DRU provides the voltage adjustment signal to the voltage regulator.
Failure of this IC could impact speed (frequency) control (and in some cases voltage control) of the EDG.
In the 2301A, the IC is used in the start fuel limit circuit and in the speed signal input (magnetic pickup) circuit. The 2301A is the electronic governor used on many EDG's. It provides speed and/or load control of the diesel engine by communicating with the governor/actuator mounted on the diesel engine. Failure of this IC could impact speed (frequency) control of the EDG.
09-09--09;02:45PM;
- 252-446-3830 5/
5 Report No.
Revision:
Date:
Page:
09/09/09 2 of 2 AFFECTED USERS:
Thirty-four (34) controls were shipped to ESI containing IC's from the suspect lot. Twenty-six (26) of the suspect controls were in ESI inventory and have been returned to Woodward to have the suspect IC replaced.
ESI shipped eight (8) controls with suspect IC's to nuclear customers as safety related items as identified in the tables below.
LISTING OF WOODWARD CONTROLS SHIPPED WITH SUSPECT IC's (DOMESTIC PLANTS)
Part Woodward ESI Sales ESI Customer Number Type S/N Order Ship Date Customer Purchase Order 9903-337 2301A 16466280 3005430 5/19/2009 McGuire 00114776 9903-470 DRU 16517000 3005474 5/14/2009 Palo-Verde 500529186 9903-470 DRU 16519303 3005474 5/14/2009 Palo-Verde 500529186 9903-444 2301A 16614277 3005474 8/12/2009 Palo-Verde 500529186 LISTING OF WOODWARD CONTROLS SHIPPED WITH SUSPECT IC's (FOREIGN PLANTS)
Part Woodward ESI Sales ESI Customer Number Type S/N Order Ship Date Customer Purchase Order 9903-470 DRU 16470403 3005479 7/30/2009 Korea-KHNP K080553241 9903-470 DRUJ 16487942 3005458 6/30/2009 Almaraz 2009/015 1
9 ER09AT06805MA 9903-337 2301A 16467615 3005458 6/30/2009 Almaraz 2009/015 ER09AT06805MA 9903-303 2301A 16529294 3005621 6/08/2009 KRSKO NEK-10271/309 CORRECTIVE ACTION:
The controls listed in the tables above should be returned to Engine Systems Inc. to have the suspect IC replaced as soon as possible. Contact ESI's Customer Service department with the part number and serial number of the control to be returned.