ML092090316

From kanterella
Jump to navigation Jump to search
ASME Section XI 90-Day Inservice Inspection Summary Report 2009
ML092090316
Person / Time
Site: Palisades Entergy icon.png
Issue date: 07/27/2009
From: Patricia Anderson
Entergy Nuclear Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
IWA-6000
Download: ML092090316 (4)


Text

Entergy Nuclear Operations, Inc.

Palisades Nuclear Plant 27780 Blue Star Memorial Highway Covert, MI 49043 Tel269 764 2000 Paula Anderson Licensing Manager July 27, 2009 ASME,Section XI, Article IWA-6000 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001

SUBJECT:

ASME Section XI 90-Day lnservice Inspection Summary Report 2009 Palisades Nuclear Plant Docket 50-255 License No. DPR-20

Dear Sir or Madam:

Entergy Nuclear Operations, Inc (ENO) is enclosing the Palisades Nuclear Plant (PNP)

Owner's Activity Report in accordance with the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code,Section XI, Article IWA-6000, and ASME Code Case N-532-4. The report contains abstracts of one non-destructive examination indication and two repairlreplacement activities completed at PNP during the twentieth fuel cycle and 2009 refueling outage that were required for continued service. EN0 completed the PNP refueling outage on May 2, 2009.

Summary of Commitments This letter identifies no new commitments and no revisions to existing commitments.

Sincerelv,

/"\\

Attachment:

1. Palisades Nuclear Plant RepairIReplacement Certification Records and Owner's Activity Report cc:

Administrator, Region Ill, USNRC Project Manager, Palisades, USNRC Resident Inspector, Palisades, USNRC

ATTACHMENT 1 PALISADESNUCLEARPLANT OWNER'S ACTlVlTV REPORT i

Two pages follow

FORM OAR-1 OWNER'S ACTIVIW REPORT PLP-1 R2O-OAR-1 Report Number Plant PALISADES NUCLEAR PLANT Unit Uo.

1 Commercial service date 12/31/1971

~ e k e l i n ~

outage no.

1R20 (l

applicaMe)

Current inspection interval 4th.

(ld, 2nd. 3rd. 4th' other)

Current inspection period 1st (1st. 2nd. 3rd)

Edition and Addenda of Section XI applicable to inspection plans 2001 with 2003 Addenda Date and revision of inspection plans 04/06/2009, Revision 18 Edition and Addenda of Section XI applicable to repairlreplacernent activities, if different than the inspection plans NA N-460, N-532-4, N-566-2, N-524, N-629, N-639 with cond~tions in Regulatory Guide 1.147 Revision 15, N-663, Code Cases used:

N595. M-722 in accordance with 10CFR50.55a. N-729-1 in accordance with 10CFR50.55a L

7

.(lfappllceMe)

I certify that (a) the statements made in this report are correct; (b) the examinations and tests meet the Inspection Plan as required by the ASME Code, Sectin XI; and (c) the repairireplacement activiies supporting the completion of 1 R20 (relueling outsge number)

Date CERnRCATE OF ENSERMCE INSPECnON I, the undersigned, holding a valid commission issued by the National Bard of Boiler and Pressure Vessel Inspectors and the State or Province of fY\\ \\CHI 663 n) and employed by t-66 GL084L ~, ~ M & $ o f CT have inspected the items described in this Ownefs Activity Report, and state that, to the best of my knowledge and belief, the Owner has performed all activities represented by this report in accordance with the requirements of Section XI.

By signing this certifiite nelher the inspector nor his employer makes any warranw, expressed or implied, concerning the repair/

replacement activities and evaluation described in this report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any kind arising from or connected with this inspection.

n Commissions _ ~ Z B 131 1 a

.$-& 1 A, N, r ! (

National hnl. Kate, him, and E n d k d n h Date 2 c., J7 )r a 4

TABLE $4 ITEMS WITH F W S OR RELEVANT CONDITIONS THAT REQUIRED EVALUATION FOR CONTINUED SERWCE Examination Category and Item Number C-F-1 I C5.11 TABLE 2 ABSTRACT OF REPAIRIREPLACERBENT ACTlVITDES REQUIRED FOR CONTINUED SERWCE Code Class 3

3 Item Description ESS-24-SIS-SH2-207 Check Valve CK-ES3166 to Tee (Weld overlaid in 1994).

Augmented inspection.

Evaluation Description Subsurface transverse linear indication in overlay material.

0.75" long x 0.055" deep, 0.225" from surface. -

Less than max. allowable a/t.

Acceptable.

Item Description HB-23 2" service water line to air compressor C-2C aftercooler E-18C HBC-42 and HBC-43 3" critical service water lines to and fram Control Room HVAC VC-10 Description of Work Replace carbon steel pipe due to plugging (MIC, sand, and silt).

Work Order 159746 Replace carbon steel with stainless steel pipe due to plugging (MIC, sand, and silt).

Work Order 51 61 261 1 Date Completed 08/2 11'2008 04/03/2009 RepairlReplacement Plan Number PLP00159746R1 PLP51612611