Request for Additional Information Regarding Amendment Application for the Technical Specification on Battery Capacity
ML092040067
Person / Time
Site: Indian Point 
Issue date: 07/23/2009
From: Boska J
Plant Licensing Branch 1
To:
Entergy Nuclear Operations
Boska J, NRR, 301-415-2901
References
TAC ME0985
Download: ML092040067 (3)


Text

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 July 23, xm Vice President, Operations Entergy Nuclear Operations, Inc.

Indian Point Energy Center 450 Broadway, GSB P.O. Box 249 Buchanan, NY 10511-0249

SUBJECT:

INDIAN POINT NUCLEAR GENERATING UNIT NO.2 - REQUEST FOR ADDITIONAL INFORMATION REGARDING AMENDMENT APPLICATION FOR THE TECHNICAL SPECIFICATION ON BATTERY CAPACITY (TAC NO. ME0985)

Dear Sir or Madam:

In a letter dated March 29, 2009, Agencywide Documents Access and Management System (ADAMS) Accession No. ML090980300, Entergy Nuclear Operations, Inc. (Entergy), submitted a license amendment request to revise the acceptance criteria for battery capacity in the Technical Specifications for Indian Point Nuclear Generating Unit No 2 (IP2).

The Nuclear Regulatory Commission staff is reviewing the submittal and has determined that additional information is needed to complete its review. The specific questions are found in the enclosed request for additional information (RAI). The Entergy staff indicated that a response to the RAI would be provided within 60 days of the date of this letter.

Please contact me at (301) 415-2901 if you have any questions on this issue.

Sincerely, g;~a, ~ct Manager Plant Licensing Branch 1-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-247

Enclosure:

RAI cc w/encl: Distribution via Listserv

REQUEST FOR ADDITIONAL INFORMATION REGARDING AMENDMENT APPLICATION FOR THE TECHNICAL SPECIFICATION ON BATTERY CAPACITY ENTERGY NUCLEAR OPERATIONS, INC.

INDIAN POINT NUCLEAR GENERATING UNIT NO.2 DOCKET NO. 50-247 By letter dated March 29, 2009, Agencywide Documents Access and Management System (ADAMS) Accession No. ML090980300, Entergy Nuclear Operations, Inc, (the licensee) requested an amendment to Facility Operating License No. DPR-26 for Indian Point Nuclear Generating Unit NO.2 (IP2), and Appendix A, Technical Specifications (TSs), of the Facility Operating License. The proposed change would revise the battery capacity acceptance criterion specified in TS Surveillance Requirement (SR) 3.8.6.6. Specifically, the proposed change would modify SR 3.8.6.6 by establishing a more restrictive acceptance criterion regarding periodic verification of battery capacity to ensure the IP2 batteries can perform their intended design functions. The Nuclear Regulatory Commission staff is reviewing the submittal and has the following question:

In the license amendment request, the licensee proposed revising the battery capacity acceptance criterion specified in Technical Specification Surveillance Requirement 3.8.6.6.

Please provide the full calculation for the proposed capacity rating, including assumptions and supporting documentation, to show that the 125 Volt direct current batteries will perform their intended design functions.

Enclosure

July 23,2009 Vice President, Operations Entergy Nuclear Operations, Inc.

Indian Point Energy Center 450 Broadway, GSB P.O. Box 249 Buchanan, NY 10511-0249

SUBJECT:

INDIAN POINT NUCLEAR GENERATING UNIT NO.2 - REQUEST FOR ADDITIONAL INFORMATION REGARDING AMENDMENT APPLICATION FOR THE TECHNICAL SPECIFICATION ON BATTERY CAPACITY (TAC NO. ME0985)

Dear Sir or Madam:

In a letter dated March 29, 2009, Agencywide Documents Access and Management System (ADAMS) Accession No. ML090980300, Entergy Nuclear Operations, Inc. (Entergy), submitted a license amendment request to revise the acceptance criteria for battery capacity in the Technical Specifications for Indian Point Nuclear Generating Unit No 2 (IP2).

The Nuclear Regulatory Commission staff is reviewing the submittal and has determined that additional information is needed to complete its review. The specific questions are found in the enclosed request for additional information (RAI). The Entergy staff indicated that a response to the RAI would be provided within 60 days of the date of this letter.

Please contact me at (301) 415-2901 if you have any questions on this issue.

Sincerely, IRA!

John P. Boska, Senior Project Manager Plant Licensing Branch 1-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-247

Enclosure:

RAI cc w/encl: Distribution via Listserv DISTRIBUTION:

PUBLIC RidsNrrDorlLpl1-1 RidsNrrPMJBoska RidsOGCRp LPL1-1 Reading File RidsNrrLASLittle RidsAcrsAcnw MailCTR RidsNrrDeEeeb RidsNrrDorlDpr RidsRgn1 MailCenter MMcConnell ADAMS ACCESSION NO.: ML000ffi)7

  • See memo dated 7/6/09 OFFICE LPL1-1/PM LPL1-1/LA EEEB/BC LPL1-1/BC NAME JBoska SLittie GWilson NSalgado DATE 7/23/09 7/23/09 7/6/09 7/2309 OFFICIAL RECORD COpy