J SOUTHERN CALIFORNIA An EDISON INTERNATIONAL Company A. Edward Scherer Director Nuclear Regulatory Affairs April 28, 2009 U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555
Subject:
Docket No. 50-362 Special Report: Inspection of Steam Generator Tubes, Cycle 15 San Onofre Nuclear Generating Station, Unit 3
Dear Sir or Madam:
San Onofre Nuclear Generating Station Unit 3 entered Mode 4 on November 30, 2008 following the completion of an inspection of steam generator tubes during the Cycle 15 Refueling Outage.
Technical Specification (TS) 5.7.2.c states "A report shall be submitted within 180 days after the initial entry into MODE 4 following completion of an inspection performed in accordance with the Specification 5.5.2.11, Steam Generator (SG) Program."
Accordingly we have attached the required report. The report contains no new commitments.
If you require any additional information, please contact Geoff Cook at (949) 368-9008.
Sincerely, Attachment cc:
E. E. Collins, NRC Regional Administrator, Region IV R. Hall, NRC Project Manager, San Onofre Units 2, and 3 G. G. Warnick, NRC Senior Resident Inspector, San Onofre Units 2 & 3 P.O. Box 128 San Clemente, CA 92674 kAo o
Inspection of Steam Generator Tubes Attachment Special Report Page 1 of 7 SPECIAL REPORT - INSPECTION OF STEAM GENERATOR TUBES Regulatory Reporting Requirements Reporting Requirement 5.7.2.c of Appendix A, Technical Specification to Facility Operating License NPF-1 5 requires a report of steam generator tube inspections to be submitted to the Nuclear Regulatory Commission within 180 days'after the initial entry into MODE 4 following completion of an inspection performed in accordance with the Specification 5.5.2.11, Steam Generator (SG) Program.
The report shall include:
- 1. The scope of inspections performed on each SG,
- 2. Active degradation mechanisms found,
- 3. Nondestructive examination techniques utilized for each degradation mechanism,
- 4. Location, orientation (if linear), and measured sizes (if available) of service induced indications,
- 5. Number of tubes plugged or repaired during the inspection outage for each active degradation mechanism,
- 6. Total number and percentage of tubes plugged or repaired to date,
- 7. The results of condition monitoring, including the results of tube pulls and in-situ testing,
- 8. The effective plugging percentage for all plugging and tube repairs in each SG, and
- 9. Repair method utilized and the number of tubes repaired by each repair method.
Inspection Scope Table 1 summarizes the scope of inspections performed on each SG. Also, when indications by the bobbin probe were non-quantifiable or distorted, the inspection scope included inspection with the Plus Point Probe. There were no significant inspection scope expansions in response to inspection results.
Inspection of Steam Generator Tubes Special Report Attachment Page 2 of 7 TABLE 1 - Scope of Inspections Performed: Unit 3 Cycle 15 (U3C15) Refueling Outage Inspection Scope SG E-088 Tubes/Percent SG E-089 Tubes/Percent Full length of tube with the bobbin probe 8617/100%
8688/100%
(excluding U-bends for Rows 1-3)
Hot leg expansion transition at the top-of-tubesheet with the Plus Point Probe to an extent of 4 inches above to 13 inches below the top-of-tubesheet Cold leg expansion transition at the top-of-tubesheet with the Plus Point Probe to an extent of 2 inches above to 13 inches below the top-of-tubesheet U-bend regions of Rows 1, 2, and 3 with both mid-frequency and high-frequency Plus Point 184/100%
174/100%*
Probes U-bend regions of Rows 4 through 10 with the mid-frequency Plus Point Probe (Note 1)
Plus Point Probe examination of tube support intersections with dents greater than, or equal 328/100%
359/100%
to, 2 volts Plus Point Probe examination of dings greater 307/100%
482/1 00%:
than, or equal to, 4 volts Plus Point Probe examination of all tube support intersections with quantified wear 795/100%
505/100%
indications by the bobbin probe Table 1 Note 1: No indications in a 100% inspection performed in 2004.
Inspection of Steam Generator Tubes Special Report Attachment Page 3 of 7 Results of the Inspection of Tubes Table 2 summarizes the degradation found and number of tubes plugged. The Appendices provide detail.
No degradation was found in:
the cold leg tubesheet region tubing bends dings in tubing freespan A robotic visual inspection of the untubed regions of the top of the tubesheet (i.e., tube bundle periphery and central blowdown lane) was performed on the secondary side of both Steam Generators.
Two previously unretrievable analyzed foreign objects were again observed and re-verified unretrievable in the cold leg periphery of Steam Generator E-088. A single new foreign object was observed and verified lodged/unretrievable in the stay cylinder region of the central blowdown lane on the cold leg side Steam Generator E-089. Eddy current results indicate there has been no tube degradation associated with foreign objects. Preventive plugging was performed in the areaassociated with the new foreign object. All three of these foreign objects have an analysis for acceptability for tube integrity documented in the Corrective Action Process.
TABLE 2 - Degradation Found and Number of Tubes Plugged U3C15 Refueling Outage Steam Generator E-088 E-089 Indication Orientation/Location Tubes with circumferentially oriented ID (initiated on the inside-'
diameter of the tubing wall) indications near the expansion 4
4, transition at the top of the hot leg tubesheet Tubes with circumferentially oriented OD (initiated on the outside-diameter of the tubing wall) indications near the 1
0 expansion transition at the top of the hot leg tubesheet Tubes with axially oriented OD indications near the top of the hot 0
1 leg tubesheet Tubes with axially oriented ID indications in the hot leg tubesheet 4
3 region Tubes with circumferentially oriented ID indications in the hot leg 1
0 tubesheet region Tubes with indications of wear at tube support locations 10 4
Foreign object preventive plugging 0
4 Total 20 j
16
Inspection of Steam Generator Tubes Special Report Attachment Page 4 of 7 Examination Techniques Table 3 provides the list of Nondestructive Examination (NDE) techniques utilized for each degradation mechanism.
TABLE 3 - Nondestructive Examination (NDE) Techniques Utilized for Each Degradation Mechanism Indication Orientation/Location Probe Type for Detection Characterization Circumferentially oriented and axially oriented ID indications near or below the expansion transition Plus Point Plus Point at the top of the hot leg and cold leg tubesheets Axially oriented OD indications and Circumferentially oriented OD indications near the Plus Point Plus Point, top of the hot and cold leg tubesheets Axially oriented OD indications not associated Bobbin Plusý Point with a tube support (freespan)
Axially oriented OD indications at tube support Bobbin Plus Point locations Plus Point (Note 1)
Plus Point Axially oriented ID'indications at tube support Bobbin Plus Point locations Plus Point (Note 1)
Plus Point Indications of wear at tube support locations Bobbin Plus Point Axially oriented ID indications and Circumferentially oriented ID indications in Low-Plus Point Plus Point Row U-bends Circumferentially oriented ID indications at the flanks Plus Point Plus Point of tubing bends Axially oriented OD indications at dings in tubing Bobbin Plus Point freespan (dings <5 volts)
Axially oriented OD indications at dings in tubing Plus Point Plus Point freespan Table 3 Note 1: Plus Point technique is used at dents greater than, or equal to, two volts..
Inspection of Steam Generator Tubes Special Report Attachment Page 5 of 7 Condition Monitoring Condition Monitoring demonstrated that performance criteria in Technical Specifications sections 5.5.2.11.b.1 (structural integrity) and 5.5.2.11.b.2 (accident induced leakage) were met during operation prior to this inspection.
In situ pressure testing was not needed for any eddy current indications. All indications were below screening criteria of the Electric Power Research Institute (EPRI) In Situ Pressure Testing Guidelines.
Table 4 contains all crack-like indications. All tubes with crack-like indications were removed from service. Voltage is the only size-related measurement for numerous indications in Table 4. This is consistent with industry guidance for tube integrity assessment. Industry guidance provides ranges of voltage measurement values for which voltage is the only needed size-related measurement. Table 4 addresses location, orientation and measured sizes of service-induced indications (except wear of tubing at tube supports). The entire population of wear indications at support structures was screened for in situ pressure testing. Appendices 3 and 4 address location and measured sizes of service-induced indications of wear of tubing at tube supports.
No tubes were removed (pulled) for destructive testing during this outage.
TABLE 4 - Measured Sizes of Service-Induced Indications: U3C15 SG Row Col Elev Inch Ind Origin PP Volts Depth PDA FLDA PP Length CA 88 2
40 TSH
-3.87 SAI ID 0.74 61 55.57 0.28 88 8
42 TSH
-2.84 SCI ID 0.55 54 2.71 26 88 11 119 TSH
-0.11 MCI ID 0.46 88 22 34 TSH
-0.11 SCI ID 0.61 68 3.48 26 88 31 55 TSH
+0.10 SCI OD 0.20 88 31 139 TSH
-0.18 MCI ID 0.40 88 36 112 TSH
-5.75 SAI ID 0.36 88 36 112 TSH
-3.68 SAI ID 0.37 88 36 112 TSH
-2.82 SAI ID 0.34 88 36 112 TSH
-2.64 SAI ID 0.50 88 38 112 TSH
-1.31 SAI ID 0.69 51 43.48 0.77 88 44 74 TSH
-7.27 SAI ID 0.54 45 51.57 0.14 88 100 76 TSH
-0.07 SCI ID 0.24 61___
___FID 02 89 27 39 TSH
-0.13 SCI ID 0.27 89 31 125 TSH
+0.02 SCI ID 0.42 89 36 68 TSH
-1.58 MAI ID 0.51 37 30.83 0.17 89 63 89 TSH
-1.33 SAI ID 0.55 61 50.85 0.13 89 63 89 TSH
-1.65 SAI ID 0.39 89 66 76 TSH
+0.70 SAI OD 0.19 89 66 76 TSH
+0.66 SAI OD 0.10 89 101 69 TSH
-0.11 SCI ID 0.93 70 5.19 51 89 103 69 TSH
-0.07 SCI ID 0.68 53 4.25 30 89 103 69 TSH
-0.09 SCI ID 0.69 53 2.58 26 89 113 99 TSH
-7.52 SAI ID 0.51 49 46.50 0.14 89 113 99 TSH
-7.78 SAI ID 0.78 54 45.35 0.17
Inspection of Steam Generator Tubes Attachment Special Report Page 6 of 7 Table 4 Notes:
SG 88 = SG E-088 SG 89 = SG E-089 PP = Plus Point Depth = Percent of Tube Wall Thickness PDA = Percent Degraded Area FLDA = Flaw-Length Degraded Area PP Length (units of measure are inches)
CA = Crack Angle (degrees)
Inspection of Steam Generator Tubes Special Report Attachment Page 7 of 7 Repair Methods, Number of Tubes Repaired and Effective Plugging Percentage All tube plugging was performed using the design, materials, and installation methods of AREVA. A "roll" method was used for all tube plugs. The repair method of sleeving has not been used for tube repair at Unit 3. Ten (1'0) tubes were "stabilized" in the vicinity of the top of the tubesheet using the design, materials, and installation methods of AREVA. The design number of tubes in each SG is 9350 tubes.
TABLE 5 - Number of Tubes Repaired and Effective Plugging Percentage F
SG 88 89
- Tubes Plugged in 3X15 20 16 4
- Tubes Plugged To Date 753 678 4 Effective Plugging Percentage 8.1 7.3 Description of Appendices Appendix 1 -
Steam Generator Reference Information Appendix 2 -
Legend for Appendices 3 and 4 Appendix 3 -
Tube Inspection Summary, Steam Generator E-088 Appendix 4 -
Tube Inspection Summary, Steam Generator E-089
Inspection of Steam Generator Tubes Special Report Appendix 1 Page 1 of 4 Appendix 1 Steam Generator Reference Information
Inspection of Steam Generator Tubes Appendix 1 Special Report Page 2 of 4 Steam Generator CE Model 3410 Tube Support Drawing
\\k/
1 OH
=
100 09H 09 30.75
\\
~30.75" 08H 08C 30.75 07H 07C 38" 06H 06C 36" 05H 05C 35.
04H 04C 38" 03H 03C 02H 02C 35.
01H 01 C 27.25' TSH TSC 23" TEH r--TEC Hot Leg Cold Leg INLET OULET
Inspection of Steam Generator Tubes Special Report Appendix 1 Page 3 of 4 STEAM GENERATOR TUBE SUPPORT INTERSECTIONS ABOVE THE 7 TH (FULL) EGGCRATE SUPPORT SUPPORT INTERSECTIONS ROW STRUCTURES 122-147 08H 09H 10H DBH VH1 VH2 VH3 VSM VC3 VC2 VC1 DBC 10C 09C 08C 120-121*
08H 09H 10H DBH VH1 VH2 VH3 VSM VC3 VC2 VC1 DBC 10C 09C 08C 115-119 08H 09H DBH VH1 VH2 VH3 VSM VC3 VC2 VC1 DBC 09C 08C 86-114 08H 09H DBH VH2 VH3 VSM VC3 VC2 DBC 09C 08C 84-85*
08H 09H DBH VH2 VH3 VSM VC3 VC2 DBC 09C 08C 83 08H DBH VH2 VH3 VSM VC3 VC2 DBC 08C 51-82 08H DBH VH3 VSM VC3 DBC 08C 49-50*
08H DBH VSM DBC 08C 19-48 DBH VSM DBC 1-18 DBH DBC
- Indicates those rows adjacent to scallop bars
Inspection of Steam Generator Tubes Special Report Appendix 1 Page 4 of 4 SOUTHERN CALIFORNIA EDISON, SAN ONOFRE CE MODEL 3410 STEAM GENERATOR I1)
A) 3o 40 so) 0 700 so So IOO 1o 120 130 140 150 1 r01 110
-~ IOOOC.0!0 0Cc o
~
14')
130 120 110 100 00~~
~
1~
0%cC 0
c 0
r g'0
'6o 0
n 0
T0~ ooc~~ccOr0
- ~
0 o~o' ~r-o o'
o'on
~
0 t,0 0
0 0
C 0
o
'ooo ~
Q'.
V" 0-000C 01
'D 0
0 0 0
000oo~o rn-141) 134)
INq)
Ito 0
a 0
co0o 0000 00 00
- 0.
00
'Q
- 00.
'00 0000 0000 000
~o~o~o0~
%~
Ho~o 0
o:ioo2 IMI II0000.
c.IN0000'C~~~c 50 80) 70 0096io 0
60K&
o0 7~0~00 o9o 0
c
- 0.
00 0o
-C o 0
oo' e
0 o~~ IQ 000 1O~~o 0000
~~~~1 00Q.O o~~0 00 0
000 IQ 0C "000"0o o(
8 00 0
0 CcO ooo oo o 0
.o ccno
~
,.or 14 -0H' "0" 0'0' o' i
'rO.0
ý Q c
o'o.-"'
Cc-C0Ccco--.
00c00",,00.C0 c'0,~
~ oooo 0
' c'-'
00%0
,0 00 CC 0
0 0v' 0'0.
o"0"c rý
ýo 0 000C%0000 o
-0l' 00 0~'y.~~c0 Q.00.
c-c' c""-"..-~-~0~~
ol(00 (.i oooo4 oooo 00 o0 Q0 0e
'.,0.
~oooo' a~
~ C
,'..o~"o 0c.-
0 l
o~-.>cr n
~
'0 oon~-a 0
I -
cc 5s 0 0 000 0o0~0 ~o"n~o"o~'
~
9ooCc&PCAoO
- 1) 1)0
'0 Cc r, 0 ~
~0 CoO Cc-'~.0 Cc~0~0~0~Cc o'o C' ~:
00,-.
00
~00.~.0~Cc" 00000A 0Cc0o0o 0 %0-%,..,~~%',,0, 0 c0 fQ 6ý o
o',
o..on 0.o C
0, 1
~
10 OcOO~O~cQ0-C 1,0r~~
0'.~y0~0%~o ooo 9o.s
ýor'~ b
,ooo~OO~O~.o 0
nC'.0 C4~~oO-~.c~co'OCcc,',.Ao I
0,Yo%:%,'9. co~,.o0 i0-
- o 0~~:A 0C0
30 20
- t* *l* * * *q T i* *1* *
- 4*1% @ *
- J%
- * * =* *
- i*
- i*l **
I I
-1(C,~.*0 04*00 0~ *~*4'to*1)*1)*'.i I I *4*)*0~00 0'*0f.
1 >I0~I8
>C~~0~8IXI~A :.-:0.,.- 0..---
+ -'
0$
AL, C, 0 c00,0 O
30 0~0~C<01.0'>'~
Cc "r'
~'
0 C.C0 00 0
'ýOC 0
0 0
0'0.co'0.CCZ
. 0 O~cOCy 00'0 0
0c40
~C, 0 0 O'cOcQ,.OC~
o%~o o',n 7c 0
1' 0
,,,~
,;00
%~
10 31(1 1')
100 06cc.-.,,
,rr 0
110 120 130) 140 150I 1 m,
Inspection of Steam Generator Tubes Special Report Appendix 2 Page 1 of 2 Appendix 2 Legend for Appendices 3 and 4
Inspection of Steam Generator Tubes Special Report Appendix 2 Page 2 of 2 List of Abbreviations and Format Used to Describe Indications from Rotating Probe Testing Abbreviations Explanation of the Abbreviations SCI Single Circumferential Indication MCI Multiple Circumferential Indications SAI Single Axial Indication MAI Multiple Axial Indications MMI Mixed Mode Indications SVI Single Volumetric Indication (i.e. no special axial or circumferential aspect)
MVI Multiple Volumetric Indications (i.e. no special axial or circumferential aspect)
TWID Through Wall Depth (an indication of tubing wear used for volumetric wear indicated with a percent value shown in the next column)
Format In Appendices 3 and 4, a single line of data is associated with each individual rotating probe indication.
Below is a descriptive example of the format.
All "I-Code" indications require a single line entry. The example above displays the form of a Resolution Report line. The VOLTS field contains the Plus Point P-to-P voltage of the largest, most representative response. The DEG field contains the corresponding phase angle. The CHN field contains the reporting channel (i.e. the appropriate 300kHz Plus Point channel). The IND field contains the appropriate 3-letter code (see list above). The %TW field indicates the percent wall loss for wear indications. The LOCATION field contains the abbreviation for the referenced landmark and the distance to the indication. The EXT fields contain the landmarks of the beginning and end of the test extent. The CAL# field identifies the calibration number associated with the acquired data. The LEG field identifies the Hot or Cold Leg as the location of the probe origination. The PROBE field contains the abbreviated identifier of the probe type used for the inspection. For the second column, the terms line and column are used interchangeably for Combustion Engineering designed steam generators.
Inspection of Steam Generator Tubes Special Report Appendix 3 Page 1 of 27 Appendix 3 Tube Inspection Summary Steam Generator E-088
AREVA NP Inc 10/31/08 11:18:03 Customer Name: SONGS Unit 3 Component:
S/G 88 Page 2 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de01_inspectionresults ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 1
113 0.31 116 P2 TWD 21 04H
+0.77 07H TEH 45 HOT 600UL 2
40 0.74 22 2
SAI TSH
-3.87 TSH TSH 69 N
HOT 58OPP 3
21 0.32 82 P3 TWD 15 DBC
-0.89 DBC TEC 56 COLD 600UL 7
1 0.36 71 P3 TWD 18 DBC
+0.94 TEC TEH 35 HOT 60OUL 7
175 0.30 151 P2 TWD 15 01C
-0.97 TEH TEC 51 COLD 600UL 8
42 0.55 26 PI SCI TSH
-2.84 TSH TSH 68 HOT 580PP 8
60 0.19 107 P3 TWD 9 DBH
-0.95 TEC TEH 41 HOT 600UL 8
134 0.37 94 P3 TWD 20 DBC
-0.96 TEH TEC 49 COLD 60OUL 9
65 0.17 110 P3 TWD 8 DBH
+0.77 TEC TEH 41 HOT 600UL 11 119 0.46 17 P1 MCI TSH
-0.11 TSH TSH 63 HOT 58OPP 15 133 0.17 102 P2 TWD 14 07H
-1.01 TEC TEH 9
HOT 600UL 16 2
0.41 68 P2 TWD 17 05H
-0.59 TEC TEH 32 HOT 600UL 17 67 0.29 15 P3 TWD 16 DBH
+1.50 TEH TEC 26 COLD 600UL 17 109 0.25
.65 P3 TWD 15 DBC
-2.00 TEH TEC
- 45.
COLD 600UL 17 173 0.51 115 P2 TWD 21 01C
-0.87 TEC TEH 42 HOT 60OUL 18 132 0.23 117 P3 TWD 17 DBH
+1.99 TEC TEH 9
HOT 600UL 19 57 0.30 91 P2 TWD 16 07H
-0.97 TEH TEC 24 COLD 600UL 21 145 0.20 154 P2 TWD 16 VSM
-1.00 TEC TEH 23 HOT 600UL 22 18 0.24 44 P2 TWD 12 VSM
-0.90 TEC TEH 26 HOT 600UL 22 24 0.14 118 P3 TWD 8 DBH
+1.71 TEC TEH 21 HOT 600UL 22 34 0.61 29 P1 SCI TSH
-0.11 TSH TSH 65 HOT 58OPP 23 13 0.12 114 P2 TWD 6
VSM
-0.95 TEC TEH 27 HOT 600UL 23 109 0.47 115 P2 TWD 20 07H
+0.04 TEH TEC 44 COLD 60OUL 23 123 0.29 108 P2 TWD 15 07H
+0.36 TEH TEC 41 COLD 600UL 23 125 0.32 35 P2 TWD 17 07H
-0.38 TEH TEC 38 COLD 600UL 23 127 0.24 130 P2 TWD 14 06H
+0.35 TEH TEC 38 COLD 600UL 23 145 0.29 89 P2 TWD 16 VSM
-1.05 TEC TEH 22 HOT 600UL 23 153 0.28 87 P2 TWD 20 VSM
-0.91 TEC TEH 31 HOT 600UL 24 20 0.36 95 P2 TWD 17 VSM
-0.78 TEC TEH 24 HOT I 600UL 24 54 0.31 118 P2 TWD 16 07H
+0.84 TEH TEC 23 COLD 600UL 24 56 0.34 140 P2 TWD 17 07H
-1.18 TEH TEC 24 COLD 600UL 24 108 0.63 119 P2 TWD 24 VSM
-0.96 TEH TEC 44 COLD 600UL 24 126.
0.27 71 P2 TWD 16 07H
+0.75 TEH TEC 39 COLD 600UL 25 39 0.30 83 P2 TWD 15 VSM
+1.18 TEC TEH 13 HOT 600UL 25 167 0.26 50 P2 TWD 10 02H
+0.23 TEC TEH 38 HOT 600UL 27 67 0.37 137 P2 TWD 18 VSM
+1.02 TEH TEC 25 COLD 600UL 27 121 0.26 125 P2 TWD 14 07H
+0.11 TEH TEC 41 COLD 600UL 28 54 0.24 94 P2 TWD 12 06H
+0.15 TEH TEC 23 COLD 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component: S/G 88 Page 3 of 27 (de0l)
Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de01_inspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 28 172 0.36 57 P2 TWD 24 01C
+0.12 TEC TEH 43 HOT 600UL 29 13 0.34 82 P3 TWD 14 DBH
+0.98 TEC TEH 26 HOT 600UL 0.13 66 P3 TWD 6
DBH
-2.01 TEC TEH 26 HOT 600UL 29 107 0.27 63 P3 TWD 15 DBH
-1.53 TEH TEC 45 COLD 600UL 30 172 0.27 33 P2 TWD 13 06H
+0.91 TEC TEH 42 HOT 60OUL 31 39 0.21 89 P2 TWD 10 07H
+0.57 TEC TEH 12 HOT 60OUL 31 55 0.53 33 P2 TWD 23, 02H
-1.06 TEH TEC 23 COLD 600UL 0.20 121 Pl SCI TSH
+0.10 TSH TSH 112 HOT 580PP 31 139 0.40
'21 Pl MCI TSH
-0.18 TSH TSH 78 HOT 580PP 31 161 0.12 120 P3 TWD 9
DBH
+1.61 TEC TEH 37 HOT 600UL 31 167 0.18 101 P3 TWD 14 DBH
+0.62 TEC TEH 39 HOT 600UL 32 42 0.35 135 P2 TWD 15 07H
+0.72 TEC TEN 10 HOT 600UL 32 60 0.32 148 P2 TWD 16 VSM
-1.10 TEH TEC 25 COLD 600UL 32 106 0.32 108 P2 TWD 16 04C
+0.88 TEH TEC 47 COLD 600UL 32 124 0.54 134 P2 TWD 24 VSM
-0.79 TEH TEC 41 COLD 600UL 32 168 0.21 85 P3 TWD 8 DBH
+0.18 TEC TEH 38 HOT 60OUL 33 43 0.18 67 P2 TWD 9 07H
+0.64 TEC TEH 10 HOT I 600UL 34 56 0.36 160 P2 TWD 17 VSM
-0.74 TEH TEC 23 COLD 600UL 34 112 0.29 57 P2 TWD 14 VSM
+0.74 TEH TEC 44 COLD 600UL 34 128 0.20 142 P2 TWD 12 VSM
+0.78 TEH TEC 38 COLD 600UL 34 172 0.38 66 P2 TWO 17 VSM
+0.87 TEC TEH 42 HOT 600UL 35 7
0.31 77 P2 TWD 16 VSM
-0.89 TEC TEH 33 HOT 600UL 35 19 0.22 134 P2 TWD 11 VSM
-0.89 TEC TEH 25 HOT 600UL 35 47 0.31 156 P2 TWD 16 VSM
+0 82 TEH TEC 21 COLD 600UL 35 51 0.25 66 P2 TWD 13 07H
-0.60 TEH TEC 22 COLD 600UL 35 53 0.22 140 P2 TWD 11 VSM
-0.77 TEH TEC 22 COLD 600UL 35 107 0.25 47 P2 TWD 14 VSM
-0.91 TEH TEC 46 COLD 600UL 0.27 159 P2 TWD 15 VSM
+0.14 TEH TEC 46 COLD 600UL 35 121 0.32 129 P2 TWD 17 05H
+0.79 TEH TEC 41 COLD 600UL 35 125 0.30 124 P2 TWD 17 VSM
+0.80 TEH TEC 38 COLD 600UL 0.19 85 P2 TWD 11 VSM
-0.74 TEH TEC 38 COLD 600UL 36 46 0.32 137 P2 TWD 16 VSM
+0.71 TEC TEH 6
HOT 600UL 0.30 93 P2 TWD 15 VSM
-0.77 TEC TEH 6
HOT 60OUL 0.20 129 P2 TWD 10 07H
-0.34 TEC TEH 6
HOT 600UL 36 50 0.31 63 P2 TWD 16 07H
+0.44 TEH TEC 22 COLD 600UL 0.27 134 P2 TWD 15 07H
-0.25 TEH TEC 22 COLD 600UL 0.27 157 P2 TWD 15 07H
+0.99 TEH TEC 22 COLD 600UL 36 52 0.32 39 P2 TWD 16 06H
+/-0.43>,
TEH TEC 21 COLD 600UL 36 108 0.54 135 P2 TWD 22 VSM
-0.80 TEN TEC 44 COLD 600UL 0.51 135 P2 TWD 21-VSM
-0.19 TEH TEC 44 COLD 600UL 36
- 112, 0.36 24 2
SAI TSH
-5.75 TSH TSH 67 HOT 58OPP 0.37 23 2
SAI TSH
-3.68 TSH TSH 67 HOT 58OPP 0.34 28 2
SAI TSH
-2.82 TSH TSH 67 HOT 58OPP 0.50 16 2
SAI TSH
-2.64 TSH TSH 67 HOT 58OPP
AREVA NP Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component: S/G 88 Page 4 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MNI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de0l inspectionresults.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.70 136 P2 TWD 28 VSM
+0.76 TEH TEC 45 COLD 600UL 0.25 127 P2 TWD 13 VSM
-0.88 TEH TEC 45 COLD.
600UL 36 162 0.31 122 P2 TWD 16 VSM
+0.84 TEC TEN 36 HOT 60OUL 37 43 0.53 128 P2 TWD 21 VSM
+0.79 TEC TEH 10
- HOT 600UL 37 51 0.32 37 P2 TWD 17 07H
+0.44 TEH TEC 21 COLD 600UL 37 69 0.28 96 P2 TWD 16 VSM
-0.91 TEH TEC 26 COLD 600UL 0.24 145 P2 TWD 15 VSM
+0.88 TEH TEC 26 COLD 600UL 37 105 0.49 38 P3 TWD 22 DBH
.+1.95 TEH TEC 46 COLD 600UL 37 127 0.27 77 P2 TWD 16 VSM
-0.92 TEH TEC 39 COLD 60OUL 0.12 95 P2 TWD 7 VSM
+0.82 TEH TEC 39 COLD 600UL 0.27 67 P2 TWD 16 VSM
+0.19 TEH TEC 39 COLD 600UL 37 147 0.20 152 P2 TWD 15 VSM
+0.75 TEC TEH 29 HOT 600UL 38 104 0.34 76 P3 TWD 15 DBH
-1.61 TEH TEC 39 COLD 606UL*
38 106 0.17 145 P2 TWD
- 10. VSM
+0.08 TEH TEC 46 COLD 600UL 0.24 15 P2 TWD 14 VSM
+0.72 TEH TEC 46 COLD 600UL 38 112 0.69 18 2
SAI TSH
-1.31 TSH TSH 66 HOT 580PP 38 170 0.16 49 P2 TWD 12 01H
-0.12 TEC TEH 39 HOT 600UL 39 41 0.32 123 P2 TWD 16 VSM
+0.88 TEC TEH 11 HOT 600UL 0.31 129 P2 TWD 16 VSM
-0.77 TEC TEH 11 HOT 600UL 39 55 0.24 130 P2 TWD 13 VSM
-0.76 TEH TEC 23 COLD 600UL 39 65 0.53 67 P2 TWD 23 VSM
+0.79 TEH TEC 25 COLD 600UL 39 67 0.51 102 P2 TWD 22 VSM
-0.86 TEH TEC 25 COLD 600UL 0.31 148 P2 TWD 15 VSM
+0.85 TEH TEC 25 COLD 600UL 40 38 0.42 139 P2 TWD 18 VSM
+0.85
- TEC TEH 12 HOT 600UL 0.21 160 P2 TWD 10 VSM
-0.82 TEC TEH 12 HOT 600UL 40 54 0.28 69 P2 TWD 15 02H
-1.22 TEH TEC 23 COLD*
600UL 40 62 0.53 115 P2 TWD 23 VSM
+0.81 TEH TEC 25 COLD 600UL 40 104 0.23 125 P2 TWD 14 VSM
-0.91 TEH TEC 38 COLD 600UL 0.12 136 P2 TWD 8 VSM
-0.06 TEH TEC 38 COLD 600UL 0.61 154 P2 TWD 27 VSM
+0..78 TEH TEC 38 COLD 600UL 40 122 0.22 90 P2 TWD 12 07H
-0.40 TEH TEC 41 COLD 600UL 41 53 0.27 47 P3 TWD 14 DBH
+1.84 TEH TEC 21 COLD 600UL 41 73 0.31 113 P3 TWD 14 DBH
-1.64 TEH TEC 27 COLD 600UL 0.55 168 P3 TWD 22 DBH
+2.10 TEH TEC 27 COLD 600UL 41 103 0.35 89 P3 TWD 17 DBH
-1.49 TEH TEC 38 COLD 600UL 0.51 105 P3 TWD 23. DBH
+2.03 TEH TEC 38 COLD 60OUL 42 36 0.33 115 P2 TWD 15.03C
+0.98 TEC TEH 12 HOT 600UL 43 5
0.57 115 P2 TWD 21 04C
-0.10 TEC TEH 32 HOT 600UL 43 9
0.19 139 P2 TWD 11 VSM
-0.82 TEC TEH 33 HOT 600UL 43 13 0.38.
139 P2 TWD 18 VSM
-0.78 TEC TEH 27 HOT 600UL 43 21 0.35 116 P2 TWD 17 VSM
+0.71 TEC TEH 25 HOT 600UL 43 53 0.20 155 P2 TWD 11 VSM
-0.85 TEH TEC 22 COLD 600UL 0.32 136 P2 TWD 16 VSM
+0.06 TEN TEC 22 COLD 600UL 0.55 129 P2 TWD 24 VSM
+0.89 TEH TEC 22 COLD 600UL 43....115...
0.56
.....143 P2...TWD....24...VEN.
+0.97.....TEN TEC....43..
COLD............
43 115 0.56 143 P2 TWD 24 VSM
+0.97 TEH TEC 43 COLD 600UL
AREVA NP.Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component:
S/G 88 Page 5 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: deOlinspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE
=
=
- ==
===================--------------
==
:
============ý 43 123 0.33 98 P2 TWD 17 07H
-0.23 TEH TEC 41 COLD 600UL 43 149 0.34 49 P2 TWD 16 VSM
+0.86 TEC TEH 28 HOT 600UL 44 74 0.16 144 P3 TWD 8 DBC
+1.70 TEH TEC 27 COLD 600UL 0.32 50 P3 TWD 15 DBH
-1.77 TEH TEC 27 COLD 600UL 0.54 15 2
SAI TSH
-7.27 TSH TSH 96 HOT 580PP 44 102 0.32 120 P3 TWD 16 DBC
+1.79 TEH TEC 38 COLD 600UL 44 108 0.85 126 P2 TWD 29 VSM
-0.78 TEH TEC 44 COLD.
600UL 0.75 109 P2 TWD 27 VSM
-0.21 TEH TEC 44 COLD 600UL 44 110 0.58 110 P2 TWD 23 VSM
+0.90 TEH TEC 44 COLD 600UL 0.22 120 P3 TWD 11 DBC
+1.58 TEH TEC 44 COLD 600UL 0.31 113 P2 TWD 14 VSM
-0.27 TEH TEC 44 COLD 600UL 44 154 0.50 i03 P2 TWD 19 VSM
+0.71 TEC TEH 30 HOT 600UL 45 75 0.31 150 P3 TWD 15 DBC
-1.82 TEH TEC 27 COLD
, 60OUL 45 101 0.90 30 P3 TWD 31 DBH
+1.62 TEH TEC 19 COLD 600UL 0.17 92 P3 TWD 9 DBH
-1.64 TEH TEC 19 COLD 600UL 0.29 64 P3 TWD 15 DBC
-1.68 TEH TEC 19 COLD 600UL 45 169 0.24 73 P2 TWD 10 02C
-0.85 TEC TEH 38 HOT 600UL 46 76 0.48 65 P3 TWD 25 DBH
-1.88, TEH TEC 14 COLD 600UL 0.13 33 P3 TWD 10 DBC
-2.08 TEN TEC 14 COLD 600UL 46 118 0.15 96 P2 TWD 5 07H
+0.39 TEH TEC 43 COLD 600UL 47 57 0.18 151 P2 TWD 9 06H
+0.86 TEH TEC 23 COLD 600UL 47 73 0.49 121 P3 TWD 20 DBC
-1.99 TEH TEC 27 COLD 600UL 47 75 0.27 88 P3 TWD 13 DBC
-1.65 TEH TEC 27 COLD 600UL 47 77 0.45 101 P3 TWD 25 DBC
-1.93 TEH TEC 14 COLD 60OUL 47 109 0.34 59 P2 TWD 16 VSM
-0.13 TEH TEC 44 COLD 600UL 47 111 0.29 159 P2 TWD 14 VSM
-0.80 TEH TEC 44 COLD 600UL 0.48 38 P2 TWD 20 VSM
+0.00 TEH TEC 44 COLD 600UL 47 125 0.28' 161 P2 TWD 16 VSM
+0.74 TEH TEC 38 COLD 600UL 47 137 0.27 75 P2 TWD 19 VSM
+0.11 TEC TEH 19 HOT 600UL 48 42 0.21 142 P2 TWD 10 07H
-0.70 TEC TEH 10 HOT 600UL 48 58 0.22 59 P3 TWD 11 DBH
-1.53 TEH TEC 23 COLD 600UL 48 68 0.51 142 P2 TWD 22 VSM
+0.81 TEH TEC 25 COLD 600UL 0.32 91 P2 TWD 16 VSM
-0.89 TEH TEC 25 COLD 600UL 48 102 0.41 81 P3 TWD 18 DBH
-1.76 TEH TEC 39 COLD 600UL 48 104 0.49 139 P2 TWD 23 VSM
+0.94 TEH TEC 46 COLD 600UL 48 106 0.33 82 P2 TWD 18 VSM
-0.73 TEH TEC 46 COLD 600UL 0.48 66 P2 TWD 23 VSM
-0.06 TEH TEC 46 COLD 600UL 0.48 92 P2 TWD 23 VSM
+0.86 TEH TEC 46 COLD 600UL 48 108 0.51 117 P2 TWD 21 VSM
-0.27 TEH TEC 44 COLD 600UL 48 126 0.53 130 P2 TWD 26 VSM
+0.80 TEH TEC 39 COLD 600UL 48 152 0.60 103 P2 TWD 21 VSM
-0.66 TEC TEH 30 HOT 600UL 48 154 0.44 126 P2 TWD 17 VSM
+0.84 TEC TEH 30 HOT 600UL 0.1.9 38 P2 TWD 8 VSM
-0.12 TEC TEH 30 HOT 600UL 49 7
0.25 100 P2 TWD 11 06H
-1.19 TEC TEH 32 HOT 600UL 49 41 0.70 116 P2 TWD 25 08H
+1.53 TEC TEH 10 HOT 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component: S/G 88 Page 6 of 27 (de01)
Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: deOl1inspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 49 43 0.30 101 P2 TWD 14 08H
+1.89 TEC TEH 10 HOT 600UL 0.45 94 P2 TWD 19 08H
-1.65 TEC TEH 10 HOT 600UL 49 49 0.18 137 P2 TWD 10 08H
-1.27 TEH TEC 21 COLD 600UL 0.31 124 P2 TWD 16 08H
+1.52 TEH TEC 21 COLD 600UL 49 75 0.25 5
P3 TWD 11 DBC
-1.41 TEH TEC 27 COLD 600UL 49 77 0.23 59 P2 TWD 11 06H
-0.90 TEH TEC 13 COLD 600UL 49 101, 0.54 74 P3 TWD 26 DBH
-1.66 TEH TEC 20 COLD 600UL 49 115 0.54 131 P2 TWD 23 08H
+1.48 TEH TEC 42 COLD 600UL 49 125 0.32 123 P2 TWD 16 08H
-1.27 TEH TEC 41 COLD 600UL 0.41 74 P2 TWD 20 08H
+1.59 TEH TEC 41 COLD 600UL 49 131 0.25 33 P3 TWD 10 DBH
-0.99 TEC TEH 8
HOT 600UL 49 169 0.48 74 P2 TWD 18 01C'
-0.85 TEC TEH 38 HOT 600UL 50 48 0.17 63 P2 TWD 10 08H
+1.45 TEH TEC 22 COLD 600UL 51 17 0.22 157 P2 TWD 11 VH3
+0.64 TEC TEH 27 HOT 600UL 51 79 0.25 111 P3 TWD 16 DBC
-1.79 TEH TEC 14 COLD 600UL 51 83 0.41 87 P3 TWD 19 DBH
-1.56 TEH TEC 19 COLD 600UL 0.81 86 P3 TWD 29 DBC
-1.68 TEH TEC 19 COLD 600UL 51 99 0.42 14 P3 TWD 23 DBH
+1.83 TEH TEC 20 COLD 600UL 0.41 46 P3 TWD 23 DBH
-2.00 TEH TEC 20 COLD 600UL 52 168 0.26 118 P2 TWD 10 01H
+0.06 TEC TEH 38 HOT 600UL 0.49 126 P2 TWD 18 01C
-0.16 TEC TEH 38 NOT 600UL 53 35 0.57 108 P2 TWD 23 VH3
+0.68 TEC TEH 12 HOT 600UL 53 37 0.44 151 P2 TWD 20 VH3
+0269 TEC TEH 13 HOT 600UL 53 81 0.32 92 P3 TWD.18 DBH
+1.69 TEH TEC 16 COLD 600UL 0.31 135 P3 TWD 18 DBC
+2.00 TEH TEC 16 COLD 600UL 53 87 0.30 134 P3 TWD 15 DBH
-1.68 TEH TEC 19 COLD 600UL 53 95 0.36 53 P3 TWD 21 DBC
-1.62 TEH TEC 20 COLD 600UL 53 145 0.19 108 P2 TWD 16 VH3
+0.49 TEC TEH 23 NOT 60OUL 54 84 0.28, 97 P3 TWD 14 DBC
-1.68 TEH TEC 19 COLD 600UL 54 88 0.37 34 P3 TWD 21 DBH
-1.64 TEH TEC 20 COLD 600UL 0-38 8
P3 TWD 21 DBH
+1.83 TEH TEC 20 COLD 600UL 55 81 0.40 106 P3 TWD 18 DBH
+1.76 TEH TEC 15 COLD 600UL 55 99 0.43 72 P3 TWD 23 DBH
-1.68 TEH TEC 20 COLD 600UL 56 38 0.58 126 P2 TWD 23 VH3
-0.89 TEC TEN 12 HOT 60OUL 56 44 0.48 52 P2 TWD 20 08H
+0.83 TEC TEH 10 NOT 600UL 56 46 0.53 125 P2 TWD 23 08H
+0.56 TEC TEH 6
HOT 60OUL 56 96 0.34 41 P3 TWD 20 DBC
+1.54 TEH TEC 20 COLD 600UL 56 98 0.71 124 P3 TWD 27 DBH
-1.60 TEH TEC 19 COLD 600UL 56 166 0.53 122 P2 TWD 20 01C
-0.83 TEC TEN 38 HOT 600UL 57 79 0.39 102 P2 TWD 19 08H
-0.98 TEH TEC 13 COLD 600UL 0.33 98 P3 TWD 15 DBC
-1.85 TEH TEC 13 COLD 600UL 57 83 0.25 70 P3 TWD 13 DBC
-1.89 TEH TEC 19 COLD 600UL 0.17 40 P3 TWD 9
DBC
+1.56 TEH TEC 19 COLD 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component: S/G 88 Page 7 of 27 (de0l)
Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de0l inspectionresults.qry ROW' COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 57 85 0.45 39 P3 TWD 20 DBH
+1.68 TEH TEC 19 COLD 60OUL 57 91 0.73 127 P3 TWD 27 DBH
-1.43 TEH TEC 19 COLD 600UL 0.53 45 P3 TWD 23 DBC
+1.68 TEH TEC 19 COLD 600UL 0.37 148 P3 TWD 17 DBC
-1.85 TEH TEC 19 COLD 60OUL 57 167 0.26 144 P2 TWD 10 0 1H
+0.10 TEC TEH 38 HOT 600UL 58 44
- 0.34 94 P2 TWD 17 08H
-0.47 TEC TEH 11 HOT 60OUL 58 50 0.19 81 P2 TWD 10 VH3
+0.97 TEH TEC 22 COLD 600UL 58 88 0.28 30 P3 TWO 17 DON
-1.49 TEN TEC 20 COLD 600UL 58 90 0.36 68 P3 TWO 17 DON
-1.49 TEN TEC 19 COLD 600UL 0.24 19 P3 TWO 12 DBC
+1.75 TEN TEC 19 COLD 600UL 58 92 0.29 44 P3 TWD 17 DBH
-1.71 TEH TEC 20 COLD 600UL 58 96 0.15 77 P3 TWD 8 DBH
-1.55 TEH TEC 19 COLD 60OUL 0.21 44 P3 TWD 11 DBC
+1.47 TEH TEC 19 COLD 600UL 58 98 0.23 23 P3 TWD 15 DBH
-1.66 TEH TEC 20 COLD 60OUL 59 93 0.52 80< P3 TWD 22 DBH
-1.55 TEH TEC 19 COLD 600UL 59 99 0.22 130 P3 TWO 12 DON
-1.43 TEN TEC 19 COLD 600UL 59 123 0.24 62 P2 TWO 13 07N
-0.38 TEN TEC 41 COLD 600UL 60 30*
0.60 i11 P2 TWO 23 VN3
-0.82 TEC TEN 16 NOT 600DL 60 84 0.31 89 P3 TWD 14 DBO
+1.39 TEH TEC 19 COLD 600UL 60 92 0.37 14 P3 TWD 18 DBH
+1.94 TEH TEC 19 COLD 600UL 60 98 0.38 14 P3 TWD 18 DBH
+1.91 TEH TEC 19 COLD 600UL 60 128 0.32 51 P2 TWD 18 08H
+0.32 TEH TEC 39 COLD 600UL 61 47 0.24 135 P2 TWD 13 08H
+0.57 TEH TEC 21 COLD 600UL 0.18 98 P2 TWO 10 03C
-1.03 TEN TEC 21 COLD 600UL 61 77 0.35 41 P2 TWO 18 08-
-0.92 TEN TEC 37 COLD 600UL 61 79 0.61 86 P2 TWD 25 VSM
+0.78 TEN TEC 13 COLD 600UL 61 81 0.29 11 P3 TWD 17 DBH
+1.36 TEH TEC 16 COLD 600UL 61 83 0.48 126 P3 TWD 23 DBC
+1.58 TEH TEC 18 COLD 600UL 61 85 0.56 28 P3 TWD 23 DBH
+1.72 TEH TEC 19 COLD 600UL 61 129 0.43 92 P2 TWD 21 08H
+0.47 TEH TEC 38 COLD 600UL 61 141 0.36
- 89 P2 TWO 19 VSN
-0.95 TEC TEN 22 NOT 600UL 62 82 0.46 119 P3 TWD 22 DOH
-1.53 TEH TEC 18 COLD 600UL 62 88 0.26 89 P3 TWD 1O DON
-1.20 TEH TEC 18 COLD 600UL 62 166 0.21 64 P2 TWD 15 01H
+0.16 TEC TEN 39 NOT 600UL 63 3S 0.2S 29 P3 TWO 13 DON
-1.66 TEC TEN 13 NOT 600UL 63 83 0.37 89 P3 TWD 17 DOC
+1.60 TEH TEC 17 COLD 600UL 63 89 0.40 104 P3 TWD 19 DBC
+1.63 TEH TEC 19 COLD 600UL 63 91 0.27 1S4 P3 TWD 14 DBC
-1.70 TEH TEC 17 COLD 600UL 64 12 0.23 85 P2 TWD 12 08C
+0.87 TEH TEC 21 COLD 600UL 64 84 0.26 45 P2 TWD 14 08H
-0.35 TEH TEC 23 COLD 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component:
S/G 88 Page 8 of 27 (de0l)
Post-U3C15 Inspection Results MAI,, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: deOlinspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 64 78 0.27 106 P2 TWD 13 08H
+0.02 TEH TEC 13 COLD 600UL 64 128 0.30 128 P2 TWD 17 08H
+0.40 TEH TEC 39 COLD 600UL 64 14.8 0.38 89 P2 TWD 18 VH3
-0.87 TEC TEH 28 HOT 60OUL 65 77 0.24 45 P3 TWD 12 DBH
-0.61 TEH TEC 37 COLD 600UL 65 85 0.36 17 P3 TWD 18 DBH
+1.71 TEH TEC 18 COLD 600UL 65 91 0.17 37 P3 TWD 9 DBC
-1.69 TEH TEC 18 COLD 600UL 65 165 0.54 121 P2 TWD 20 01C
-0.81 TEC TEH 38 HOT 600UL 66 14 0.25 109 P2 TWD 13 04C
-0.16 TEC TEH 27 HOT 60OUL 66 40 0.17 100 P3 TWD 9 DBC
+1.97 TEC TEH 11 HOT 600UL 66 74 0.28 118 P3 TWD 18 DBH
+1.87 TEH TEC 28 COLD 600UL 66 78 0.27 82 P2 TWD 15 02H
-0.27 TEH TEC 14 COLD 600UL 66 80 0.17 145 P3 TWD 12 DBH
-2.03 TEH TEC 14
- COLD
- .600UL 67 45 0.16 118 P2 TWD 9 08H
+0.34 TEC TEH 11 HOT 600UL 67 63 0.21 47 P2 TWD 11 VSM
-0.89 TEH TEC 25 COLD
- 600UL 67 143 0.48 98 P2 TWD 23 VH3
+0.78 TEC TEH 22 HOT 600UL 0.31 33 P2 TWD 17 VC3
+0.84 TEC TEH 22 HOT 600UL 68 56 0.23 101 P2 TWD 12 05C
-0.90 TEH TEC 23 COLD 600UL 68 68 0.27 92 P2 TWD 14 VC3
+0.28 TEH TEC 25 COLD 600UL 68 88
.0.34 142 P3 TWD 16 DBH
-1.61 TEH TEC 17 COLD 600UL 69 59 0.12 48 P3 TWD 7 DBC
+1.82 TEH TEC 24 COLD 600UL 69 77 0.39 71 P3 TWD 18 DBH
+1.99 TEH TEC 37 COLD 600UL 70 50 0.29 117 P2 TWD 15 08H
-1.08 TEH TEC 22 COLD 600UL 70 114 0.27 135 P2 TWD 12 07H
-0.79 TEH TEC 43 COLD 600UL 70 138 0.29 119 P2 TWD 20 VC3
-0.93 TEC TEH 19 HOT 60OUL 70 162 0.22 159 P2 TWD 17 08H
+0.80 TEC TEH 37 HOT 600UL 70 164 0.41 49 P2 TWD 16 08H
+1.03 TEC TEH 38 HOT 60OUL 71 23 0.20 42 P3 TWD 11 DBH
+1.68 TEC TEH 25 HOT 600UL 71 89 0.51 52 P3 TWD 22 DBC
-1.70 1
TEH TEC 17 COLD 600UL 72 14 0.39 88 P3 TWD 16 DBC
-1.65 TEC TEH 26 HOT 600UL 72 34 0.50 122 P2 TWD 20 VSM
-0.89 TEC TEH 12 HOT 60OUL 72 36 0.17 84 P2 TWD 8 VH3
-0.29 TEC TEH 12 HOT 600UL 72 42 0.41 140 P2 TWD 18 VH3
+0.64 TEC TEH 10 HOT 600UL 0.35 101 P2 TWD 15 VH3
+0.06 TEC TEH 10 HOT 600UL 0.32 100 P2 TWD 14 VH3
-0.49 TEC TEH 10 HOT 600UL 0.23 157 P2 TWD 11 VSM
-0.87 TEC TEH 10 HOT 600UL 72 44 0.29 60 P3 TWD 12 DBC
+2.11 TEC TEH 10 HOT 600UL 72 58 0.35 124 P2 TWD 17 08H
+0.66 TEH TEC 23 COLD 600UL 72 90 0.24 103 P3 TWD 12 DBC
+1.50 TEH TEC 17 COLD 600UL 72 148 0.25 106 P2 TWD 13 VC3
+0.93 TEC TEH 28 HOT 60OUL 0.23 27 P2 TWD 11 VH3
+0.93 TEC TEH 28 HOT 600UL 73 31 0.39 75 P2 TWD 18 VH3
+0.88 TEC TEH 17 HOT 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component: S/G 88 Page 9 of 27 (de0l)
Post-U3Cl5 Inspection Results
- MAI, MCI, MI, NMVI,
- SAI, SCI,
- SVI, TWD QUERY: de0l inspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 73 33 0.27 152 P2 TWD 12 VH3
+0.74 TEC TEH 16 HOT 606UL 0.45 97 P3 TWD 18 DBH
+1.96 TEC TEH 16 HOT 600UL 73 39 0.28 146 P2 TWD 14 VC3
+0.88 TEC TEH 13 HOT 600UL 73 45 0.46 78 P2 TWD 19 VC3
+0.19 TEC TEH 10 HOT 60OUL 73 51 0.35 121 P2 TWD 18 VSM
+0.74 TEH TEC 21 COLD 60OUL 0.31 144 P2 TWD 16 VC3
+0.76 TEH TEC 21 COLD 60OUL 0.40 100 P2 TWD 19 VC3
+0.21 TEH TEC 21 COLD 600UL 0.21 29 P2 TWD 21 VSM
+0.19 TEH TEC 21 COLD 600UL 0.27 126 P2 TWD 14 VSM
-0.88 TEH TEC 21 COLD 600UL 0.32 146 P2 TWD 16 VH3
+0.74 TEHTEC 21 COLD 600UL 0.27 91 P2 TWD 14 VH3
+0.21 TEH TEC 21 COLD 600UL 73 53 0.23 136 P2 TWD 12 VH3
-0.87 TEH TEC 21 COLD 600UL 0:37 123 P2 TWD 18 VC3
+0.21 TEH TEC 21 COLD 60OUL 0.50 124 P2 TWD 23 VC3
+0.79 TEH TEC 21 COLD 600UL 0.33 66 P2 TWD 17 VH3
-0.06 TEH TEC 21 COLD 60OUL 73 55 0.21 154 P2 TWD 11 VH3
+0.88 TEH TEC 24 COLD 60OUL 73 61 0.17 127 P2 TWD 9 VH3
-0.85 TEH TEC 25 COLD 60OUL 0.46 119 P2 TWD 21 VSM
+0.81 TEH TEC 25 COLD 600UL 0.34 157 P2 TWD 16 VC3
-0.81 TEH TEC 25 COLD 600UL 0.18 105 P2 TWD 10 VC3
+0.21 TEH TEC 25 COLD 600UL 73 65 0.34 111 P2 TWD 19 VH3
-0.76 TEH TEC 26 COLD 600UL 0.20 158 P2 TWD 12 VH3
+0.87 TEH TEC 26 COLD 600UL 0.18 53 P2 TWD 11 VSM
-0.97 TEH TEC 26 COLD 600UL 73 73 0.29 38 P2 TWD 14 VSM
+0.86 TEH TEC 28 COLD 600UL 0.36 144 P2 TWD 17 VC3
-0.72 TEH TEC 28 COLD 600UL 73 85 0.18 107 P3 TWD 11 DBC
+2.02 TEH TEC 18 COLD 60OUL 73 89 0.19 156 P3 TWD 10 DBH
+1.56 TEH TEC 18 COLD 600UL 73 107 0.27 126 P2 TWD 14 VH3
-0.84 TEH TEC 47 COLD 600UL 0.77 124 P2 TWD 29 VH3
+0.76 TEH TEC 47 COLD 600UL 73 111 0.24 134 P2 TWD 12 VSM
-0.66 TEH TEC 44 COLD 600UL
'0.39 148 P2 TWD 17 VSM
+0.78 TEH TEC 44 COLD 600UL 73 113 0.37 73 P2 TWD 17 02H
-1.22 TEH TEC 42 COLD 600UL 74 20 0.33 174 P3 TWO 16 0DB1
+1.53 TEC TEN 25 NOT 600UL 74 32 0.39 23 P3 TWD 19 DBH
+1.65 TEC TEH 17 HOT 600UL 74 34 0.35 58 P3 TWD 16 DBH
+1.67 TEC TEH 13 HOT 600UL 74 38 0.22 136 P3 TWD1 06 DBH
+1.52 TEC TEH 13 HOT 600UL 74 62 0.17 47 P3 TWD 11 DBH
+2.17 TEH TEC 26 COLD 600UL 74 84 0.35 136 P3 TWO 18 DBC
-1.44 TEN TEC 18 COLD 600UL 74 94 0.30 120 P3 TWD 16 DB0
-1.69 TEH TEC 18 COLD 600UL 74 118 0.43 96 P2 TWD 21 08H
+0.88 TEH TEC 41 COLD 600UL 74 160 0.37 101 P2 TWD 24 08C
-0.21 TEC TEH 37 HOT 600UL 75 15 0.17 5
P3 TWD 9 DBC
+1.88 TEC TEH 27 HOT 600UL 75 31 0.25
.4 P3 TWD 10 DBC
+1.65 TEC TEH 16 HOT 600UL 0.30 128 P2 TWD 13 VH3
+0.80 TEC TEH 16 HOT 600UL 0.14 69 P3 TWD 6 DBH
-1.56 TEC TEH 16 HOT 600UL
L ----------------------------------------------------------------------------.
75 33 0.31 89 P3 TWD 16 DBC
-1.56 TEC TEH 17 HOT 600UL 0.26 127 P2 TWD 13 VC3
+0.86 TEC TEH 17 HOT 600UL 75....35...0.09.....114....P3...TWO.....4......C..-1.48......TEC....TEN....13...NOT...........U*
75 35 0.09 114 P3 TWD 4 DBC
-1.48 TEC TEH 13 HOT
- 600OUL
AREVA NP Inc 10/31/08 11:18:03 Customer Name: SONGS Unit 3 Component: S/G 88 Page 10 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: deOlinspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 75 37 0.12 140 P3 TWD 5 DBC
+2.01 TEC TEH 12 HOT 600UL 75 45 0.37 107 P2 TWD 18 VSM
+0.88 TEC TEH 11 HOT 60OUL 0.38 130 P2 TWD 18 VH3
+0.73 TEC TEN 11 HOT 600UL 0.26 84 P2 TWD 13 VH3
+0.09 TEC TEH 11 HOT 600UL 0.29 117 P2 TWD 15 VH3
-0.83 TEC TEH 11 HOT 600UL 75 47 0.22 87 P2 TWD 12 VH3
+0.13 TEH TEC 21 COLD 60OUL 0.36 136 P2 TWD 18 VC3
+0.76 TEH TEC 21 COLD 600UL 0.19 151 P3 TWD 10 DBC
+1.64 TEH TEC 21 COLD 60OUL 75 75 0.33 148 P2 TWD 16 VSM
+0.85 TEH TEC 27 COLD 600UL 0.54 136 P2 TWD 23 VSM
-0.91 TEH TEC 27 COLD 600UL 75 85 0.23 50 P3 TWD 12 DBC
-1.97 TEH TEC 17 COLD 600UL 75 121 0.15 113 P2 TWD 9 VH3
-0.86 TEH TEC 41 COLD 600UL 76 18 0.58 151 P2 TWD 23 VH3
+0.88 TEC TEH 24 HOT 600UL 76 28 d.16 32 P3 TWD 6 DBC
+2.12 TEC TEH 20 HOT 600UL 76 32 0.46 50 P3 TWD 18 DBH
+1.89 TEC TEN 16 NOT 60OUL 76 34 0.12 177 P3 TWD 6 DBC
+2.13 TEC TEH 12 HOT 600UL 0.52 106 P2 TWD 22 VH3
+0.85 TEC TEN 12 HOT 60OUL 0.17 139 P3 TWD 8 DBH
+1.44 TEC TEH 12 HOT 600UL 76 36 0.44 130 P2 TWO 19 VN3
-0.19 TEC TEN 12 NOT
- 600UL 0.62 114 P2 TWD 24 VH3
-0.70 TEC TEH 12 HOT 600UL 0.33 131 P3 TWD 14 DBC
+2.19 TEC TEH 12 HOT 600UL 0.18 7
P3 TWD 8 DBH
+1.65 TEC TEH 12 HOT 60OUL 76 40 0.39 77 P2 TWD 17 VH3
+0.72 TEC TEH 10 HOT 600UL 0.19 84 P3 TWD 9 DBC
+1.78 TEC TEH 10 HOT 60OUL 76 48 0.28 30 P2 TWD 15 VH3
-0.11 TEH TEC 21 COLD 600UL 0.51 133 P2 TWD 23 VSM
-0.90 TEH TEC 21 COLD 600UL 0.42 148 P2 TWD 20 VSM
+0.90 TEH TEC 21 COLD 600UL 0.13 143 P2 TWD 8 VC3
-0.76 TEH TEC 21 COLD 600UL 0.29 50 P2 TWD 15 VC3
+0.93 TEH TEC 21 COLD 60OUL 0.26 121 P2 TWD 14 VH3
+0.78 TEH TEC 21 COLD 60OUL 76 52 0.27 148 P2 TWD 14 VH3
-0.80 TEH TEC 21 COLD 600UL 76 56 0.21 137 P2 TWD 11 05C
+0.83 TEH TEC 23 COLD 600UL 0.24 127 P2 TWD 12 04C
+0.84 TEH TEC 23 COLD 60OUL 0.17 126 P2 TWD 9 03C
+0.97 TEH TEC 23 COLD 600UL 76 58 0.13 130 P3 TWD 7 DBC
-1.69 TEH TEC 23 COLD 600UL 76 62 0.29 126 P2 TWD 15 04C
+0.89 TEH TEC 25 COLD
. 600UL 76 68 0.41 71 P2 TWD 19 07H
+0.99 TEH TEC 25 COLD 600UL 76 72 0.21 71 P2 TWD 11 VH3
-.0.91 TEH TEC 28 COLD 600UL 76 90 0.26 47 P2 TWD 14 08C
-0.17 TEH TEC.17 COLD 600UL 76 114 0.32 133 P2 TWD 16 VSM
-0.72 TEH TEC 42 COLD 600UL 0.54 116 P2 TWD 23 VH3
+0.57 TEH TEC 42 COLD 600UL 0.37 134 P2 TWD 18 VC3
+0.82 TEH TEC 42 COLD 600UL 76 132 0.32 97 P2 TWD 16 VH3
+0.77 TEC TEH 8
HOT 600UL 0.19 123 P3 TWD 8 DBC
-1.80 TEC TEH 8
HOT 600UL 0.30 99 P2 TWD 15 VH3
-0.81 TEC TEH 8
HOT 600UL 76 134 0.15 26 P3 TWD 6 DBC
+2.15 TEC TEH 14 HOT 600UL 76 136 0.33 92 P2 TWD 15 VSM
-0.83 TEC TEH 18 HOT 600UL 0.61 116 P2 TWD 24 VH3
+0.95 TEC TEH 18 HOT 600UL 77 15 0.32 87 P3 TWD 14 DBC
-1.88 TEC TEH 26 HOT 600UL 77 27 0.31 13 P3 TWD 13 DBC
+2.18 TEC TEH 20 N
HOT 60OUL
AREVA NP Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component: S/G 88 Page 11 of 27 (de0l) Post-U3Cl5 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY:
deOl inspectionresults-qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL #VLEG PROBE 77 29 0.29 152 P2 TWD 13 VC3
-0.84 TEC TEH 20 HOT 600UL 0.219 90 P3 TWD 12 DBC
-1.81 TEC TEH 20 HOT 600UL 77
- 31.
0.31 126 P2 TWD 15 VC3
+0.88 TEC TEN 17 NOT 600UL 0.56 126 P2 TWD 23 VSM
+0.84 TEC TEH 17 HOT 600UL 0.44 127 P3 TWD 20 DBH
+1.96 TEC TEH 17 HOT 600UL 77 57 0.52 71 P2 TWD 23 VC3
+1.06 TEH TEC 23 COLD 600UL 0.35 105 P2 TWD 17 VC3
+0.21 TEH TEC 23 COLD 600UL 77 73 0.27 133-P2 TWD 13 VH3
+0.85 TEH TEC 28 COLD 600UL 77 113 0.09 139 P3 TWD 4 DBC
+1.80 TEH TEC 42 COLD 600UL 0.24 144 P2 TWD 12 VH3
-0.86 TEH TEC 42 COLD 600UL 0.43 83 P2 TWD 20 VH3
+0.74 TEH TEC 42 COLD 600UL 0.24 93 P2 TWD 12 VSM
-0.04 TEH TEC 42 COLD 600UL 0.26 54 P2 TWD 13 VSM
+0.82 TEH TEC 42 COLD 600UL 0.19 144 P2 TWD 10 VC3
-0.90 TEH TEC 42 COLD 600UL 77 131 0.34 92 P2 TWD 16 VH3
-0.93 TEC TEH 8
HOT 600UL 77 161 0.24 37 P2 TWD 13 07C
-0.93 TEC TEH 36 HOT 600UL 0.26 27 P3 TWD 11 DBH
+1.75 TEC TEH 36 HOT 600UL 0.17 160 P2 TWD 10 08C
-0.93 TEC TEH 36 HOT 600UL 78 20 0.38 60 P3 TWD 18 DBO
+1.71 TEC TEH 25 HOT 600UL 78 38 0.24 126 P2 TWD 13 VH3
-0.89 TEC TEH 13 HOT 600UL 0.23 58 P3 TWD 11 DBH
+1.39 TEC TEH 13 HOT 600UL 78 102 0.39 16 P3 TWD 19 DBH
+1.94 TEH TEC 38 COLD 600UL 78 124 0.36 100 P2 TWD 18 VC3
-0.83 TEH TEC 41 COLD 600UL 0.58 85 P2 TWD 26 VH3
+0.83 TEH TEC 41 COLD 600UL 0.40 120 P2 TWD 20 VH3
+0.06 TEH TEC 41 COLD 600UL 0.54 110 P2 TWD 24 VC3
+0.95 TEH TEC 41 COLD 600UL 79 21 0.24 52 P3 TWD 11 DBC
+1.57 TEC TEH 24 HOT 600UL 0.62 110 P3 TWD 23 DBH
+1.60 TEC TEH 24 HOT 600UL 79 29 0.32 103 P2 TWD 14 VC3
-0.93 TEC TEH 20 HOT 600UL 0.11 172 P3 TWD 4 DBH
+1.73 TEC TEH 20 HOT 600UL 79 47 0.24 116 P2 TWD 13 VC3
-0.90 TEH TEC 21 COLD 600UL 79 55 0.13 169 P3 TWD 6
, DBH
+1.78 TEH TEC 23 COLD 600UL 79 59 0.35 147 P3 TWO 16 DON-
+1.95 TEN TEC 23 COLD 600UL 79 89 0.30 149 P3 TWD 15 DBH
+1.50 TEH TEC 17 COLD 600UL 0.51 133 P2
-TWO 23 VN3
+0.91 TEN TEC 17
.COLD 600UL 79 115 0.37 148 P2 TWD 17 VN3
+0.76 TEH TEC 42 COLD 600UL 0.31 131 P2 TWD 15 VSN
-0.16 TEH TEC 42 COLD I 600UL 0.37 58 P2 TWD 17 VC3
-0.90 TEH TEC 42 COLD 600UL 79 117 0.25 114 P2 TWD 13 07N
-0.83 TEH TEC 42 COLD 600UL 0.67 99 P2 TWD 26 VC3
-0.97 TEH TEC 42 COLD 600UL 0.72 116 P2 TWD 28 VC3
+0.80 TEH TEC 42 COLD 600UL 79 125 0.33 136 P2 TWD 18 VC3
-0.86 TEH TEC 40 COLD 600UL 0.38 123 P2 TWD 19 VC3
+0.86 TEH TEC 40 COLD 600UL 79 131 0.24 88 P2 TWD 12 VSN
-0.58 TEC TEN 8
NOT C
600UL 79 161 0.44 97 P2 TWO 21 08N
-0.16 TEC TEN 36 NOT 600UL 0;28 55 P3 TWO 12 DON
+1.58 TEC TEN 36 NOT
-600UL 80 22 0.25 60 P3 TWO 10 DON
+2.13 TEC TEN 24 NOT 600UL 80 38 0.21 90
- P2 TWO 10 VC3
+0.76 TEC TEN 12 NOT 600UL 0.34 128 P2 TWD 16 VC3
-0.93 TEC TEN 12 OT 600UL 0.79 121 P2 TWD 28 VSM
+0.76 TEC TEH 12 HOT 600UL 0.99 136 P2 TWD 32 VN3
-0.91 TEC TEH 12 HOT 600UL 0.57 125 P3 TWD 21 DBH
+1.53 TEC TEH 12 HOT 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name: SONGS Unit 3 Component: S/G 88 Page 12 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY:
deOl inspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 80 40 0.20 124 P3 TWD 9 DBC
+1.49 TEC TEH 10 HOT 600UL 0.29 94 P2 TWD 13 VC3
-0.08 TEC TEN 10 HOT 600UL 0.23 86 P2 TWD 11 VC3
+0.66 TEC TEN 10 HOT 600UL 0.18 160 P2 TWD 9 VH3
+/-0.64 TEC TEH 10 HOT 60OUL 0.42 86 P2 *TWD 18 VH3
+0.02, TEC TEN 10 HOT 600UL 80 80 0.67 77 P2 TWD 27 VSM
+0.95 TEH TEC 17 COLD 60OUL 0.40 71 P2 TWD 19 VH3
+0.59 TEH TEC 17 COLD 600UL 80 102 0.61 86 P2 TWD 27 VC3
-0.91 TEN TEC 38 COLD 60OUL 80 132 0.13 176 P3 TWD 6 DBC
+1.66 TEC TEH 8
HOT 600UL 80 142 0.58 111 P2 TWD 26 VC3
+0.72 TEC TEN 22 HOT 600UL 0:47 143 P2 TWD 23 VC3
-0.88 TEC TEN 22 HOT 600UL 0.28 123 P2 TWD 15 VSM
+0.80 TEC TEH 22 HOT 600UL 0.37 134 P2 TWD 19 VSM
-0.80 TEC TEH 22 HOT 600UL 0.48 128 P2 TWD 23 VH3
+0.74 TEC TEH 22 HOT 600UL 0.58 127 P2 TWD 26 VH3
-0.97 TEC TEH 22 HOT 600UL 81 33 0.40 146 P2 TWD 20 VSM
-0.84 TEC TEH 2
HOT 600UL 0.72 136 P2 TWD 28 VH3
+0.81 TEC TEN 2
HOT 600UL 0.34 62 P2 TWD 17 VH3
+0.28 TEC TEH 2
HOT 600UL" 81 35 0.18 42 P3 TWD 10 DBC
-1.72 TEC TEH 2
HOT 600UL 81 39 0.35 137 P2 TWD 18 VH3
-0.70 TEC TEH 2
HOT 600UL 0.31 103 P2 TWD 16 VC3
+0.83 TEC TEN 2
HOT 60OUL 81 41 0.22 152 P2 TWD 13 'VSM
+0.81 TEC TEN 6
HOT 600UL 0.33 129 P2 TWD 18 VH3
+0.87 TEC TEN 6
HOT 600UL 0.47 65 P2 TWD 23 VH3
+0.00 TEC TEN 6
HOT 600UL 0.25 157 P2 TWD 14 VH3
-0.98 TEC TEN 6
HOT 60OUL 81 57 0.33 80 P2 TWD 17 07H
+0.95 TEH TEC 32 COLD 600UL 81 59 0.26 43 P3 TWD 13 DBH.
+1.67 TEH TEC 31 COLD 600UL 0.63 130 P2 TWD 26 VC3
-0.72 TEH TEC 31 COLD 600UL 0.63 53 P2 TWD 26 VC3
+0.08 TEH TEC 31 COLD 60OUL 81 63 0.43 133 P2 TWD 18 VSM
-0.81 TEN TEC
- 34.
COLD 600UL 81 65 0.34 144 P2 TWD 17 VH3
-0.81 TEN TEC 27 COLD 600UL 0.54 147 P2 TWD 23 VSM
+0.82 TEH TEC 27 COLD
.600UL 81 69 0.21 139 P2 TWD 13 VC3
-0.95 TEH TEC 33 COLD 600UL 0.25 93 P2 TWD 15 VSM
-0.78 TEH TEC 33 COLD 600UL 0.10 71 P3 TWD 6 DBH
+1.10 TEN TEC 33 COLD 600UL 0.16 130 P3 TWD 9 DBH
+1.33 TEH TEC 33 COLD 600UL 0.38 31 P2 TWD 20 VH3
+0.02 TEH TEC 33 COLD 600UL 0.39 104 P2 TWD 20 VC3
+0.99 TEH TEC 33 COLD 600UL 81 81 0.36 144 P2 TWD 19 VH3
-0.74 TEN TEC 1
COLD 600UL 0.62 113 P2 TWD 27 VC3
-0.63 TEN TEC 1
COLD 600UL 0.52 62 P2 TWD 24 VC3
+0.80 TEH TEC 1
COLD 600UL 0.37 154 P2 TWD 18 VH3
+0.78 TEN TEC 1
COLD 600UL 0.30 136 P2 TWD 15 VSM
+0.82 TEN TEC 1
COLD.
60OUL 0.25 59 P2 TWD 12 VC3
-0.08 TEN TEC 1
COLD 600UL 81 109 0.25 100 P2 TWD 13 VSM
-0.06 TEH TEC 7
.COLD 600UL 81 121 0.61 108 P2 TWD 26 VH3
-0.89 TEH TEC 5
COLD 600UL 0.41 156 P2 TWD 20 VH3
+0.79 TEH TEC 5
COLD 600UL 81 141 0.38 141 P2 TWO 18 VN3
+0.85 TEC TEd 3
NOT 600UL 0.38 149 P2 TWD 18 VH3
-0.83 TEC TEN 3
HOT 600UL 81 153 0.27 157 P3 TWD 11 DBC
+1.89 TEC TEN 8
HOT 600UL 82 20 0.15 110 P3 TWD 8 DBC
+2.00 TEC TEH 2
HOT 600UL 82 22 0.42 107 P3 TWD 17 DBC
+1.67 TEC TEH 1
HOT 600UL 82 28 0.37 27 P3 TWD 18 DBH
-1.66 TEC TEH 2
HOT 60OUL 82 62 0.33 34 P2 TWD 18 VH3
+0.81 TEN TEC 32 COLD 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name: SONGS Unit 3 Component:
S/G 88 Page 13 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de01_inspectionresults.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.22 63 P2 TWD 13 VH3
-0.87 TEH TEC 32 COLD 600UL 82 68 0.42 145 P2 TWD 17 VH3
-0.82 TEH TEC 34 COLD 600UL 0.37 64 P2 TWD 16 VSM
-0.27 TEH TEC 34 COLD 600UL 0.33 47 P2 TWD 14 08C
-0.15 TEH TEC 34 COLD 600UL 82 74 0.41 23 P3 TWD 20 DBH
+1.63 TEH TEC
- 36.
COLD
- 60OUL 82 84 0.48 87 P3 TWD 21 DBH
-1.61 TEH TEC 1
COLD 600UL 82 100 0.46 120 P2 TWD 22 VH3
-0.78 TEH TEC 10 COLD 600UL 0.35 51 P2 TWD 18 VH3
+0.93 TEH TEC 10 COLD 600UL 82 110 0.39 65 P2 TWD 18 VH3
+0.70 TEH TEC 7
COLD
- 600UL 82 130 0.38 96 P2 TWD 18 VC3
-0.83 TEC TEH 3
HOT 60OUL 0.63 131 P2 TWD 26 VH3
-0.94 TEC TEH 3
HOT 600UL 82 132 0.31 119 P2 TWD 15 VN3
-0.84 TEC TEN 3
. NOT 600UL 0.36 114 P2 TWD 17 VH3
+0.94 TEC TEN 3
HOT 600UL 82 152 0.36 126 P2 TWD 17 08C
-0.17 TEC TEH
- 8.
HOT 600UL 83 19 0.40 121 P2 TWD 17 VH2
+0.80 TEC TEH 1
HOT 600UL 0.29 65 P2 TWD 13 09C
+1.50 TEC TEH 1
HOT 600UL 83 25 0.23 29 P3 TWD 11 DBC
-0.79 TEC TEH 1
HOT 60OUL
.83 101 0.20 100 P2 TWD 11 07H
-0.66 TEH TEC 9
COLD 600UL 83 117 0.29 131 P2 TWD 16 05C
+0.49 TEH TEC 5
COLD 60OUL 83 139 0.29 148 P2 TWD 20 VN2
+0.90 TEC TEN 4
NOT EDO600UL 83 153 0.52 113 P2 TWD 22 VH2
+0.83 TEC TEH 8
HOT 600UL 83 157 0.41 110 P2 TWD 19 VH2
+0.94 TEC TEH 8
HOT 600UL 84 58 0.38 106 P2 TWD 19 09H
-1.29 TEN TEC 31 COLD 600UL 0.67 84 P2 TWO 27 09
+--1.73 TEN TEC 31 COLD 600UL 84 60 0.32 140 P2 TWD 16 09H
-1.61 TEH TEC 31 COLD 600UL 84 68 0.28 132 P2 TWO 16 09N
-1.50 TEN TEC 33 COLD 600UL 0.20 62 P2 TWD 12 09H
+0.66 TEH TEC 33 COLD 600UL 84 74
'0.19 156 P2 TWO 10 VN2
-0.72 TEE TEC 35 COLD 600UL 84 98 0.20 98 P2 TWD 16 09H
-1.40 TEH TEC 10 COLD 60OUL 84 102 0.34 145 P2 TWD 17 07H
-0.80 TEH TEC 10 COLD 600UL 0.22 98 P2 TWD 12 09H
+1.51 TEH TEC 10 COLD
.600UL 0.42 118 P2 TWO 21 09N
-1.40*
TEN TEC 10 COLD 600UL 84 104 9.20 66 P2 TWD 12 09H
-1.17 TEH TEC 8
COLD 600UL 84 106 0.28 99 P2 TWD 15 09H
-1.42 TEH TEC 8
COLD 600UL 0.60 121 P2 TWt 26 09H
+1.59 TEN TEC 8
COLD 600UL 84 108 0.37 147 P2 TWD 19 09H
-1.63 TEH TEC 8
COLD
- 600UL, 0.33 129 P2 TWD 17 09H
+1.69 TEH TEC 8
COLD 600UL 84 110 0.30 23 P2 TWO 15" 08H
-0.02
- TEN TEC 7
COLD 600UL 0.38 122 P2 TWD 18 09H
-1.49 TEH TEC 7
COLD 600UL 0.64 100 P2 TWO 25 09W
+1.45 TEN TEC 7
COLD 600UL 84 114 0.45 139 P2 TWD 22 09H
-1.62 TEH TEC 6
COLD 600UL 0.37 124 P2 TWO 19 09N
+1.45 TEE TEC 6
COLD E00UL 84 116 0.34 99 P2 TWD 18 09H
-1.46 TEH TEC 6
COLD 600UL 0.52 146 P2 TWD 24 09H
+1.59 TEH TEC 6
COLD 600UL 84 118 0.35 138 P2 TWD 18 09H
-1.24 TEH TEC 6
COLD 600UL 84 122 0.39 124 P2 TWD 20 09H
-1.42 TEH TEC 7
COLD 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name: SONGS Unit 3 Component: S/G 88 Page 14 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de01_inspectionresults.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 85 61 0.50 94 P2 TWD 23 08H
+0.59 TEH TEC 31 COLD 600UL 85
- 83.
0.22 143 P2 TWD 11 06H
+0.82 TEH TEC 11 COLD 600UL 85 157 0.21 42 P3 TWD 16 DBH
+1.80 TEC TEH 9
HOT 600UL 86 60 0.36 141 P2 TWD 19 08H
-0.73 TEH TEC 32 COLD 60OUL 0.28 99 P2 TWD 16 09H
-0.78 TEH TEC 32 COLD 600UL 86 94 0.24 32 P2 TWD 12 01C
-0.95 TEH TEC 13 COLD 600UL 86 98 0.19 62 P2 TWD 10 06H
+0.80 TEH TEC 10 COLD 60OUL 86 102 0.27 164 P2 TWO 14 09H
+0.59 TEN TEC 10 COLD 600UL 86 108 0.28 84 P2 TWD 14 09H
+0.64 TEH TEC 17 COLD 600UL 86 112 0.32 42 P2 TWD 17 08H
-0.17 TEH TEC 6
COLD 60OUL 87 61 0.53 47 P2 TWD 25 08H
+0.74 TEH TEC 32 COLD 60OUL 87 77 0.24 90 P2 TWO 13 VN2
-0.78 TEN TEC 2
COLD 600UL 87 99 0.20 124 P2 TWD 11 08H
-0.34 TEH TEC 9
COLD 60OUL 0.25 50 P2 TWO 14 07N
+1.00 TEN TEC 9
COLD i*600UL 87 101 0.33 115 P2 TWO 17 Q7N
+0.26 TEN TEC 9
COLD ED60UL 87 111 0.21 111 P2 TWD 10 08H
-0.49 TEH TEC 7
COLD 600UL 87 117 0.S2 113 P2 TWD 17 0H
+0.32 TEH TEC 9
COLD 60OUL 88 64 0.33 125 P2 TWD 14 VSN
-0.72 TEH TEC 34 COLD 600UL 88 66 0.43 152 P2 TWD 18 VH2
-0.91 TEH TEC 34 COLD 600UL 88 68 0.29 73 P2 TWD 16 08H
-0.96
- TEH TEC 33 COLD 600UL 88 72 0.317 88 P2 TWD 9 V03
+0.61 TEH TEC 35 COLD 600UL 88 76 0.51 148 P2 TWD 24 VN2
-0.72 TEH TEC 1
COLD 600UL 89 29 0.46 111 P2 TWD 22 VN2
+0.06 TEC TEN 2
NOT S00UL 0.28 141 P2 TWO 15 VN2
+0.86 TEC TEN 2
NOT 600UL 89 57 0.42 126 P2 TWO 20 b9N
+0.55 TEN TEC
.31 COLD 600UL 89 59 0.45 117 P2 TWO 21 09N
+0.86.
TEN TEC 31
- COLD 600UL 89 61 0.43 112 P2 TWD 20 09H
+0.84 TEH TEC 31 COLD 600UL 89 79 0.42 90 P2 TWO 20 09N
-0.19 TEN TEC 2
COLD 600UL 89 101 0.41 149 P2 TWO 19 07N
+0.92 TEN TEC 9
COLD 600UL<
89 109 0.26 55 P2 TWO 13 08N
-0.36 TEN TEC 7
COLD
!600UL 0.21 110 P2 TWO 11 09N
+0.57 TEN TEC 7
COLD 60001 89 113 0.41 100 P2 TWO 21 09N
+0.57 TEN TEC S
COLD
.600UL 89 151 0.26 113 P2 TWO 19 VC3
-0.94 TEC TEN 9*
NOT 600UL 90 60 0.31 48 P2 TWD 17 08H
-0.13 TEH TEC 32 COLD 600UL 90 72 0.31 85 P2 TWD 16 08H
-0.43 TEH TEC 36 COLD 600UL 90 78 0.32 100 P2 TWD 16 09H
-0.06 TEH TEC 1
COLD 60OUL 0.24 133 P2 TWO 11 09N
+0.78 TEN TEC 1
COLD
- 600UL 90 102 0.42 122 P2 TWD 21 08H
+0.89 TEN TEC 10 COLD 600UL 0.17 137 P2 TWD 9 09H
+0.89 TEN TEC 10 COLD 600UL 0.22 22 P2 TWD 12 09H
-0.23 TEH TEC 10 COLD 600UL 90 116 0.45 147 P2 TWD 22 VH2
-0.78 TEH TEC 5
COLD 600UL 91 69 0.58 127 P2 TWD 22 08H
+0.70 TEH TEC 34 COLD 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component:
S/G 88 Page 15 of 27 (de0l) Post-U3Cl5 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: deOlinspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.52 94 P2 TWD 20 09H
-0.27 TEH TEC 34 COLD 60OUL 91 73 0.66 148 P2 TWD 28 09H
-0.32 TEH TEC 36 COLD 600UL 0.38 132 P2 TWD 19 08H
+0.84 TEH TEC 36 COLD 600UL 91 79 0.21 74 P2 TWD 13-07H
+0.27 TEH TEC 1
COLD 600UL 0.34 85 P2 TWD 18 09H
+0.46 TEH TEC 1
COLD 600UL 91 99 0.28 109 P2 TWD 15 08K
+0.91 TEN TEC 9
COLD 600UL 0.28 46 P2 TWD 15 08H
-0.89 TEH TEC 9
COLD 600UL 91 103 0.32 113 P2 TWD 16 08K
+0.83 TEN TEC 9
COLD GODUL 0.10 127 P2 TWD 6 08H
-0.90 TEH TEC 9
COLD 600UL 91 105 0.32 76 P2 TWD 16 09H
-0.21 TEH TEC 7
COLD 60OUL 91 111 0.42 61 P2 TWD 18 09K
-0.28 TEN TEC 7
COLD 600UL 91 113 0.19 118* P2 TWD.11 09K
-0.40 TEN TEC 5
COLD E0OUL 0.51 97 P2 TWD 24 09H
+0.51 TEH TEC 5
COLD 600UL 91 115 0.30 135 P2 TWD 16 09H
+0.28 TEH TEC 6
COLD 600UL 92 42 0.42 84 P2 TWD 19 VN2
-1.11 TEC TEN 6
NOT 600UL 92 66 0.40 136 P2 TWO 16 09H
-0.13 TEN TEC 34 COLD 600UL 0.23 89 P2 TWO 11 09K
+0.93 TEN TEC 34 COLD 600UL 92 68 0.64 140 P2 TWO 27 09H
-0.17 TEN TEC
.33 COLD 600UL 92 72 0.38 129 P2 TWO 19 09K
-0.02 TEN TEC 35 COLD E00UL 0.20 43 P2 TWD 18 09H
+0.65 TEH TEC 35 COLD 60OUL 0.34 112 P2 TWD 17 05H
+0.82 TEH TEC 35 COLD 600UL 92 74 0.48 107 P2 TED 22 07K
+0.85 TEN TEC 35 COLD 600UL 0.28 36 P2 TWD 15 09H
+0.95 TEH TEC 35 COLD 600UL 92 76 0.31 135 P2 TWD 16 09H
-0.48 TEH TEC 2
COLD 600UL 92 96 0.26 144 P2 TWD 13 09H
-0.13 TEN TEC 10 COLD 600UL 92 98 0.21.
75 P2 TWO 11 08K
-0.47 TEN TEC 10 COLD SOQUL 92 102 0.46 84 P2 TWD 22 09H
+0.93 TEH TEC 10 COLD 600UL
- 0.58 144 P2 TWO 26 09K
-1.00 TEN TEC 10 COLD
.600UL 92 104
.0.26 153 P2 TWO 14 09K
-0.30 TEN TEC 8
COLD 600UL 0.23 32 P2 TWD 13 09H
+0.87 TEH TEC 8
COLD 600UL 92 112 0.14 124 P2 TWD 9 09H
-1.21 TEH TEC 6
COLD 600UL 9
0.56 104 P2 TWD 25 09H
+0.34 TEH TEC 6
COLD 600UL 0.22 100 P2 TWD 13 09H
+0.91 TEH TEC 6
COLD 600UL 93 61 0.67 98 P2 TWO 27 09K
+0.72 TEN TEC 31 COLD
.600UL 93 63 0.37 65 P2 TWO 16 09K
+1.02 TEN TEC 34 COLD 600UL 93 69 0.27 128 P2 TWD 15 09H
,+0.72 TEH TEC 33 COLD 600UL 93 73 0.35 154 P2 TWD 18 09H
+0.80 TEH TEC 35 COLD 600UL 0.19 50 P2 TWD 15 08H
-0.87 TEH TEC 35 COLD 600UL 93 75 0.64 83 P2 TWO 27 09K
-0.25 TEN TEC 35 COLD 600UL 93 77 0.32 66 P2 TWD 17 09H
-0.25 TEH TEC 2
COLD 600UL 93 79 0.25 110 P2 TWO 14 09K
-0.17 TEN TEC 2
COLD
- 600UL 93 97 0.39 119 P2 TWD 19 09H
-0.19 TEH TEC 9
COLD 600UL 0.15 136 P2 TWO 9 09K
+0.83 TEN TEC 9
COLD 600UL 93 105 0.21 122 P2 TWD 11 08H
-0.49 TEH TEC 7
COLD 600UL 93 104 0.38 128 P2 TWD 16 08H
+0.30 TEH TEC 7
COLD 600UL 93 113 0.32 64 P2 TWD 17 09H
+0.70 TEH TEC 6
COLD 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component: S/G 88 Page 16 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de01_inspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 93 149 0.16 31 P3 TWD 13 DBC
-1.60 TEC TEN 9
HOT 600UL 94 28 0.45 102 P2 TWD 21 VSM
-0.79 TEC TEH
- 2.
HOT 600UL 0.29 103 P2 TWD 15 VH3
+0.92 TEC TEH.
2 NOT 600UL 0.34 102 P2 TWD 17 VH2
-0.97 TEC TEH 2
HOT 600UL 0.22 106 P2 TWD 13 VH2
+0.82 TEC TEH 2
HOT 600UL 94 40 0.80 137 P2 TWD 28 VSM
+0.70 TEC TEH 5
HOT 600UL 0.87 121 P2 TWD 29 VH2
-0.94 TEC TEH 5
HOT 600UL 94 62 0.24 115 P2 TWD 14 09H
+0.06 TEH TEC 32 COLD 600UL 94 64 0.19 138 P2 TWD 11 08H
-0.43 TEH TEC 33 COLD 60OUL 0.26 119 P2 TWD 15 09H
+0.36 TEH TEC 33 COLD 600UL 94 66 0.18 130 P2 TWD 11 09H
+0.61 TEH TEC 33 COLD 60OUL 0.15 146 P2 TWD 10 VH2
-1.10 TEH TEC 33 "
COLD 60OUL 94 68 0.49 144 P2 TWD 20 VH2
+0.95 TEH TEC 34 COLD 60OUL 94 72 0.18 114 P2 TWD 10 07H
+0.38 TEH TEC 36 COLD 600UL 94 74 0.26 72 P2 TWD 14 09H
-0.36 TEH TEC 35 COLD 600UL 94 78 0.32 149 P2 TWD 17 09H
+0.53 TEH TEC 1
COLD 600UL 0.33 113 P2 TWD 16 09H
-0.15 TEH TEC 1
COLD 600UL 94 82 0.42 147 P2 TWD 21 09H
-0.21 TEH TEC 12 COLD 600UL 94 84 0.38 66 P2 TWD 17 08H
-0.40 TEH TEC 11 COLD 600UL 94 88 0.61 133 P2 TWD 24 09H
-0.85 TEH TEC 11 COLD 600UL 94 94 0.17 145 P2 TWD 10 07H
+0.93 TEH TEC 14 COLD 600UL 94 96 0.13 32 P2 TWD 8 09H
+0.87 TEH TEC 9
COLD 600UL 0.24 41 P2 TWD 13 08H
-0.49 TEH TEC 9
COLD 600UL 94 102 0.30 113 P2 TWD 16 09H
-0.44 TEH TEC 10 COLD 600UL 94 104 0.22 103 P3 TWD 14 DBH
+1.16 TEH TEC 8
COLD 60OUL 0.24 98 P2 TWD 13 09H
+0.40 TEH TEC 8
COLD 600UL 94 134 0.21 36 P3 TWD 8
DBC
+2.06 TEC TEH 3
HOT 600UL 94 146 0.64 100 P2 TWD 26 VH3
-0.96 TEC TEH 3
HOT 600UL 0.28 69 P2 TWD 14 VH2
+0.81 TEC TEH 3
HOT 600UL 0.29 67 P2 TWD 14 VH2
-0.89 TEC TEH 3
HOT 600UL 94 148 0.29 43 P2 TWD 14 VC3
+0.81 TEC TEN 3
HOT 600UL 95 63 0.29 96 P2 TWD 16 09H
+0.25 TEH TEC 33 COLD 600UL 95 65 0.61 67 P2 TWD 25 09H
-0.17 TEH TEC 27 COLD 600UL 0.15 159 P2 TWD 8 09H
+0.89 TEN TEC 27 COLD 600UL 0.33 71 P2 TWD 16 08H
+0.32 TEH TEC 27 COLD 600UL 95 67 0.31 142 P2 TWD 17 09H
+0.63 TEH TEC 33 COLD 600UL 95 69 0.38 128 P2 TWD 16 08H
+0.65 TEH TEC 34 COLD 600UL 95 71 0.17 155 P2 TWD 11 07H
-0.93 TEH TEC 33 COLD 600UL 95 73 0.35 158 P2 TWD 18 VSM
+0.82 TEH TEC 36 COLD 600UL 0.33 92 P2 TWD 17 VH3
+0.78 TEH TEC 36 COLD 600UL 0.49 92 P2 TWD 23 09H
+0.67 TEH TEC 36 COLD 600UL 0.31 149 P2 TWD 16 VH3
+0.04 TEH TEC 36 COLD 600UL 0.27 26 P2 TWD 14 VC2
+0.04 TEH TEC 36 COLD 600UL 0.19 27 P2 TWD 9
. 07H
-0.88 TEH TEC 36 COLD 600UL 0.30 84 P2 TWD 15 07H
+0.64 TEN TEC 36 COLD 600UL 0.49 146 P2 TWD 23 VC3
+0.69 TEH TEC 36 COLD 600UL 95 77 0.24 116 P2 TWD 13 08H
+0.57 TEH TEC 2
COLD 600UL 95 85 0.29 79 P2
- TWD 16 09H
+0.82 TEH TEC 12 COLD 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name: SONGS Unit 3 Component: S/G 88 Page 17 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de01_inspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.29 122 P2 TWD 16 08H
+0.82 TEH TEC 12 COLD 600UL 95 89 0.26 135 P2 TWD 13 09H
+0.55 TEH TEC 11 COLD
.60UL 95 97 0.26 106 P2 TWD 14 09H
-0.23 TEH TEC 10 COLD 600UL 95 101 0.53 92 P2 TWD 23 09H
-0.44 TEH TEC 9
COLD 60OUL 0.17 41 P2 TWD 10 09H
+0.72 TEH TEC.
9 COLD 600UL 95 103 0.36 94 P2 TWO 18 09-
+0.83 TEN TEC 9
COLD 600UL 95 105 0.56 136 P2 TWD 23 09H
+0.80 TEH TEC 7
COLD 600UL
.0.22 58 P3 TWO 11 DBN
+0.53 TEN TEC 7
COLD 600UL 95 109 0.29 87 P2 TWD 14 09H
+0.89 TEH TEC 7
COLD 600UL 95 111 0.31 86 P2 TWO 17 09W
+1.00 TEE TEC 6
COLD 600UL 96 60 0.29 47 P2 TWO 16 09W
-0.30 TEN TEC 32 COLD 600UL 96 66 0.29 42 P2 TWO 12 08W
-0.06 TEN TEC 34 COLD 600UL 0.28 47 P2 TWD 13 07H
+0.82 TEN TEC 34 COLD 60OUL 96 68 0.14 27 P2 TWO 9 09W
-0.80 TEN TEC 33 COLD 600UL 0.29 100 P2 TWD 16 09H
+0.87 TEH TEC 33 COLD 600UL 96 70 0.69 132 P2 TWD 29 07W
+0.83 TEN TEC 33 COLD 600UL 0.11 154 P2 TWD 7 09H
-0.06 TEH TEC 33 COLD 600UL 96 72 0.13 85 P2 TWD 7 09H
-0.93 TEH TEC 35 COLD 600UL 0.23 44 P2 TWD 12 09H
+0.25 TEH TEC 35 COLD 600UL 96 80 0.24 158 P2 TWD 14 VH2
-0.82 TEH TEC 12 COLD 600UL 96 86 0.21 118 P2 TWD 10 07H
+0.22 TEH TEC 13 COLD 600UL 96 90 0.20 109 P2 TWD 10 09H
+0.57 TEH TEC 13 COLD 600UL 96 98 0.40 133 P2 TWD 20 09H
+0.64 TEH TEC 10 COLD 600UL 96 110 0.31 92 P2 TWD 15 09H
+0.13 TEH TEC 7
COLD 600UL 96 152 0.24 131 P2 TWD 18 02C
+0.84 TEC TEN 9
NOT 600UL 97 43 0.44 106 P2 TWO 18
- VN2
+0.85 TEC TEN 7
NOT 600UL 97
.61 0:16 140 P2 TWO 10 04C
-0.91 TEN TEC 32 COLD
.600UL
.97 65 0.32 43 P2 TWO 17 VW2
+0.85 TEN TEC 33 COLD 600UL 0.23 154 P2 TWO 13 09W
-0.70 TEN TEC 33 COLD 600UL 97 69 0;20 40 P2 TWO 12 07W
+0.94 TEN TEC 33 COLD 600UL 97 73 0.35 117 P2 TWD 17 08H
+0.76 TEH TEC 35 COLD 600UL 0.25 145 P2 TWD 13 08H
-0.62 TEH TEC 35 COLD 600UL 0.49 118 P2 TWO 23 09W
+0.70 TEN TEC 35 COLD 600UL 97 85 0.26 136 P2 TWD 12 09H
-0.14 TEH TEC 11 COLD 600UL 97 103 0.55 131 P2 TWD 24 09H
+0.36 TEH TEC 9
COLD 600UL 97 107 0.68.
99 P2 TWD 26 09H
-0.66 TEH TEC 7
COLD 600UL 0.44 53 P2 TWD 20 09H
-0.04 TEN TEC 7
COLD 600UL 97 141 0.26 133 P2 TWD 185 VN2
+0.8&
TEC TEN 4
NOT 600UL 98 24 0.30 155 P2 TWD 13 06C
+0.87 TEC TEH 1
HOT 600UL 0.19 37 P2 TWO 9 06C
+0.00 TEC TEN 1
NOT EQOUL 98 28 0.14 26 P3 TWO 8 DEN
-1.65 TEC TEN 2
NOT 600UL 98 42 0.38 98 P2 TWD 18 VH2
-0.85 TEC TEH 6
HOT 600UL 98 64 0.31 140 P2 TWD 17 VH2
-0.83 TEH TEC 33 COLD 600UL 98 66 0.32 100 P2 TWD 17 09H
+0.87 TEH TEC 33 COLD 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name: SONGS Unit 3 Component:
S/G 88 Page 18 of 27 (deOl)
Post-U3CI5 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: deOlinspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE
=---------------------------=------------------------ =--==-----------------
98 68 0.29 49 P3 TWD 24 DBH
+2.22 TEH TEC 34 COLD 60OUL 98 72 0.46 85 P2 TWD 22 07H
+0.83 TEH TEC 36 COLD 600UL 98 106 0.34 150 P2 TWD 17 09H
+0.87 TEH TEC 8
COLD 600UL 0.28 73 P2 TWD 15 09H
-0.18 TEH TEC 8
COLD 600UL 98 142 0.36 143 P2 TWD 17 VH2
-0.94 TEC TEH 3
HOT
.600UL 99 29 0.31 123 P3 TWD 13 DBH
+1.41 TEC TEH 1
HOT 600UL 99 65 0.36 122 P2 TWD 16 08H
+0.63 TEH TEC 34 COLD 600UL 99 79 0.33 111 P2 TWD 18 07H
+0.88 TEH TEC 1
COLD 600UL 99 81 0.48 145 P2 TWD 23 09H
+0.66 TEH TEC 12 COLD 1 600UL 99 89 0.54 127 P2 TWD 22 09H
+0.70 TEH TEC 11 COLD 600UL 99 93 0.32 91 P2 TWD 17 09H
+0.53 TEH TEC 14 COLD 600UL 99 99 0.44 130 P2 TWD 21 09H
-0.21 TEH TEC 9
COLD 60OUL 99 101 0.30 124 P2 TWD 15 08H
-0.17 TEH TEC 9
COLD 600UL 0.33 108 P2 TWD 17 09H
+0.72 TEH TEC 9
COLD 600UL 0.15 25 P3 TWD 8 DBH
+0.51 TEH TEC 9
COLD 600UL 99 103 0.27 73 P2 TWD 14 09H
+0.64 TEH TEC 9
COLD 600UL 0.49 105 P2 TWD 22 09H
+0.89 TEH TEC 9
COLD 600UL 99 109 0.17 161 P2 TWD 9 09H
+0.72 TEH TEC 7
COLD 600UL 100 28 0.22 106 P2 TWD 10 08C
+1.03 TEC TEH 1
HOT 600UL 100 74 0.28 63 P2 TWD 15 09H
-0.15 TEH TEC 35 COLD 60OUL 0.27 154 P2 TWD 14 09H
+0.91 TEH TEC 35 COLD 600UL 100 76 0.24 30 P1 SCI TSH
-0.07 TSH TSH 136 HOT 580PP 100 100 0.43 137 P2 TWD 21 09H
+0.91 TEH TEC 10 COLD 600UL 100 102 0.32 103 P2 TWD 17 09H
-0.23 TEH TEC 10 COLD 600UL 0.40 106 P2 TWD 20 VH2
-0.85 TEH TEC 10 COLD 600UL 100 134 0.13 136 P3 TWD 11 DBC
+2.21 TEC TEH 4
HOT 600UL 101 67 0.50 57 P2 TWD 20 09H
+0.80 TEH TEC 34 COLD 600UL 101 71 0.25 103 P3 TWD 21 DBH
-1.50 TEH TEC 34 COLD 60OUL 0.28 155 P2 TWD 13 09H
+0.78 TEH TEC 34 COLD 600UL 101 77 0.25 149 P2 TWD 15 09H
-0.69 TEH TEC 1
COLD 600UL 0.63 113 P2 TWD 27 09H
+0.63 TEH TEC 1
COLD 600UL 101 79 0.54 62 P2 TWD 24 09H
+0.97 TEH TEC 1
COLD 600UL 101 81 0.52 145 P2 TWO 21 09W
-0.70 TEN TEC 11 COLD 600UL 101 83 0.50 126 P2 TWD 21 09H
-0.51 TEH TEC 11 COLD 600UL 101 85 0.34 119 P2 TWD 16 09H
-0.49 TEH TEC 11 COLD 600UL 101 97 0.55 120 P2 TWD,24 09H
-0.97 TEH TEC 9
COLD 60OUL 0.15 30 P2 TWD 9 09H
-0.04 TEH TEC 9
COLD 600UL 101 101 0.28 115 P2 TWD 15 09H
-0.15 TEH TEC 9
COLD 600UL 101 113 0.52 19 P3 TWD 23 DBH
+1.20 TEH TEC 5
COLD 600UL 102 30 0.46 76 P2 TWD 18 08C
-1.01 TEC TEH 1
HOT 600UL 0.22 41 P2 TWD 10 08C
+0.09 TEC TEH 1
HOT 600UL 102 66 0.42 115 P2 TWD 21 VH2
-0.76 TEH TEC 33 COLD 600UL 0.24 134 P2 TWD 14 09H
+0.89 TEH TEC 33 COLD 60OUL
AREVA NP Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component: S/G 88 Page 19 of 27 (de0l)
Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY:
deOl inspectionresults.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 102 74 0.26
., 140 P2 TWD 13 09H
+0.84 TEH-TEC 36 COLD 600UL 102 78 0.49 128 P2 TWD 23 09H
+0.92 TEH TEC 2
COLD 600UL 102 82 0.28 103 P3 TWD 11 DBH
+1.84 TEH TEC 11 COLD 600UL 0.27 151 P2 TWD 13 09H
+0.50 TEH TEC 11 COLD 60OUL 102 84 0.25 85 P3 TWO 10 DON
+1.15 TEN TEC 11 COLD 600UL 102 92 0.25 133 P3 TWD 16 DBH
+1.92 TEH TEC 14 COLD 600UL 102 106 0.18 69 P2 TWD 10 04C
+0.89 TEH TEC 8
COLD 60OUL 102 128 0.41 128 P2 TWD 20 VN2
+0.00 TEH TEC 4
COLD 60OUL 103 33 0.44 148 P2 TWD 18 VH2
+0.94 TEC TEN 1
NOT 600UL 103 65 0.32 139 P2 TWO 13 VC3
-0.80 TEN TDEC 34 COLD 600UL 103 71 0.36 93 P2 TWD 19 09H
+0.84 TEN TEC 33 COLD 600UL 103 75 0.38 125 P2 TWD 19 09N
-0.80 TEH TEC 36 COLD 600UL 0.20 108 P2 TWD i0 09H
+0.70 TEH TEC 36 COLD 600UL 0.32 115 P2 TWD 16 09H
+0.97 TEH TEC 36 COLD 600UL 0.55 88 P2 TWO 25 VN2
+0.80 TEN TEC 36 COLD 600UL 0.26 134 P2 TWD 13 09H
+0.49 TEH TEC 36 COLD 600UL 103 79 0.32 124 P2 TWD 18 09H
-0.86 TEH TEC 1
COLD 600UL 0.36 121 P2 TWD 19 09H
+0.21 TEH TEC 1
COLD 60OUL 0.35 112 P2 TWD 19 09H
+0.65 TEH TEC 1
COLD 60OUL 103 81 0.51 93 P2 TWO 24 09N
+0.80 TEE TEC 12 COLD 600UL 103 85 0.30
.94 P2 TWO 16 "09N
+0.17 TEN TEC 12 COLD 600UL 103 87 0.31 96 P2 TWD 17 09H
-0.06 TEH TEC 12 COLD 600UL 103 97 0.17 43 P2 TWD 9 09H
-0.72 TEH TEC 10 COLD 600UL 0.40 126 P2 TWD 20 09H
+0.99 TEH TEC 10 COLD 600UL 104 78 0.23 79 P2 TWD 13 09H
+0.84 TEH TEC 2
COLD 600UL 104 88 0.37 118 P2 TWD 17 08H
+0.51 TEH TEC 11 COLD 600UL 105 49 0.25 62 P2 TWD 13 VN2
-0.82 TEH TEC 30 COLD 600UL 105 81 0.27 32 P2 TWD 13 09H
-0.61 TEH TEC 11 COLD 600UL 105 101 0.19 109 P2 TWD 10 VN2
+0.30 TEH TEC 10 COLD 600UL 105 105 0.27 118 P2 TWO 14 VN2
-0.42 TEN TEC 7
COLD
-600UL 105 113 0.24 133 P2 TWO 14 VN2
-0.87 TEN TEC S
COLD 600UL 106 48 0.38 22 P3 TWD 17 DOH
+2.10 TEH TEC 29 COLD I 600UL 106 50 0.37 145 P2 TWD 18 VH2
-0.79 TEH TEC 29 COLD 600UL 0.49 97 P2 TWO 23 VN2
+0.88 TEN TEC 29
.COLD 600UL 0.22 128 P2 TWO 12 VN3
+0.90 TEN TEC 29 COLD 600UL 106 52 0.17 27 P3 TWO 9 DEC
.- 1.85 TEN TEC 29 COLD 600UL 106 64 0.34 134 P2 TWO 18 VC2
-0.72 TEN TEC 33 COLD 600UL 0.22 60 P2 TWD 13 VC2
-0.13 TEH TEC 33 COLD 600UL 0.20 140 P2 TWO 12 VC2
+0.76 TEN TEC 33 COLD 600UL 106 72 0.45 147 P2 TWO 22 VC2
-0.84 TEN TEC 36 COLD 600UL 106 86 0.49 96 P2 TWO 21 VN3
-0.89 TEN TEC 11 COLD 600UL 106 100 0.40 137 P2 TWD 19 09H
-0.78 TEH TEC 9
COLD 600UL 106 112 0.19 122 P3 TWD 12 DEC
-1.89 TEH TEC 6
COLD 600UL 106 120 0.15 90 P3 TWD 9 DBC
+1.66 TEH TEC 5
COLD 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component: S/G 88 Page 20 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY:
deOlinspectionresults.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL f LEG PROBE 106
- 134, 0.69 118 P2 TWD 27 VH2
-0.92 TEC TEH 3
HOT 600UL 107 29 0.43 166 P2 TWD 18 VH2
-0.88 TEC TEH 1
HOT 60OUL 107 31 0.27 51 P2 TWO 12 VH2
-1.00 TEC TEH 1
HOT 60OUL 107 143 0.43 I11 P2 TWD.26 VH2
-0.89 TEC TEH 4
HOT 60OUL.
108 64 0.21 110 P3 TWD 20 DBH
+1.91 TEH TEC 34 COLD 600UL 108 66 0.16 51 P3 TWD 16 DBH
+2.23 TEH TEC 34 COLD 60OUL 108 100 0.41 135 P2 TWD 20 VH2
-0.80 TEH TEC 10 COLD 60OUL 108 144 0.39 146 P2 TWD 18 VH2
- +0.83 TEC TEH 3
HOT 600UL 109 31 0.29 45 P3 TWD 12 DBC
-1.80 TEC TEH 1
HOT 600UL 109 37 0.14 166 P3 TWD 8 DBC
+1.35 TEC TEH 2
HOT 60OUL 109 47 0.21 123 P2 TWDOI1 09C
-0.91 TEH TEC 29 COLD 600UL Ii0 32 0.34 147 P2 TWD 17 02H
-0.98 TEC TEH 2
HOT 600UL 110 38 0.15 146 P3 TWD 6 DBH
+1.69 TEC TEH 1
HOT 60OUL 110 40 0.12 153 P3 TWD 5 DBH
+1.58 TEC TEH 1
HOT 600UL 110 42 0.23 148 P2 TWD 14 VH2
-0.89 TEC TEH 6
HOT 600UL 0.11 152 P2 TWD 7 VH2
+0.94 TEC TEH 6
HOT 600UL 110 98 0.51 93 P2 TWD 24 VH2
-0.85 TEH TEC 10 COLD 600UL 110 140 0.51 150P2 TWD 22 VH2
+0.75 TEC TEH 3
HOT 600UL 110 142 0.31 83 P2 TWO 15 VC2
-1.00 TEC TEH 3
HOT 60OUL 111 33 0.39 142 P2 TWD 16 VH2
-0.83 TEC TEH 1
HOT 600UL 111 35
, 0.76 89 P2 TWD 26 VH2
-0.99 TEC TEH 1
HOT 600UL 111 37 0.46 121 P2 TWO 18 VH2
-0.94 TEC TEH 1
HOT 600UL 111 39 0.42 86 P2 TWD 17 VH2
-0.96 TEC TEH 1
HOT 600UL 111 43 0.49 93 P2 TWD 23 VH2
-1.04 TEC TEH 6
HOT 600UL 111 107 0.57 123 P2 TWD 23 VH2
-0.63 TEH TEC 7
COLD 600UL 112 52 0.43 25 P3 TWD 21 DBH
+1.98 TEH TEC 30 COLD 600UL 112 64 0.30 96 P2 TWD 14 VH2
-0.89 TEH TEC 34 COLD 600UL 0.24 12 P3 TWD 21 DBH
+1.73 TEH TEC 34 COLD 600UL 112 86 0.17 62 P2 TWD 10 08H
+1.00 TEH TEC 12 COLD 600UL 112 122 0.49 72 P2 TWO 23 04C
-0.90 TEH TEC 4
COLD 600UL 112 132 0.28 72 P2 TWO 20 VC2
-0.92 TEC TEH 4
HOT 600UL 0.31 42 P2 TWD 21 VC3
+0,64 TEC TEH 4
HOT 600UL 113 37 0.39 146 P2 TWD 19 VH2
-1.00 TEC TEH 2
HOT 600UL 113 39 0.44 103 P2 TWD 21 VH2
-0.98 TEC TEH, 2
HOT 600UL 113 41 0.22 171 P3 TWO 11 DBH
+2.09 TEC TEH 6
HOT 600UL 113 81 0.24 117 P3 TWD 10 DBH
+1.68 TEH TEC 11 COLD 600UL 113 111 0.52 40 P2 TWD 21 09H
-1.21 TEH TEC 7
COLD 600UL 113 117 0.17 48 P3 TWD 10 DBH
+1.79 TEH TEC 5
COLD 600UL 114 34 0.52 61 P3 TWO 20 DBC
+1.86 TEC TEH 1
HOT 600UL 114 42 0.12 146 P3 TWD 7 DBH
+1.84 TEC TEH 6
HOT 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component:
S/G 88 Page 21 of 27 (de0l) Post-U3Cl5 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY:
deOlinspectionresults.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE
=----------------------=----------------------------=
=---------=-----------------
114 84 0.19 134 P3 TWD 8 DBH
+1.84 TEH TEC 11 COLD 60OUL 114 92 0.39 96 P3 TWD 22 DBH
+1.88 TEH TEC 14 COLD 600UL 114 94 0.23 17 P3 TWD 15 DBH
-0.49 TEH TEC 14 COLD 600UL 114 96 0.31 153 P3 TWD 17 DBH
+1.76 TEH TEC 9
COLD 600UL 0.48 104 P2 TWD 20 VH2
-0.82 TEH TEC 9
COLD 600UL 114 110 0.32 118 P2 TWD 16 VH2
-0.72 TEH TEC 8
COLD 600UL 114 112 0.40 94 P2 TWD 20 VH2
-0.80 TEH TEC 5
COLD 600UL 114 126 0.33 113 P2 TWO 17 VC2
-0.89 TEN TEC 4
COLD 600UL 114 128 0.41 112 P2 TWD 20 VN2
-0.91 TEH TEC 4
COLD 600UL 114 138 0.47 104 P2 TWD 21 VH2
-0.90 TEC TEN 3
NOT D 60UL 115 39 0.30 93 P2 TWD 13 VH2
-0.99 TEC TEH 1
HOT 600UL 115 107 0.23 8
P3 TWO 11 DEN
+2.22 TEN TEC 7
COLD 600UL 115 133 0.35 67 P2 TWD 23 VHI
+0.96 TEC TEH 4
HOT 600UL 116 54 0.32 33 P3 TWO 15 DEN
+2.11 TEN TEC 31 COLD 600UL 116 64 0.15 78 P3 TWD 15 DBH
+2.20 TEH TEC 34 COLD 600UL 116 90 0.18 143 P3 TWO 10 DEN
+1.50 TEN TEC 13 COLD 600UL 117 43 0.27 155 P2 TWD 13 VH2
-0.98 TEC TEH 7
HOT 600UL 118 40 0.31 132 P3 TWO 13 DEN
-1.54 TEC TEN 1
NOT 600UL 118 48
.0.42 137 P2 TWO 20 VN1
-0.57 TEN TEC 30 COLD 600UL 118 54 0.30 11 P3 TWD 24 DBH
+.177 TEH TEC 32 COLD 600UL 118.
92 0.44 54 P3 TWO 24 DEN
+2.00 TEN TEC 14 COLD 600UL 119 37 0.16 95 P3 TWO 7 DEC
-1.33 TEC TEN 1
NOT 600UL 119 45 0.52 1i1 P2 TWO 23 VNI
+0.85 TEC TEN 6
NOT 600UL 119 79 0.12 70 P3 TWO 7 DEN
+0.13 TEN TEC 1
COLD 600UL 119 87 0.19 39 P3 TWD 13 DBH
+0.51 TEH TEC 12 COLD 600UL 119 91 0.37 72 P3 TWD 17 DBH
+1.99 TEH TEC 13 COLD 600UL 120 42 0.21 92 P3 TWO 10 DEC
+1.80 TEC TEN 5
NOT 600UL 120 44 0.42 126 P2 TWD 18 VHN
-1.00 TEC TEH 7
HOT 600UL 120 56 0.45 116 P2 TWD 21 iOH
+1.67 TEN TEC 31 COLD 600UL 120 66 0.48 65 P2 TWD 20 VHl
-0.78 TEH TEC 34 COLD 600UL 120 114 0.26 95 P3 TWO 16 DEN
+0.59 TEN TEC 6
COLD 600UL 120 120 0.46 113 P2 TWO 22 iON
-1.73 TEN TEC 6
COLD 600UL 120 124 0.39 79 P2 TWO 19 iON
+1.45 TEN TEC 4
COLD SCOUL 121 59 0.19 12 P3 TWD 10 DBC
- 1.62 TEH TEC 31 COLD 600UL 121 65 0.37 51 P2 TWD 19 VNH
+0.82 TEH TEC 33 COLD 60OUL 121 81 0.46 64 P2 TWO 22 VN1
+0.63 TEN TEC 3
coLD 6000L 121 89 0.17 64 P3 TWD 12 DBE
-1.13 TEN TEC 14 COLD 600UL 0.13 149 P3 TWD 9 DBH
+0.36 TEH TEC 14 COLD 600UL 121 91 0.20 89 P3 TWD 13 DBH
+1.96 TEH TEC 14 COLD 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name:
SONGS Unit 3 Component:
S/G 88 Page 22 of 27 (de0l)
Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de01_inspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 121 117 0.33 132 P2 TWD 18 VH2
-0.73 TEH TEC 5
COLD 600UL 121 121 0.09 15 P2 TWD 6 10H
+1.16 TEN TEC 5
COLD 600UL 122 46 0.49 83 P2 TWD 20 VC2
+0.89 TEC TEH 7
HOT 600UL 122 48 0.22 63 P2 TWD 12 VHN
+0.57 TEN TEC 30 COLD 600UL 122 52 0.34 74 P2 TWD 17 VH1
+0.98 TEH TEC 29 COLD 600UL 122 86 0.25 115 P3 TWD 10 DBH
+1.75 TEH TEC 11 COLD 600UL 122 110 0.30 154 P2 TWD 16 VHl
-0.88 TEH TEC 8
COLD 600UL 122 114 0.23 97 P2 TWD 13 VH1
+0.68 TEH TEC 6
COLD 600UL 122 128 0.35 98 P2 TWD 18 VH2
-0.89 TEH TEC 4
COLD 600UL 123 43 0.28-132 P2 TWD 13 08C
+0.89 TEC TEH 7
HOT 600UL 123 49 0.23 50 P2 TWD 12 VHN
-0.99 TEH TEC 30 COLD 600UL 123 57 0.29 170 P3 TWD 24 DBH
+1.86 TEN TEC 32 COLD 600UL 123 91 0.15 102 P3 TWD 7 DBH
+1.52 TEN TEC 13 COLD 60OUL 123 95 0.64 137 P2 TWD 27 VHl
+0.89 TEH TEC 14 COLD 600UL 123 97 0.39 125 P3 TWD 21 DBH
+1.48 TEH TEC 10 COLD 600UL 124 42 0.26 121 P2 TWD 11 04C
+0.84 TEC TEH 5
HOT 600UL 124 54 0.18 114 P2 TWD 10 VHl r0.99 TEH TEC 29 COLD 60OUL 0.22 113 P2 : TWD 12 10H
+0.70 TEH TEC 29 COLD 60OUL 124 56 0.13 147 P3 TWD 8 DBH
+1.95 TEH TEC 31 COLD 600UL 124 76 0.26 124 P3 TWD 16 DBH
+1.91 TEH TEC 2
COLD 600UL 124 86 0.14 143 P3 TWD 10 DBH
-0.06 TEN TEC 12 COLD 600UL 0.14 81 P3 TWD 9 DBH
+1.79 TEH TEC 12 COLD 600UL 124 96 0.43 50 P3 TWD 23 DOH
+1.69 TEH TEC 10.
COLD 600UL 0.11 30 P3 TWD 6 DBH
+0.88 TEH TEC 10 COLD 600UL 124 110 0.54 106 P2 TWD 25 VPI
-0.17 TEH TEC 6
COLD 600UL 124 112 0.55 73 P2 TWD 25 VHl
+0.63 TEH TEC 6
COLD 600UL 124 116 0.62 150 P2 TWO 27 VHl
-0.78 TEN TEC 6
COLD 600UL 124 120 0.52 120 P2 TWD 24 VH2
-0.88 TEH TEC 5
COLD 600UL 124 134 0.07 146 P3 TWD 5 DBH
+1.65 TEC TEH 4
HOT 600UL 125 49 0.30 97 P2 TWD 16 08C
+0.81 TEH TEC 29 COLD 600UL 125 55 0.42 11 P3 TWD 19 DBH
+1.94 TEH TEC 31 COLD 600UL 125 67 0.34 52 P2 TWD 18 VHl
+0.97 TEH TEC 33 COLD 600UL 125 93 0.49 93 P3 TWD 21 DBH
+1.63 TEN TEC 13 COLD 600UL 125 97 0.24 50 P3 TWD 12 DBH
+1.64 TEH TEC 9
COLD 600UL 125 99 0.24 54 P3 TWD 12 DBH
+0.59 TEH TEC 9
COLD 600UL 0.27 109 P3 TWD 13 DBH
+1.57 TEH TEC 9
COLD 600UL 125 115 0.28 154 P2 TWD 16 VHl
+0.74 TEH TEC 5
COLD 600UL 126 52 0.41 140 P2. TWD 20 VHl
+0.83 TEH TEC 29 COLD 60OUL.
126 56 0.18 69 P2 TWD 11 VHl
-0.91 TEH TEC 31 COLD 600UL 126 60 0.56 121 P2 TWD 25 VHl
-0.91 TEH TEC 32 COLD 600UL
AREVA NP Inc 10/31/08 11:18:03 Customer Name: SONGS Unit 3 Component:
S/G 88 Page 23 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de0l inspectionresults.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE
=--==------------=----
126 62 0.31 127 P2 TWD 17 VHl
-1.10 TEH TEC 32 COLD 600UL 0.20 70 P2 TWD 11 VHl
+0.02 TEH TEC 32 COLD 600UL 126 66 0.41 93 P2 TWD 21 VHE
-0.63 TEH TEC 33 COLD 60OUL 0.25 62 P2 TWD 15 VHI
+0.95 TEH TEC 33 COLD 600UL 126 80 0.38 134 P2 TWD 19 VHE
-0.90 TEH TEC 4
COLD 60DUL 126 96 0.39 138 P2 TWD 20 VHE
-0.74 TEH TEC 10 COLD 600UL 126 l00 0.33 99 P2 TWD 17 VHE
-0.88 TEH TEC 10 COLD 60OUL 126 104 0.36 138 P2 TWD 18 VHE
-0.87 TEH TEC 8
COLD 600UL 126 106 0.45 125 P2 TWD 22 VHE.
-0.68 TEH TEC 8
COLD 600UL 126 108 0.44 146 P2 TwD 21 VHE
-1.12 TEH TEC 8
COLD 600UL 0.24 119 P2 TWD 13 VHE
+0.21 TEH TEC 8
COLD 60OUL 126 114 0.28 113 P2 TWD 16 VHE
+0.00 TEH TEC.
6 COLD 600UL 126 118 0.26 161 P2 TWD 15 VHE
+0.85 TEH TEC 5
COLD 600UL 126 124 0.33 129 P2 TWD 17 VHE
-0.74 TEH TEC 4
COLD 60OUL 127 85 0.28 115 P2 TWD 16 VH2
+0.88 TEH TEC 12 COLD
- 600UL 127 103 0.33 115 P2 TWD 17 VHE
-0.70 TEH TEC 9
COLD 600UL 0.68 97 P2 TWD 27 VHE
+0.89 TEH TEC 9
COLD 600UL 127 107 0.24 46 P2 TWD 12 VHI
-0.08 TEH TEC 7
COLD 60OUL 127 Ill 0.29 150 P2 TWD 16 VHE
-0.88 TEH TEC 5
COLD 60OUL 127 115 0.38 95 P2 TWD 19 VHE
+0.87 TEH TEC 5
COLD 600UL 127 119 0.20 138 P2 TWD 12 VHE
-0.96 TEH TEC 5
COLD 600UL 128 46 0.23 134 P2 TWD 12 02C
+0.90 TEC TEHE 6 HOT 600UL 128 58 0.37 106 P2 TWD 19 VH3
+0.78 TEH TEC 32 COLD 600UL 0.16 26 P2 TWD 10 VH3
+0.30 TEH TEC 32 COLD 60OUL 128 78 0.44 142 P2 TWD 21 VHE
-0.92 TEH TEC 2
COLD 600UL 128 84 0.32 143 P2 TWD 15 VHE
+0.91 TEH TEC 11 COLD
.600UL 0.34 153 P2 TWD 16 VH2
-0.91 TEH TEC 11 COLD 60OUL 128 100 0.52 147 P2 TwD 24 VHE
-0.82 TEH TEC 10 COLD 600UL 0.34 148 P2 TWD 17 VH2
-0.84 TEH TEC 10 COLD 600UL 128 106 0.48 144 P2 TWD 23 VHE
-0.82 TEH TEC 8
COLD 600UL 128 130 0.20 73 P2 TWD 15 08C
-0.98 TEC TEH 4
HOT 600UL 129 75 0.38 118 P2 TWD 19 VHE
+0.82 TEH TEC 35 COLD 60OUL 129 99 0.53 72 P2 TWD 23 10H
-0.25 TEH TEC 9
COLD 600UL 129 129 0.37 131 P3 TWD 18 DBH
+2.01 TEH TEC 3
COLD 600UL 130 54 0.28 146 P3 TWD 14 DBH
-1.81 TEH TEC 29 COLD 600UL 130 56 0.14 152 P3 TWD 8 DBH
-1.67 TEH TEC 31 COLD 600UL 130 68 0.39 143 P2 TWD 20 VHE
-0.78 TEH TEC 33 COLD 600UL 0.47 147 P2 TWD 23 VH2
-0.89 TEH TEC 33 COLD 600UL 130 72 0.24 146 P2 TWD 13 VHE
-0.84 TEH TEC 35 COLD 60OUL 130 74 0.46 127 P2 TWD 22 VHI
-0.87 TEH TEC 35 COLD 60OUL 130 76 0.56 115 P2 TWD 25 VHE
+0.76 TEH TEC 2
COLD 600UL 130 78 0.32 136 P2 TWD 17 VHE
-0.90 TEH TEC 2
COLD 600UL
AREVA NP Inc 10/31/08 11:18:04 Customer Name:
SONGS Unit 3 Component: S/G 88 Page 24 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: deOlinspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE
.............------------------------------------- =--------------=-----------------
130 84 0.58 119 P2 TWD 26 VH1
-0.99 TEH TEC 12 COLD 600UL 0.23 113 P2 TWD 13 VHN
+0.74 TEH TEC 12 COLD 60OUL 130 88 0.28 78 P2 TWD 16 VHN
+0.11 TEH TEC 12 COLD 600UL 0.15 154 P2 TWD 9 VHN
+0.69 TEH TEC 12 COLD 600UL 130 106 0.45 141 P2 TWD 22 VHN
-0.80 TEH TEC 8
COLD 60OUL 0.24 82 P2 TWD 13 VHN
-0.22 TEH TEC 8
COLD 600UL 130 128 0.42 90 P2 TWD 20 VH2
-0.95 TEH TEC 4
COLD 600UL 131 51 0.55 131 P2 TWD 25 VH2
+0.82 TEH TEC 54 COLD 60OUL 0.52 111 P3 TWD 22 DBC
+1.79 TEH TEC 54 COLD 600UL 131 55 0.23 17 P3 TWO 12 DON
+1.63 TEN TEC 54 COLD 600UL 131 57 0.21 124 P3 TWD 11 DBH
+2.05 TEH TEC 54 COLD 600UL 131 83 0.29 76 P2 TWD 16 VNH
-1.01 TEH TEC 54 COLD 600UL 0.34 38 P2 TWD 18 VHl
-0.80 TEH TEC 54 COLD 600UL 131 89 0.18 93 P2 TWD 10 VHI
-0.94 TEH TEC 52 COLD 600UL 131 97 0.17 29 P2 TWD 10 VH1
-0.92 TEH TEC 52 COLD 600UL 0.29 97 P2 TWD 15 VHI
+0.92 TEH TEC 52 COLD 60OUL 132 54 0.20 119 P3 TWO 10 DON
-1.51 TEN TEC 54 COLD
- 600UL, 132 56 0.13 59 P3 TWO 7 DON
-1.92 TEN TEC 54 COLD P600UL 132 70 0.18 100 P2 TWO 11 VN1
+0.21 TEN TEC 54 COLD 600UL 0.62 109 P2 TWD 27 VHN
+0.71 TEH TEC 54 COLD 600UL 132 96 0.20 149 P2 TWD 12 VNH
+0.67 TEH TEC 52 COLD 600UL 0.41 121 P2 TWO 20 VNT
- 0.8 5 TEN TEC 52 COLD I600UL 132 100 0.46 137 P2 TWO 22 VHIi
-0.92 TEN TEC 52 COLD 600UL 132 118 0.09 141 P3 TWO 4 DON
+1.74 TEN TEC 52 COLD 6OdUL 133 S1 0.19 59 P2-TWO 11 08C
+0.85 TEN TEC 55 COLD 600UL 133 57 0.30 19 P3 TWD 16 DBH
-1.38 TEH TEC 55 COLD 600UL 133 61 0.12 152 P3 TWO 7 DOC
-1.49 TEN TEC 55 COLD 600UL 133 25 0.42 53 P2 TWO 20 1ON
+0.79 TEN TEC 55 COLD 600UL 133 91 0.22 112 P2 TWD 13 VHN
+0.89 TEH TEC 53 COLD 600UL 0.13 117 P2 TWD 8 VHI
-0.86 TEH TEC 53 COLD 600UL 133 101 0.21 155 P2 TWO 12 VN1
-1.00 TEN TEC 53 COLD 600UL.
134 58 0.27 145 P2 TWD 15 VH1
-0.92 TEH TEC 54 COLD 600UL 0.33 93 P2 TWO 18 VC1
-0.94 TEN TEC 54 COLD 600UL 0.32 149 P2 TWD 17 VC2
-0.77 TEH TEC 54 COLD 600UL 134 60 0.44 85 P3 TWO 21 DON
+1.66 TEN TEC 55 COLD 600UL 134 74 0.33 91 P2 TWO 18 VN1
-0.90 TE-TEC 54 COLD 600UL 134 88 0.61 134 P2 TWD 26 VHI
-0.87 TEH TEC 52 COLD S60UL 134 90 0.18 127 P2 TWD 10 V4 H
+0.83 TEH TEC 52 COLD 600UL 134 94 0.33 142 P2 TWO 18 VN1
-0.87 TEN TEC S53 COLD
.600UL 0.20 105 P2 TWD 12 V0l
+0.91 TEH TEC 53 COLD 600UL 134 96 0.43 144 P2 TWD 22 VHl
-0.91 TEH TEC 53 COLD 600UL 134 102 0.32 152 P2 TWD 17 V02
+0.83 TEH TEC 55 2
COLD 60OUL 134 110 0.S4 151 P2 TWD 25 VHl
-0.89 TEH TEC 53 COLD 600UL 134 120 0.35 107 P2 TWD 18 VHl
-0.65 TEH TEC 53 COLD 600UL
AREVA NP Inc 10/31/08 11:18:04 Customer Name:
SONGS Unit 3 Component: S/G 88 Page 25 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI*,
- SVI, TWD QUERY: de0l inspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 135 57 0.35 11 P3 TWD 17 DBH
+2.13 TEH TEC 54 COLD 600UL 135 97 0.43 80 P2 TWD 21 VH1
-0.86 TEH TEC 52 COLD 600UL 136 62 0.33 109 P2 TWD 17 VH2
-1.24 TEH TEC 55 COLD 600UL 136 70 0.57 52 P2 TWD 24 VHN
+1.00 TEH TEC 55 COLD 600UL 136 76 0.49 56 P2 TWD 22 VH1
-0.94 TEH TEC 55 COLD 600UL
.0.45 114 P2 TWD 21 VH1
+0.60 TEH TEC 55 COLD 600UL 0.42 79 P2 TWD 20 VH2
-1.18 TEH TEC 55 COLD 600UL 136 78 0.54 124 P2 TWD 24 VH1
-0.98 TEH TEC 55 COLD 60OUL 136 82 0.44 143 P2 TWD 21 VH1,
-1.12 TEH TEC 55 COLD 600UL 136 84 0.31 67 P2 TWO 17 VH1
-0.92 TEN TEC 54 COLD 600UL 0.31 89 P2 TWD 17 VH1
+0.57 TEH TEC 54 COLD 600UL 136 100 0.30 133 P2 TWD 16 VN1
-0.96 TEN TEC 52 COLD 600ut 0.18 157 P2 TWD 10 VHN
+0.73 TEH TEC 52 COLD 60OUL 136 108 0.43 135 P2 TWO 21 VH1
-0.94 TEH TEC 52 COLD 600UL 0.31 108 P2 TWD 16 VHI
+0.73 TEH TEC 52 COLD 600UL 136 112 0.44 49 P2 TWD 21 VHN
-0.65 TEH TEC 53 COLD 600UL 136 118 0.21 29 P3 TWO 14 DEN
+1.06
'TEN TEC 53 COLD 600UL 137 59 0.35.9 P3 TWO 18 DEN
+1.92 TEN TEC 55 COLD 600UL 0.44 109 P3 TWO 21 DEC
+2.00 TEN TEC 55 COLD 600UL 137 67 0.47 18 P3 TWO 22 DEN
+2.08 TEN TEC 55 COLD 600UL 137 69 0.20 147 P2 TWD 11 VHN
+0.85 TEHWTEC 55 COLD 600UL 0.36 144 P2 TWD 18 VH1
-0.89 TEH TEC 55 COLD 600UL 137 85 0.23 46 P2 TWO 13 09N
+0.85 TEN TEC 55 coLD 600UL 0.07 152 P2 TWD 4 09H
-0.90 TEH TEC 55 COLD 600UL 137 89 0.15 142 P2 TWD 9 VNH
-0.91 TEH TEC 53 COLD 600UL 0.30 130 P2 TWD 15 VN1
+0.83 TEH TEC 53 COLD 600UL 137 91 0.12 7
P3 TWD 9 DBC
+1.68 TEH TEC 53 COLD 600UL 137 93 0.28 61 P2 TWD 16 VHI
-0.91 TEH TEC 53 COLD 600UL 137 103 0.58 65 P2 TWO 25 VHN
-0.89 TEH TEC 52 COLD 60OUL 0.42 43 P2 TWO 20 VNH
+0.65 TEH TEC 52 COLD 600UL 138 68 0.20 61 P3 TWD 10 DNH
+2.09 TEH TEC 54 COLD 600UL 138 70 0.17 28 P3 TWO 9 DEN
+2.23 TEN TEC 54 COLD 600UL 138 76 0.30 91 P2 TWD 16 VH1
-0.19 TEH TEC 54 COLD 600UL 0.17 164 P2 TWD 10 VH1
+0.83 TEH TEC 54 COLD 600UL 0.49 134 P2 TWO 23 VN2
-0.79 TEN TEC 54 COLD 600UL 136 78 0.37 153 P2 TWO 19 VN2
-0.83 TEN TEC 54 COLD 600UL 138 94 0.35 83 P2 TWD 17 VN1
+0.86 TEH TEC 52 COLD 600UL 139 93 0.22 133 P2 TWD 13 VCI
+0.89 TEH TEC 53 COLD 60OUL 139 111 0.35 126 P3 TWO 16 DEN*
+1.69 TEN TEC 52 COLD*
600UL 140 64 0.39 147 P2 TWD 19 VH2
-0.83 TEH TEC 55 COLD 600UL 140 66 0.25 30 P3 TWD 14 DEH
-1.62 TEH TEC 55 COLD 600UL 140 72 0.35 21 P3 TWD 17 DBH
+1.54 TEH TEC 54 COLD G60UL 140 76 0.67 123 P2 TWD 27 VHIl
-0.96 TEH TEC 55 COLD 600UL 0.4,4 149 P2 TWD 21 VH2
-0.8S TEH TEC 55 COLD 600UL
- m.
AREVA NP Inc 10/31/08 11:18:04 Customer Name:
SONGS Unit 3 Component: S/G 88 Page 26 of 27 (de0l) Post-U3CT5 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY:
de0a inspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 140 106 0.24 71 P3 TWD 16 DBH
+2.14 TEH TEC 53 COLD 600UL 141 63 0.32 139 P2 TWD 17 08H
+0.75 TEH TEC 55 COLD 60OUL
-0.35 79 P3 TWD 18 DBH
-1.88 TEH TEC 55 COLD 600UL 0.37 130 P2 TWD 18 09H
-0.29 TEH TEC 55 COLD 600UL 0.37 140 P2 TWD 18 VHl
-0.85 TEH TEC 55 COLD 600UL 141 67 0.31 66 P3 TWO 16 DON
+1.72 TEN TEC 55 COLD 600UL 141 69 0.34 4
P3 TWD 17 DBC
+1.53 TEH TEC 54 COLD 600UL 0.22 50 P3 TWO 11 DBN
+1.84 TEN TEC 54 COLD 600UL 141 71 0.23 92 P3 TWD 13 DBO
+1.73 TEH TEC 55 COLD 600UL 141 75 0.29 154 P3 TWO 15 DON
-1.69 TEN TEC 55 COLD 600UL 0.22 34 P3 TWD 12 DBH
+1.70 TEH TEC 55 COLD 60OUL 141 81 0.23 58 P3 TWD 13 DBH
-2.22 TEH TEC 55 COLD 600UL
_141 83 0.58 118 P2 TWO 25 VC1
+0.90 TEN TEC 55 COLD 600UL 141 93 0.22 152 P2 TWO 13 VC1
+0.87 TEN TEC 53 COLD 600UL 141 97 0.32 119 P2 TWO 17 VN2
+1.00 TEN TEC 53 COLD 600UL 141 113 0.22 19 P3 TWD 15 DBH
+2.07 TEH TEC 53 COLD 600UL 0.24 137 P2 TWO 14 09C
+0.71 TEN TEC 53 COLD 6000L 142 72 0.32 147 P3 TWD 17 DBH
-1.82 TEH TEC 55 COLD 600UL 0.30 58 P3 TWD 16 DBH
+1.91 TEH TEC 55 COLD 60OUL 0.55 150 P2 TWD 24 VCt
+0.71 TEH TEC 55 COLD 600UL 142 74 0.29 48 P3 TWO 15 DON
+2.06 TEN TEC 55 COLD 600UL 142 82
.0.67 108 P2 TWO 28 VE2
-0.90 TEN TEC.54 COLD 600UL 142 92 0.32 154 P2 TWD 17 VHI
-0.86 TEH TEC 54 COLD 600UL 142 94 0.18 35 P2 TWO 10 VET
+0.88 TEN TEC 54 COLD 600UL 142 98 0.23 148 P2 TWD 13 VHT
+0.58 TEH TEC 53 COLD 600UL 142 104 0.25 131 P3 TWD 15 DBH
+2.14 TEN TEC 53 COLD 600UL 142 108 0.24 142 P2 TWD 14 VN3
+0.87 TEH TEC 53 COLD 600UL 142 110 0.19 83 P3 TWD 13 DBH
+1.93 TEH TEC 53 COLD 60OUL 143 75 0.31 68 P3 TWD 15 DBH
+1.61 TEN TEC 54 COLD 600UL 143 83 0.16 123 P3 TWO 9 DEC
+2.01 TEN TEC 54 COLD 600UL 143 89 0.20 103 P2 TWO 12 08C
+0.90 TEN TEC 54 COLD 6000L 143 91 0.35 31 P2 TWO 18 VC1
-0.87 TEE TEC 55 COLD SO0UL 143 99 0.15 24 P3 TWO 8 DOC
+1.67 TEE TEC 52 COLD GO0UL 143 101 0.30 62 P2 TWO 16 VCT
-0'.87 TEN TEC 52 COLD 600UL 0.11 37 P3 TWD 6 DEC
+1.73 TEH TEC 52 COLD 600UL 143 105 0.50 28 P3 TWO 27 DOE
+1.71 TEE TEC 53 COLD 600UL 0.40 91 P3 TWO 23 DEC
+1.61 TEN TEC 53 COLD 6000L 0.40 67 P3 TWO 22 DOE
-1.81 TEN TEC 53 COLD 600UL 144 80 0.52 148 P3 TWD 23 DBC
+2.06 TEH TEC 55 COLD 600UL 144 82 0.61 121 P2 TWD 26 VH2
-0.96 TEH TEC 55 COLD 600UL 0.13 73 P3 TWO 8 DEC
+2.02 TEE TEC 55 COLD CO0UL 0.27 124 P3 TWD 15 DOH
+1.77 TEH TEC 55 COLD 600UL 144 90 0.17 178 P3 TWD 10 DEC
+2.01 TEH TEC 55 COLD 60OUL 0.20 101 P2 TWD 12 06C
+0.98 TEH TEC 55 COLD 600UL 0.19 82 P2 TWD 11 06C
-0.89 TEH TEC 55 COLD 600UL 144 892 0.29 134 P2 TWD1 12C0C
+0.96 TEN TEC 54 COLD 600UL 144 92 0.29 34 P2 TWD 16 10C
-0.96 TEH TEC 54 COLD 60OUL
'I AREVA NP Inc 10/31/08 11:18:04 Customer Name:
SONGS Unit 3 Component:
S/G 88 Page 27 of 27 (de0l) Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de01_inspection_results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE
==I
=
=
=====-==========
:=
=
-===*
=
144 96 0.33 68 P3 TWD 20 DBH
+1.99 TEH TEC 53 C OLD 60OUL 0.27 33 P2 TWD 15 VHN
+0.23 TEH TEC 53 COLD 600UL 0.81 94 P2 TWD 32 VHN
+0.85 TEH TEC 53 COLD 600UL 144 102 0.28 54 P3 TWD 18 DBH
+2.05 TEH TEC 53 COLD 600UL 0.44 56 P2 TWD 22 VC3
+0.83 TEH TEC 53 COLD 600UL 145 73 0.55 96 P3 TWD 24 DBH
+1.87 "TEH TEC 55 COLD
. 600UL 145 91 0.09 150 P3 TWD 5 DBH
+1.94 TEH TEc 54 COLD 600UL 0.47 84 P2 TWD 23 VCl
-0.96 TEN TEC 54 COLD 600UL 145 93 0.31 54 P2 TWD 16 VC1,
+0.27 TEH TEC 55 COLD 600UL 0.53 89 P3 TWD 23 DBC
+1.59 TEH TEC 55 COLD 60OUL 145 95 0.16 36 P3 TWD 8 DBC
-1.45 TEH TEC 54 COLD 60OUL 145.
101 0.26 47 P3 TWD 17 DBH
-1.41 TEH TEC 53 COLD 600UL 146 92 0.47 89 P3 TWD 22 DBC
+1.65 TEH TEC 55 COLD 60OUL 0.36 72 P2 TWD 18 VCl
+1.02 TEH TEC 55 COLD 600UL 0.39 111 P2 TWD 19 10C
+0.79 TEH TEC 55 COLD 600UL 147 91 0.68 105 P2 TWD 27 VCI
-0.91 TEH TEC 55 COLD 60OUL 0.64 109 P2 TWD 26 VCI
+0.68 TEH TEC 55 COLD 600UL 147 93 0.70 136 P2 TWD 28 VH2
-0.68 TEH TEC 55 COLD 600UL Total. Tubes
- 802 Total *Records: 1126
Inspection of Steam Generator Tubes Special Report Appendix 4 Page 1 of 17 Appendix 4 Tube Inspection Summary Steam Generator E-089
AREVA NP Inc 10/31/08 10:35:55 Customer Name:
SONGS Unit 3 Component: S/G 89 Page 2 of 17 (de0l) Post-U3C!5 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de0linsnectionresults ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 14 110 0.24 28 P3 TWD 11 DBH
-1.95 TEH TEC 54 COLD 600UL 21 67 0.61 81 P2 TWD 22 VSM
-0.72 TEH TEC 33 COLD 600UL 22 66 0.25 42 P2 TWD 11 VSM
-0.82 TEH TEC 30 COLD 600UL 22 134 0.24 127 P2 TWD 12 VSM
-0.72 TEC TEH 20 HOT 600UL 24 22 0.24 141 P2 TWD 14 VSN
-0.78 TEC TEH 18 HOT 60OUL 24 68 0.41 49 P3 TWD 15 DBH
+1.77 TEH TEC 32 COLD 60OUL 0.25 76 P2 TWD 12 VSM
-0.77 TEH TEC 32 COLD 600UL 25 65 0.44 117 P2 TWD 16 VSM
+1.17 TEH TEC 31 COLD 600UL 25 67 0.34 100 P2 TWD 14 VSM
-1.18 TEH TEC 33 COLD 600UL 25 115 0.70 106 P2 TWD 26 VSM
+0.82 TEN TEC 53 COLD 600UL 26 48 0.75 32 P2 TWD 26 VSM
-1.04 TEH TEC 28 COLD 600UL 27 39 0.27 29 P1 SCI TSH
-0.13 TSH TSH 56 HOT 58OPP 29 107 0.36 92 P3 TWD 15 DBC
-1.80 TEH TEC 55 COLD 600UL 30 122 0.28 62 P2 TWD 12 05H
+0.49 TEH TEC 51 COLD 600UL 31 51 0.34 125 P2 TWD 13 06H
+0.78 TEH TEC 31, COLD 60OUL 31 125 0.42 24 P1 SCI TSH
+0.02 TSH TSH 49 HOT 580PP 31 167 0.26 16 P2 TWD 13 VSM
+0.99 TEC TEH 37 HOT 60OUL 32 118 0.40 106 P2 TWD 17 VSM
-0.86 TEH TEC 53 COLD 600UL 33 61 0.74 46 P2 TWD 23 VSM
-0.04 TEH TEC 31 COLD 600UL 0.60 135 P2 TWD 20 VSM
+0.89 TEH TEC 31 COLD 60OUL 33 171 0.24 127 P2 TWD 10 01C
-0.12 TEC TEH 36 HOT 600UL 34 148 0.43 103 P2 TWD 19 VS14
-0.81 TEC TEH 29 HOT 600UL 35 113 0.46 84 P2 TWD 19 VSM
-0.92 TEH TEC 53 COLD
.60UL 0.29 22 P2 TWD 13 VSM
-0.11 TEH TEC 53 COLD 600UL 36 30 0.36 99 P2 TWD 18 VSM
+0.80 TEC TEH 18 HOT 600UL 36 34 0.14 60 P2 TWD 8 VSM
+0.80 TEC TEH 14 HOT 60OUL 36 36 0.38 83 P2 TWD 16 01H
.+0.78 TEC TEN 15 HOT 60000 36 50 0.16 164 P3 TWD 9 DB0
+2.00 TEN TEC 33 COLD 600UL 36 68 0.51 12 2
MAI TSH
-1.58 TSH TSH 104 HOT 58OPP 36 72 0.51 133 23 TWD 18 D3H
-1.79 TEH TEC 32 COLD 600UL 36 104 0.26 162 P3 TWD 11 DEH
+1.57 TEH TEC 55 COLD 600UL 0.21 5
P3 TWD 9 DBC
+1.21 TEN TEC 53 COLD 600UL 36 144 0.34 111 P2 TWD 16 VSM
-0.82 TEC TEH 24 HOT 60OUL 36 146 0.34 68 22 TWD 16 VSM
+0.78 TEC TEH 24 HOT 600UL 37 53 0.42 104
?2 TWD 17 VSM
-0.04 TEH TEC 33 COLD 600UL 37 145 0.48 100 P2 TWD 21 VSM
+0.82 TEC TEH 24 HOT 600UL 37 157 0.25 42 P2 TWD 12 VSM
+0.80 TEC TEH 32 HOT 600UL 37 171 0.61 121 P2 TWD 23 VSM
-0.84 TEC TEH 36 HOT 600UL 38 28 0.34 103 P2 TWD 14 VSM
-0.83 TEC TEH 19 HOT 600UL 0.41 44 P2 TWD 17 VSM
+0.81 TEC TEN 19 HOT 600UL
............................. L.................................................................
AREVA NP inc Customer Name:
SONGS Unit 3 10/31/08 10:35:55 Component:
S/G 89 Page 3 of 17 (de0l) Post-U3C!5 Insoection Results
,AI, MCI, WE4T, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de0! insoection results cry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 38 38 0.35 27 P2 TWD 15 VSM
-0.02 TEC TEH 15 HOT 600UL 38 56 0.23 131 P2 TWD 11 06H
+0.50 TEH TEC 34 COLD
ý 600UL 38 128 0.22 138 P2 TWD 9 VSM
+0.86 TEH TEC 50 COLD 60OUL 38 162 0.27 95 P2 TWD 13 VSM
-0.06 TEC TEH 33 HOT 60OUL 0.31 124 P2 TWD 15 VSM
-0.82 TEC TEH 33 HOT 600UL 39 41 0.28 75 P3 TWD 14 DBH
-1.62 TEC TEH 10 HOT 600UL 39 43 0.47 115 P2 TWD 19 VSM
+0.91 TEC TEH 11 HOT 60OUL 39 69 0.45 151 P2 TWD 17 VSM
+0.65 TEH TEC 35 COLD 60OUL 39 101 0.37 32 P3 TWD 13 DBH
-1.49 TEH TEC 20 COLD 60OUL 39 117 0.32 126 P2 TWD 13 VSM
-0.81 TEH TEC 54 COLD 60OUL 0.28 137 P2 TWD 11 VSM
+0.80 TEH TEC 54 COLD 600UL 39 147 0.41 129 P2 TWD 18 VSM
+0.81 TEC TEH 28 HOT 60OUL 40
.66 0.17 22 P3 TWD 9
DBC
+1.68 TEEH TEC 35, COLD 600UL 40 68 0.46 20 22 TWD 19 VS7
-0.78' TEH TEC 34 COLD 60OUL 40 146 0.43 53 P2 TWD 19 VSM
+0.78 TEC TEH 24 HOT 60OUL 40 162 0.39 118 P2 TWD 17 VSM
-0.73 TEC TEH 32 HOT 600UL 0.22 36 P2 TWD 11 VSM
-0.01 TEC TEH 32 HOT 600UL 40 168 0.67 45 P2 TWD 24 VSM
+0.90 TEC TEH 36 HOT 60OUL 0.40 49 P2 TWO 16 VSM
-0.08 TEC TEH 36 HOT 600UL 0.20 157 P2 TWD 8 VSM
-0.69 TEC TEH 36 HOT 60OUL 40 170 0.42 140 P2 TWD 18 01C
+0.89 TEC TEH 37 HOT 60OUL 41 7
0.46 81 P2 TWD 21 VSM
+0.88 TEC TEH 30 HOT 60OUL 0.41 114 P2 TWD 19 VSM
-0.78 TEC TEH 30 HOT 600UL 41 39 0.22 167 P3 TWD 12 DBC
+1.52 TEC TEH 10 HOT 600UL 41 47 0.44 127 P2 TWD 18 VSM
+0.00 TEH TEC 33 COLD 600UL 0.44 129 P2 TWD 18 VSM
+0.82 TEH TEC 33 COLD 60OUL 41 55 0.29 86 P2 TWD 13 VSM
-0.84 TEH TEC 34 COLD 600UL 41 59 0.55 91 P2 TWD 21 VSM
-0.73 TEH TEC 34 COLD 600UL 0.54 124 P2 TWD 21 VSM
+0.00 TEH TEC 34 COLD 600UL 4a 0.63 32 P2 TWD 24 VSM
-0.71 TEH TEC 34 COLD 600UL 0.76
- 72.
P2 TWD 26 VSy
+0.04 TEE TEC 34 COLD 600UL 41 69 0.55 41 103 0.66 41 107 0.23 0.28 41 113 0.50 0.21 41 123 0.5E 0.25 87 P2 TWD 21 V7SM
+0.80 TEH TEC 34 COLD 60OUL 104 P3 TWD 24 DBC
+1.75 TEH TEC 55 COLD 60OUL 23 P2 TWD 14 66 P2 TWD 14 124 P2 TWD 18 127 P2 TWD 8
!11 P2 TWD 20 150 P2 TWD 10 41 131 0.57 64 P2 TWD 23 0.56 101 P2 TWD 23 41 157 0.60 123 P2 TWD 23 42 54 0.21 108 P2 TWD 8 42 62 0.43 89 P2 TWD 18 42 144 0.51 87 P2 TWD 21 VSM
-0.54 TEE TE S 5 COLD 600UL VSM
+1.08 TEH TEC 55 COLD 600UL VSM
-0.85 TEH TEC 54 COLD 60OUL VSM
-0.12 TEE TEC 54 COLD 60OUL VSM
+0.86 TEH TEC 52 COLD 60OUL VS7
-0.59 TEH TEC 52 COLD 600UL VSM
+0.70 TEC TEH 21 HOT 60OUL VSM
-'.87 TEC TEH 21 HOT 600UL VSM
+0.75 TEC TEH 32 HOT 60OUL VS7
+0.96 TEH TEC 32 COLD 600UL VSW
+0.25 TEH TEC 34 COLD 60OUL v3M
+0.89 TEC TEH 25 HOT 600UL
AREVA NP Inc Customer Name:
SONGS Unit 3 10/31/08 10:35:55 Compohent: S/G 89 Page 4 of 1 (de0!)
Post-U3Cl5 Insoection Results
- MAi, MCI, MIII, MVI,
- SAI, SC,
- SVI, TWD QUERY: de0l insoection-results.arv ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.15 159 P2 TWD 7 VSM
-0.74 TEC TEH 25 HOT 600UL 42 148 0.41 81 P2 TWD 18 VSM
+0.25 TEC TEH 29 HOT 60OUL 42 170 0.30 76 P2 TWD 12 01H
-0.14 TEC TEH 36 HOT 60OUL 43 45 0.36 35 P3 TWD 14 DEH
+1.37 TEC TEH 11 HOT 600UL 43 51 0.31 131 P2 TWD 14 02H
+0.75 TEH TEC 32 COLD 600UL 43 65 0.43 108 P2 TWD 18 VSM
+0.02 TEH TEC 34 COLD 600UL 43 107 0.34 68 P2 TWD 12 VSM
+0.19 TEH TEC 56,
COLD 600UL 0.40 123 P2 TWD 14 VSM
+0.81 TEH TEC 56 COLD 60OUL 0.42 76 P3 TWD 16 DBC
+1.58 TEH TEC 56 COLD 600UL 43 119 0.33 119 P2 TWD 13 VSM
-0.83 TEH TEC 52 COLD 60OUL 0.15 121 P2 TWD 6 VSM
+0.26 TEN TEC 52 COLD 60OUL 43 131 0.51 90 P2 TWD 22 VSM
+0.88 TEC TEH 20 HOT 600UL 43 161 0.30 100 P2 TWD 14 VSM
-0.80 TEC TEH 33 HOT 600UL 44 6
0.50 133 P2 TWD 22 VSM
+0.86 TEC TEH 30 HOT 60OUL 44 66 0.26 151 P2 TWD 10 VSM
+0.61 TEH TEC 37 COLD 60OUL 0.18 127 P3 TWD 7 DBC
+1.65 TEH TEE 37 COLD 60OUL 44 72 0.30 17 P2 TWD 12 VSM
+0.84 TEH TEC 35 COLD 60OUL 0.41 151 P3 TWD 18 DBC
+1.09 TEH TEC 35 COLD 600UL 44 74 0.29 55 P3 TWD 14 DSH
-1.39 TEH TEC 35 COLD 600UL 44 100 0.51 60 P3 TWD 18 DEH
-1.59 TEH TEC 20 COLD 600UL 44 112 0.48 86 P2 TWO 20 VSM
-0.83 TEH TEC 53 COLD 600UL 0.38 110 P2 TWD 17 VSM
+0.06 TEH TEC 53 COLD 600UL 0.25 62 P2 TWD 11 VSM
+0.82 TEH TEC 53 COLD 60SUL 44 114 0.51 111 P2 TWD 21 VSM
+0.90 TEH TEC 53 COLD 600UL 0.51 89 P2 TWD 20 VSM
-0.91 TEH TEE 53 COLD 60OUL 44 128 0'.51 144 P2 TWD 22 VSM
-0.80 TEH TEC 49 COLD 600UL 0.49 114 P2 TWD 21 VSM
+0.79 TEH TEC 49 COLD 600UL 44 134 0.29 80 P2 TWD 14 VSM
-0.76 TEC TEH 20 HOT 600UL 44 158 0.42 108 P2 TWD 18 VSM
+0.88 TEC TEH 32 HOT 600UL 0.35 101 P2 TWD 16 VSM
-0.69 TEC TEH 32 HOT 600UL 45 47 0.27 107 P3 TWD 14 DBH
+/-1.4,9 TEN TEC 33 COLD 600UL 45 119 0.52 127 P2 TWD 20 VSM
-0.83 TEH TEC 51 COLD 600UL 0.51 99 P2 TWD 19 VSM
+0.71 TEH TEC 51 COLD 600UL 45 133 0.18 36 P3 TWD 9 DBC
-1.41 TEC TEH 20 HOT 600UL 0.34 136 P2 TWD 17 VSM
-0.66 TEC TEH 20 NOT 6000L 45 167 0.16 153 P2 TWD 6 VYSM
+0.91 TEC TEH 36 HOT 600UL 45 169 0.39 122 P2 TWD 16 0C
' -0.93 TEC TEH 36 HOT 600UL 46 30 0.26 29 P2 TWDO 11 VY
+0 19 TEC EEP '9 HOT 600UL 48 52 0>27 109 P3 TWO 10 DEN
+1.61 TEN TEE 32 COLD 600UL 46 54 0.27 115 P3 TWD 10 DBH
+1.80 TEH TEC 32 COLD 600UL 72 0.40 64 P2 TWD 17 VSM
+0.84 TEN TEC 34 COLD 600UL 46 104 0.85 122 P2 TWD 26 VSM
-0.89 TEH TEC 56 COLD 600UL 46 118 0.20 146 P2 TWD 8 VSM
-0.78 TEH TEC 52 COLD 600UL 46 134 0.43 134 P2 TWD 19 VSM
+0.79 TEC TEH 21 HOT 60OUL
AREVA NP Inc Customer Name:
SONGS Unit 3 10/31/08 10:35:55 Component: S/G 89 Page 5 of 17 (de0l) Post-U3CT5 Insoection Results NAT, MCI,
- MMJT, MVT,
- SAI, ICE, SVI, TWD QUERY: deO!_inspection resulzs.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 46 138 0.42 114 P2 TWD 19 04C
-0.12 TEC TEH 25 HOT 600UL 46 146 0.55 108 P2 TWD 22 VSM
+0.95 TIC TEH 25 HOT 600UL 0.57 83 P2 TWD 23 VSM
-0.64 TEC TEH 25 HOT 60OUL 46 164 0.24 63 P2 TWD 12 VSM
+0.88 TEC TEH 37 HOT 600UL 0.28 94 P2 TWD 13 VSM
-0.19 TEC TEH 37 HOT 600UL 0.40 133 P2 TWD 18 VSM
-0.78 TEC TEH 37 HOT 600UL 46 166 0.40 97 P2 TWD 16 VSM
+0.84 TEC TEH 36 HOT 600UL 46 170 0.28 49 P2 TWD 12 05C
+0.84 TEC TEH 36 HOT 60DUL 47 101 0.61 33 P3 TWD 23 DBC
+1.82 TEH TEC 21 COLD' 600UL 47 103 0.29 17 P3 TWD 13 DBH
-1.51 TEH TEC 55 COLD 60OUL 0.21 84 P3 TWD 10 DBH
+1.99 TEH TEC 55 COLD 600UL 0.35 32 P3 TWD 15 DBC
+1.35 TEH TEC 55 COLD 60OUL 47 119 0.42 34 P2 TWD 15 VSM
-0.77 TEH TEC 52 COLD 600UL
.48 120 0.42 113 P2 TWD 17 VSM
+0.82 TEH TEC 51 COLD 1 60OUL 0.36 104 P2 TWD 14 VSM
-0.85 TEH TEC 51 COLD 60OUL 49 43 0.22 119 P2 TWD 12 08C
-1.63 TEC TEH 10 HOT 600UL 49 47 0.22 109 P3 TWD 12 DBH
+1.09 TEH TEC 33 COLD 600UL 49 49 0.54 148 P2 TWD 20 08H
+1.43 TEH TEC 33
- COLD 600UL 49 97 0.51 51 P3 TWD 18 DBH
+1.82 TEH TEC 20 COLD 600UL 49 101 0.69 96 P3 TWD 23 DBH
-1.75 TEH TEC 20 COLD
" 600UL 49 129 0.38 59 P2 TWD 17 08H
-1.53 TEH TEC 49 COLD 600UL 50 18 0.63 87 P2 TWD 24 VSM
-0.86 TEC TEH 23 HOT 600UL 0.23 157 P2 TWD 10 VSM
+0.70 TEC TEH 23 HOT 60OUL 50 20 0.41 116 P2 TWD 20 VSM
+0.62 TEC TEH 22 HOT 60OUL 0.60 94 P2 TWD 26 VSM
+0.16 TEC TEH 22 HOT 600UL 50 74 0.23 102 D3 TWD 10 DBH
-1.88 TEH TEC 34 COLD 600UL 50 78 0.39 53 P3 TWD 16 DBH
-1.66 TEH TIC 17 COLD 600UL 50 98 0.46 82 P3 TWD 19 DBC
-1.78 TEN TEC 21 COLD 60OUL 0.57 81 P3 TWD 22 DBH
-1.99 TEH TEC 21 COLD 60OUL 0.07 66 P3 TWD 4 DBW
+2.10 TEH TEC 21 COLD 60OUL 50 100 0.39 66 P2 TWD 15 VSM
-0.76 TEH TEC 21 COLD 600UL 0.28 160 P2 TWO 12 VSM
+0.95 TEH TEC 21 COLD 600UL 51 99 0.53 120 P3 TWD 20 DBH
-1.37 TEH TEC 20 COLD 600UL 52 76 0.40 61 P3 TWD 16 D0C
-1.58 TEH TEC 17 COLD 600UL 52 75 0.39 15 P3 TWD 15 DBH
+1.91 TEH TEC 16 COLD 60OUL 52 80 0.48 75 P3 TWD 19 D=N
-1.54 TEH TEC 17 COLD 60OUL 0.22 153 P3 TWD 9 DBC
-1.66 TEH TEC 17 COLD 60OUL 0.12 105 P3 TWD 4 DB0
+2.16 TEH TEC 17 COLD 600UL 52 94 0.71 125 P3 TWD 23 DEC
-1.59 TEH TEC 20 COLD 600UL 0.65 29 P3 TWD 22 DBH
+1.81 TEH TEC 20 COLD 600UL 52 100 0.47 35 P3 TWD 17 DBC
-1.67 TIH TEC 20 COLD 600UL 53 47 0.30 142 P2 TWD 13 03C
+0.78 TEH TEC 33 COLD 600UL 53 91 0.40 144 P3 TWD 15 DBH
-1.88 TEH TEC 20 COLD 600UL 0.42
!11 P3 TWD 15 DBH
+1.97 TEH TEC 20 COLD 600UL 53 93 0.47 123 P3 TWD 19 DEH
-1.68 TEH TEC 21 COLD 600UL 53 95 0.30 113 P,3 TWD 11 DIH
+1.99 TEH TIC 20 COLD 60OUL
AREVA NP Inc 10/31/08 10:35:55 Customer Name:
SONGS Unit 3 Component: S/0 89 Page 6 of 17 (de0l) Posz-U3C15 Inspection Results
- MAI, NCI, MDMI, NU,
- SAI, SCI,
- SVI, TWD QUERY: deOlinscection-results.ary ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.55 96 P3 TWD 19 DBC
-1.68 TEH TEC 20 COLD 600UL 0.32 146 P3 TWD 12 DEH
-1.82 TEH TEC 20 COLD 600UL 53 97 0.43 33 P3 TWD 16 DBH
-1.07 TEH TEC 20 COLD 600UL 53 101 0.41 62 P3 TWD 17 DEH
-1.84 TEH TEC 21 COLD 600UL 53 107 0.36 119 P3 TWD 15 DBH
-2.19 TEH TEC 55 COLD 600UL 54 8
0.39 113 P2 TWD 18 02C
-0.92 TEC TEH 30 HOT 60OUL 54 78 0.46 17 P3 TWD 18 DEH
-1.12 TEH TEC 17 COLD 60OUL 54 102 0.49 28 P3 TWD 18 DBC
+2.03 TEH TEC 56 COLD 600UL 0.34 126 P3 TWD 13 DBC
-1.88 TEH TEC 56 COLD 600UL 55 9
0.22 61 P2 TWD 12 02C
+0.10 TEC TEH 26 HOT 600UL 55, 81 0.68 16 P3 TWO 24 DEN
+-1.77 TEN TEC 17 COLD 600UL 55 87 0.63 14 P3 TWD 21 DBH
+1.13 TEN TEC 18 COLD 600UL 55 93 0.32 108 P3 TWD 12 DBE
+1.59 TEH TEC 20 COLD 60OUL 55 95 0.41 111 P3 TWD 17 DBH
-1.84 TEH TOC 21 COLD 600UL 55 99 0.41 46 P3 TWD 15 DBH
-1.17 TEH TEC 20 COLD 600UL 55 103 0.46 71 P2 TWD 16 VC3
+1.22 TEH TEC 56 COLD 600UL 56 76 0.71 95 P2 TWD 23 VSM
+0.72 TEH TEC 17 COLD 600UL 56 136 0.45 112 P2 TWD 21 VSM
+0.78 TEC TEH 20 HOT 600UL 0.58 116 P2 TWD 25 VSM
-0.72 TEC TEH 20 NOT 600UL 57 47 0.34 108 P2 TWD 15 08H
+0.49 TEH TEC 33 COLD 600UL 57 51 0.25 155 P2 TWD i1 08H
+0.36 TEH TEC 33 COLD 600UL 0.29 91 P2 TWD 13 08H
+0.82 TEH TEC 33 COLD 600UL 57 79 0.49 88 P3 TWD 19 DBH
+1.85 TEH TEC 17 COLD 600UL 57 89 0.22 160 P3 TWD 12 DBH
-2.21 TEH TEC 19 COLD 60OUL 57 129 0.26 142 P3 TWND 11 DBH
-0.45 TEH TEC 50 COLD 60OUL 57 143 0.79 106 P2 TWD 28 VN3
+0.78 TEC TEH 24 HOT 600UL 58 92 0.30 25 93 TWO 12 DEN
-1.21 TEN TEC 20 COLD E00UL 58 148 0.48 77 P2 TWD 21 VSM
+0.87 TEC TEH 29 HOT 60OUL 0.24 144 P2 TWD 12 VH3
-0.85 TEC TEH 29 HOT 600UL 0.57 126 P2 TWD 23 VC3
-0.85 TEC TEN 29 NOT 600UL 59 33 0.35 150 P2 TWD 17 VH3
-0.86 TEC TEH 14 HOT 600UL 59 97 0.22 144 P3 TWD 10 DBC
-1.67 TEH TEC 21 COLD 600UL 60 48 0.79 91 P2 TWO 26 08N
-0.93 TEH TEC 33 COLD 600UL 60 50 0.40 68
?2 TWD 16 08D
-0.34 TEN TEC 33 COLD 600UL 60 94 0.20 128 P3 TWD 9 DBH
-1.90 TEH TEC 21 COLD 600UL 0.41 11 P3 TWD 17 DBH
+2.00 TEH TEC 21 COLD 600UL 60 164 0.22 149 P2 TWD i1 08C
+0.86 TEC TEH 33 HOT 600UL 61 79 0.44 36 P3 TWD 18 DEH
+1.89
'TEH TEC 17 COLD 600UL 61 91 0.38 97 P2 TWD 14 03H
+0.10 TEH TEC 21 COLD 60OUL 61 99 0.32 147 P2 TWD 13 VSM
+0.89 TEN TEC 21 COLD 600UL 0.25 121 P2 TWO 11 UN3
-0.87 TEH TEC 21 COLD 600UL 0.27 59 P2 TWD 11 VH3
+0.74 TEH TEC 21 COLD 600UL 0.06 140 22 TWD 3 VH3
-0.13 TEH TEC 21 COLD 600UL
AREVA NP Inc 10/31/08 10:35:55 Customer Name: SONGS Unit 3 Component:
S/G 89 Page 7 of 17 (de0l) Post-U3C15 Inspection Results iA-,
MC I,
%am1,
- MVI, S A I, ECI, SVI, TWD QUERY: de,0!_inspection results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 62 50 0.75 83 P2 TWD 26 08H
-0.13 TEH TEC 32 COLD 6000UL 62 78 0.42 26 P3 TWD 17 DBH
+2.06 TEH TEC 17 COLD 60OUL 62 166 0.41 97 P2 TWD 17 02H
-0.82 TEC TEH 36 HOT 600UL 0.34 104 P2 TWD 14 02H
-0.20 TEC TEH 36 HOT 600UL 63 53 0.54 103 P2 TWD 21 08H
+0.48 TEH TEC 32 COLD 600UL 63 85 0.27 129 P3 TWD 11 DBH
+1.58 TEH TEC 16 COLD 60OUL 63 89 0.55 21 2
SAI TSH
-1.33 TSH TSH 86 HOT 58OPP 0.39 19 2
SAI TSH
-1.65 TSH TSH 86 HOT 580PP 64 44 0.30 116 P2 TWD 15 VC3
+0.82 TEC TEH 10 HOT 600UL 64 96 0.28 34 P3 TWD 11 DBC
+1.30 TEH TEC 20 COLD 600UL 64 166 0.25 21 P2 TWD 10 07H
+0.70 TEC TEH 36 HOT 6000L 65 49 0.58 153 P2 TWD 21 VH3
-0.78 TEH TEC 33 COLD 600UL 0.25 158 P2 TWD 11 VH3
+0.82 TEN TEC 33 COLD 600UL 65 53 0.35 77 P2 TWO 15 08W
-0.62 TEN TEC 33 COLD 600UL T
0.30 95 P2 TWD 13 081
-0.15 TEN TEC 33 COLD 60OUL 65 59 0.85 118 P2 TWD 28 VSM
-0.79 TEH TEC 34 COLD 600UL 0.42 138 P2 TWD 18 EVSN
+0.81 TEH TEC 34 COLD 600UL 65 87 0.66 106 P3 TWD 26 DBH
+1.70 TEH TEC 19 COLD 60OUL 65 97 0.29 132 P3 TWD 11 DBC
-1.90 TEH TEC 20 COLD 600UL 65 151 0.32 95 P2 TWD 16 VSM
+0.88 TEC TEH 28 HOT 60OUL 0.41 37 P2 TWD 19 VSM
-0.80 TEC TEH 28 HOT 600UL 0.19 37 P2 TWD 10 VSM
+0.16 TEC TEH 28 HOT 600UL 66 76 0.19 95 2
SAl TSH
+0.70 TSH TSH 86 HOT 5802P 0.10 101 2 SAI TSH
+0.66 TSH TSH 86 NOT 580PP 66 82 0.30 32 P3 TWD 13 DBH
-1.68 TEH TEC 17 COLD 600UL 0.31 121 P2 TWD 12 VH3
+0.88 TEH TIC 17 COLD 600UL 66 96 0.27 135 P3 TWO 12 DBE
-2.05 TEH TEC 21 COLD 600UL 66 98 0.50 144 P3 TWD 20 DBN
-1.31 TEH TEC 21 COLD 600UL 67 55 0.31 121 P2 TWD 14 08H
+0.75 TEH TEC 34 COLD 60OUL 67 87 0.68 164 P3 TWD 23 DBH
+1.32 TEH TEC 18 COLD 600UL 0.36 60 P3 TWD 33 DBC
-1.77 TEI TEC 18 COLD 600UL 67 165 0.62 84 P2 TWD 23 0!C
-0.16 TEC TEH 36 HOT 600UL 0.22 139 P2 TWD 9 01C
+0.90 TEC TEH 36 HOT 6000L 63 12 0.42 119 P2 TWD 19 02C
+0.00 TEC TEI 27 NOT 600UL 68 54 0.38 118 P2 TWD 16 06H
+0.38 TEH TEC 34 COLD 6000L 66 88 0.48 108 P3 TWO 22 DBH
-1.70 TEH TEC 19 COLD 600UL 66 92 0.40 152 P3 TWD 15 DBH
-1.61 TEH TIC 20 COLD 600UL 68 132 0.78 88 P2 TWD 29 VC3
+0.87 TEC TEH 20 HOT 600UL 68 164 0.23 109 P2 TWD 11 01C
-0.06 TEC TNH 33 HOT 600UL 0.39 110 P2 TWD 18 01C
+0.97 TEC TEH 33 HOT 600UL 69 39 0.31 93 P2 TWD 15 VW3
-0.88 TEC TEH 10 HOT 600UL 69 55 0.41 145 P2 TWD 16 08H
+0.80 TEH TEC 35 COLD 600UL 69 65 0.49 121 P2 TWD 18 VC3
-0.76 TEN TEC 37 COLD 60OUL 0.37 36 P2 TWD 14 VC3
+/-0.17 TIN TEC 37 COLD 600UL 69 127 0.27 85 P2 TWD 13 VSM
+0.86 TEI TEC 49 COLD 60OUL
AREVA NP Inc Customer Name:
SONGS Unit 3 10/31/08 10:35:55 Component:
S/G 89 Page 8 of 17 (de0l) Post-U3CI5 insoeczion Results NA:, MC-,
- Mj4I, MVI,
- SAT, SCI,
- SVI, TWD QUERY: de0l inspection resuls.arv ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.37.
107 P2 TWD 17 VC3
-0.79 TEH TEC 49 COLD 600UL 70 56 0.30 121 P2 TWD 14 08H
+0.69 TEN TE 34 COLD EDOUL 70 80 0.45 73 P2 TWD 17 VH3
-0.86 TEH TEC 17 COLD 60OUL 70 86 0.24 48 P3 TWD 10 DBC
+1.49 TEH TECE 17 COLD 60OUL 70 92 0.32 81 P3 TWD 14 DEN
-1.58 TEH TEC 21 COLD 600UL 71 19 0.31 149 P3 TWD 13 DBH
+1.97 TEC TEH 23 HOT 60OUL 71 53 0.37 44 P2 TWD 16 08H
+0.42 TEH TEC 32 COLD 600UL 71 65 0.37 124 P2 TWD 15 VH3
+0.83 TEH TEC 36 COLD 60OUL 71 75 0.37 156 P2 TWD 16 VH3
+0.84 TEH TEC 38 COLD 600UL 71 133 0.72 140 P2 TWD 28 VH3
+0.66 TEC TEH 20 HOT 600UL 0.61 142 P2 TWD 25 VC3
-0.82 TEC TEH 20 HOT 600UL 0.67 81 P2 TWD 27 VH3
-0.74 TEC TEH 20 HOT 60OUL 71 163 0.22 77 P2 TWD 11 02C
+0.10 TEEC TEH 33 HOT 60OUL 72 84 0.76 100 P2 TWD 25 VSM
-0.78 TEH TEC 17 COLD 60OUL 0.26 143 P2 TWD 10 VSM
+0.90 TEH TEC 17 COLD 600UL 0.45 153 P2 TWD 17: VC3
-0.10 TEH TEC 17 COLD 600UL 0.55 73 P2 TWD 19 VC3
+0.76 TEH TEC 17 COLD 600UL 73 53 0.35 26 P2 TWD 15 08H
+0.55 TEH TEC 33 COLD 60OUL 73 95 0.34 4
P3 TWD 15 DBC
+2.07 TEH TEC 21 COLD 600UL 73 157 0.27 76 P2 TWD 13 VC3
+0.94 TEC TEN 32 HOT 600UL 74 42 0.30 66, P2 TWD 13 VH3
+0.06 TEC TEH 1I HOT 60OUL 0.47 83 P2 TWD 19 VH3
+0.70 TEC TEN 11 HOT 600UL 74 110 0.49 41 P2 TWD 18 03H
-0.17 TEH TEC 54 COLD 600UL 74 118 0.29 92 P2 TWD 12 VSM
-0.77 TEH TEC 52 COLD 600UL 74 140 0.33 113 P2 TWD 15 VC3
+0.79 TEC TEH 25 HOT 600UL 75 19 0.26 54 P2 -TWD 12 VSM
-0.70 TEC TEH 23 HOT 60OUL 0.76 135 P2 TWD 27 VC3
+0.78 TEC TEH 23 HOT 60OUL 75 43 0.84 75 45 0.43 75 79 0.29 0.71 75 95 0.94 0.22 0.31 75 147 0.66 101 P2 TWD 28 VC3
+0.81 TEC TEH 11 HOT 600UL
.144 P2 TWO 18 VN3
-0.80 TEC TEH 11 HOT 60OUL 152 P2 TWD 12 VSM
-0.87 TEH TEC 16 COLD 60OUL 143 P2 TWD 24 VSM
-0.85 TEH TEC 16 COLD 600UL 73 P2 TWD 29 VC3
-0.84 TEH TEC 20 COLD 600UL 22 P2 TWD 10 VCo
+0.59 TEH TEC 20 COLD 60OUL 25 P3 TWD 12 DBC
+!89 TEH TECE 20 COLD 600UL 112 P2 TWD 25 VC3
+0.73 TEC TEH 28 HOT 600UL 75 157 0.51 5
P3 TWD 20 DBC
+1.61 TEC TEH 33 HOT 600UL 76 16 0.41 76 54 0.20 76 132 0.43 0.34 76 134 0.28 104 P2 TWD 17 08C
+0. 00 TEC TEH 23 NOT 600UL 156 P3 TWD 8 DBH
+0.84 TEH TEC 34 COLD 60OUL 132 P2 TWD 20 VH3
-0.80 TEC TEH 20 HOT 600UL 91 P2 TWD 17 V C
+0.80 TEC TEH 20 HOT 600UL 157 P3 TWD 13 DBC
-1.54 TEC TEH 20 HOT 60OUL 7.;
146 76 152 0.60 38 P2 TWO 24 VH3
+0.72 TEC TEH 24 HOT 600UL 0.61 136 P2 TWD 24 VH3
-0.94 TEC TEH 24 HOT 600UL 0.34..82..2.TWO..16.Vol.-0.......72......TEE......TEN.......28.....NOT..............UL.
0.34 82 P2 TWD 16 VC3
-0.72 TEC TEE 28 HOT 600UL
AREVA NP inc Customer Name:
SONGS Unit 3 10/31/08 10:35:55 Component:
S/G 89 Page 9 of 17 (deOl)
Post-U3C15 Inspection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY:
deOl insoection results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 76 162 0.27 50 P2 TWD 13 08F
+0.76 TEC TEH 32 HOT 60OUL 77 29 0.62 143 P2 TWD 26 VC3
+0.78 TIC TEH 18 HOT 600UL 77 39 0.32 102 P2 TWD 16 VC3
+0.90 TEC TEH 10 HOT 60OUL 77 61 0.62 114 P2 TWD 21 VN3
-0.86 TEN TEC 29 COLD 600UL 0.71 148 P2 TWD 23 VSO
+0.70 TEH TEC 29 COLD 60OUL 77 75 0.40 35 P2 TWD 16 VHS
-0.96 TEH TEC 39 COLD 60OUL 0.26 42 P3 TWD 12 DBC
+2.09 TEH TEC 39 COLD 600UL 77 135 0.34 75 P2 TWD 17 VSM
-0.97 TEC TEH 20 HOT 600UL 0.30 76 P2 TWD 15 VH3
+0.82 TEC TEH 20 HOT 600UL 77 155 0.39 141 P2 TWD 17 VH3
-0.83 TEC TEH 32 HOT 60OUL 0.84 129 P2 TWO 28 VH3.
+0.79 TEC TOH 32 HOT 60CUL 78 16 0.29 75 P2 TWD 16 05C
+0.80 TEC TEH 22 HOT 600UL 79 24 0.57 95 P2 TWD 22 VC3
-1.01 TEC TEH 19 HOT 600UL 78 40 0.23 18 P3 TWD 10 DBC
-1.63 TEC TEH 11 HOT 60UL 78 62
.0.49 105 P2 TWD 19 VC3
-0.60 TEH TEC 28 COLD 78 138 0.23 125 P2 TWO 11 VH3
-0.92 TEC TOH 25 HOT 79 25 0.36 49 P2 TWD 18 08C
-0.98 TEC TEH 18 HOT 600UL 600UL 600TUL 79 29 0.37 147 P2 TWO 19 VSM
-0.74 TEC TEH 18 HOT 60OUL 0.38 45 P2 TWD 19 VC3
+0.76 TEC TEH 18 HOT 600UL 79 39 0.41 104 P3 TWD 19 DBC
+1.77 TEC TEH 10 HOT 600UL 79 61 0.37 93 P2 TWD 14 VH3
-0.86 TEH TEC 29 COLD 600UL 79 95 0.25 5
P3 TWD 12 DBC
+1.75 TEN TOO 17 COLD 600UL 79 157 0.32 143 P2 TWD 14 01H
+0.84 TEC TEH 32 HOT 60OUL 79 159 0.25 24 P3 TWO 12 030
+1.91 TOO TON 32 HOT 600UL 80 64 0.24 170 P3 TWO 9 DBH
+1.19 TEH TEC 28 COLD 600UL 80 112 0.29 15 P3 TWD 12 DSH
+1.61 TEH TOC 53 COLD 50OUL 80 152 0.31 81 27 0.23 81
. 29 0.40 20 P3 TWD 15 DBC
+1.42 TEC TEH 28 NOT 600UL 97 P3 TWD 127 P2 TWD 12 DBH
-1.25 T
13 VH3
+0.81 T
EC TEH I
HOT 60OUL EC TEO 1
HOT 60OUL 81 51 0.22 174 P3 TWO 8 DBH
+2.05 TEH TOC 25 COLD 600UL
! 1, 0.17 64 P2 TWD 6 VH3
-0.76 TEE TEC 27 COLD 600UL 81 153 0.46 117 P2 TWD 21 VH3
+0.91 TEC TEH 17 HOT 60OUL 0.33 6
P3 TWO 15 DBC
+1.43 TEC TEH 17 HOT 600UL 82 18 0.35 123 P2 TWD 17 080
+0.74 TEC TEH 1
HOT 600UL 82 64 0.67 99 P2 TWO 24 VH3
+0.96 TEO TEC 26 COLD 600UL 12 94 0.38 136 P2 TWD 15 VH3
-0.04 TEH TEC 6
COLD 600UL 83 17 0.45 79 P2 TWD 19 02C
+0.94 TEC TEH 2
HOT 60OUL 0.50 100 P2 TWD 21 08H
+0.81 TEC TEH 2
HOT 60OUL 0.14 120 P2 TWD 7 08W
-1.09 TEC TEH 2
HOT 60OUL 33 59 0.30 17 P3 TWD 12 DnH
+2.02 TEO TEC 27 COLD 600UL 63 73 0.33 99 P3. TWD 14 DNH
+!.66 TEH TEC 21 COLD 600UL 33 101 0.29 91 P2 TWD 12 VSM
-1.25 TEH TEC 6
COLD 60OUL
AREVA NP Inc.
Customer Name: SONGS Unit 3 10/31/08 10:35:55 Component:
S/G 89 Page 10 of 17 (de~l) Posr-U3C15 Insoecr-ion R~esult~s N:AT, MCI, 14141, NUjT, SAT, SCI, SVT, TWO QUERY: de~l inacaction resulr~s.crv ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 83 103 0.60 110 22 TWD 22 09H
+1.52 TEH TEC 6
COLD 83 107 0.32 125 ?2 TWD 13 09H
-1.21 TEL TEC 6
COLD PROBE 60OUL 60OUL 83 115 0.59 122 P2 TWD 20 VSM 0.77 122 P2 TWD 24 09H
+1.24 TEH TEC 3
COLD 60OUL
+1.67 TEH TEC 3
COLD 60OUL 84 24 0.38 7
P3 TWD 18 DBC
+1.66 TEC TEH 1
HOT 600UL 84 32 0.20 21 P3 TWD 11 DBH
-1.78 TEC TEH 1
HOT 600UL 84 60 0.15 81 P3 TWO 8 03W
+0.92 TEH TEC 26 COLD 60OUL 84 126 0.51 168 P2 TWO 21 VH2
-0.91 TEH TEC 1
COLD 60OUL 85 31 0.20 27 P3 TWD 11 DBH
-1.82 TEC TEH 1
HOT 600UL 86 66 0.55 119 ?2 TWD 21 09H
+0.19 TEH TEC 26 COLD 600UL 0.47 74 P2 TWD 18 VSM
-0.81 TEH TEC 26 COLD 600UL 86 76 0.25 105 P2 TWD 11 07H
+0.17 TEH TEC 8
COLD 600UL 86 80 0.38 52 P2 TWD 17 09H
+0.21 TEH TEC 7
COLD 600UL 86 144 0.53 49 P2 TWO 23 VN2
+0.79 TEC TEN 17 NOT 600UL 66 156 0.52 67 P2 TWD 23 VH2
-0.71 TEC TEH 17 HOT 600UL 87 103 0.48 89 P2 TWD 18 08H
+0.74 TEN TEC 6
COLD 60OUL 0.46 137 P2 TWO 18 09W
+0.76 TEN TEC 6
COLD EDOUL 87 105 0.22 154 P2 TWD 10 08H
+0.55 TEH TEC 6
COLD 600UL 87 157 0.46 143 P2 TWO 21 03W
-1.23 TEC TEN 16 NOT 600UL 83 46 0.29 104 23 TWO 15 030
-1.63 TEC TEN S
NOT 600UL 83 66 0.36 99 P2 TWD 15 09H
+0.85 TEH TEC 26 COLD 600UL 88 102 0.49 80 22 TWD 20 VH2
-0.81 TEH TEC 6
COLD 600UL 86 104 0.14 133 P2 TWD 8 08H
-0.94 TEN TEC 5
COLD 600UL 0.30 67 P2 TWD 13 08H
-0.10 TEH TEC 5
COLD 600UL 88 116 0.67 135 22 TWD 23 VH2
-0.69 TEH TEC 4
COLD 69 71 0.28 129 P2 TWD i!
09H
+0.46 TEN TEC 23 COLD 89 73 0.19 148 P3 TWD 8 D3H
-1.05 TEH TEC 23 COLD 89 101 0.27 27 P2 TWD 13 08W
+0.71 TEN TEC 5
COLD 89 121 0.41 89 P2 TWD 16 VH2
+0.66 TEH TEC 4
COLD 600UL S00UL 60OUL 600UL 600UL 69 131 0.34 53 P2 TWD 14 VH2
+1.13 TEC TEH 7
HOT 600UL 137 0.53 130 P2 TWD 22 VH2
+0.87 TEC TEH 8
HOT 600UL 0.50 100 P2 TWD 21 VH2
-0.96 TEC TEH 8
HOT 6001UL 0.51 1i1 P3 TWD 22 D0H
+1.58 TEC TEH 8
HOT 600UL 90 68 0.27 110 P2 TWD 12 09H
+0.60 TEN TEC 28 COLD 600UL 91 67 0.28 152 P2 TWD 11 VH3
-0.80 TEH TEC 29 COLD 600UL 91 137 0.22 38 P3 TWD 12 DEH
+2.18 TEC TEH 8
HOT 600UL 93 87 0.36 64 P2 TWD 16 07H
+0.92 TEN TEC 10 COLD 600UL 0.61 149 P2 TWD 23 03H
+0.79 TEH TEC 10 COLD 600UL 94 106 0.49 81 P2 TWD 19 VH2
-1.01 TEN TEC 6
COLD 600TUL 96 24 0.58 98 P2 TWD 24 09C
+0.83 TEC TEN 1
NOT S00UL 97 27 0.12 156 P3 TWD 7 DBC
-1.75 97 53 0.69 64 P2 TWD 21 VH2
+0.84 TEC TEH 1
HOT 600UL TEH. TEC 25 COLD I60UL
AREVA NP Inc Customer Name:
SONGS Unit 3 10/31/08 10:35:55 Component: S/G 89 Page 11 of 17 (de0l) Post-U3C!5 inspec"ion Results
- MAi, MCi,
- Y141, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de0l inspectionresults.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.40 45 P2 TWD 13 VH2
+0.23 TEN TEC 25 COLD 60OUL 0.38 158 P2 TWD 13 VH3
-0.89 TEH TEC 25 COLD 60OUL 97 71 0.10 164 P3 TWD 4 DBW
+/-1.57 TEH TEC 23 COLD 600UL 97 89 0.25 159 P3 TWD 10 DBH
+0.33 TEH TEC 10 COLD 600UL 97 99 0.18 161 P3 TWD 10 DBH
+0.00 TEH TEC 5
COLD 60OUL 98 24 0.42 149 P2 TWD 18 04H
-1.02 TEC TEN 2
HOT 60OUL 98 144 0.28 108 P2 TWD 14 09H
-0.83 TEC TEH 17 HOT
.600UL 99
. 121 0.41 ill P2 TWD 16 Vh2
-0.76 TEH TEC 4
COLD 600UL 99 151 0.49 136 P2 TWD 22 08H
-0.68 TEC TEH 16 HOT 60OUL 100 42 0.32 52 P2 TWD 14 VH2
-0.93 TEC TEH 6
HOT 600UL 100 90 0.29 59 P3 TWD 8
DBH
-1.69 TEH TEC 15 COLD 600UL 101 69 0.93 28 P1 SCI TSH
-0.11 TSH TSH 84 HOT 580PP 101 123 0.29 119 P2 TWD 12 VH2
+/-0.97 TEH TEC 2
COLD 60OUL 102 44 0.16 24 P3 TWD 8 DBH
+1.43 TEC TEH 6
HOT 600UL 102 124 0.65 119 P2 TWD 23 VH2
-0.95 TEH TEC 2
COLD 60OUL 102 150 0.25 147 P3 TWD 12 DBC
+1.59 TEC TEH 16 HOT 60OUL 103 29 0.56 106 P2 TWD 22 VH2
+0.75 TEC.TEH 2
HOT 600UL 0.54 77 P2 TWO 22 VH2
-0.83 TEC TEH 2
HOT 60OUL 103 69 0.69 18 P1 SCI TSH
-0.09 TSH TSH 85 HOT 580PP 0.68 16 P1 SCI TSH
-0.07 TSH TSH 85 HOT 580PP 103 119 0.33 149 P3 TWD 14 DBH
+1.71 TEH TEC 3
COLD 600UL 103 149 0.53 135 P2 TWD 23 08H
-0.06 TEC TEN 16 HOT 600UL 104 116 0.57 126 P2 TWD 21 VH2
-0.80 TEH TEC 4
COLD 600UL 104 120 0.35 124 P2 TWD 16 VH2
-0.76 TEH TEC 3
COLD 600UL 105 33 0.42 127 F2 TWD 18 VH2
+0.93 TEC TEH 2
HOT 600UL 105 117 0.24 110 P.3 TWD 10 DBH
+1.28 TEH TEC 4
COLD 60OUL 106 28 0.34 138 P3 TWD 15 DBH 56 TEC T7o'EN 2 NOT 600UL 106 30 0.32 115 P2 TWD 16 09H
-.0.97 TEC TEN 1
NOT 60OUL 106 4A 0.27 102 P2 TWD 12 VH3
-0.95 TEC TEH 6
HOT 60OUL 106 110 0.39 102 P3 TWD 15 DBH
-1.40 106 112 0.42 134 P2 TWD 18 VH2
-0.87 0.39 72 P2 TWD 17 VH2
+0.95 107 31 0.27 131 P3 TWD 12 DEH
-1.62 107 45 0.76 46 P2 TWD 26 VH2
+0.85 0.64 67 P2 TWD 23 VH2
-0.95 107 55' 0.3'4 24 P2 TWD 12 08C
+0.88 TEH TEC 12 COLD 60OUL TEN TEC 12 COLD 600UL TE' TEC 12 COLD 600UL TEC TEH 2
HOT 600UL
=T TEN 6
HOT 600UL TEC TEH 6
HOT 600UL TEH TEC 25 COLD 60OUL 107 121 0.54 36 P2 TWO 20 V"2
-0.93 TEN TEC 4
COLD 0.94 154 P2 TWD 29 VH2
+0.93 TEH TEC 4
COLD 107 123 0.18 106 P3 TWD 8 DBH
-0.31 TEH TEC 1
COLD 107 125 0.42 56 P2 TWD 18 VH2
+0.87 TEN TEC 1
COLD 107 139 0.43 100 P2 TWD 20 091H 0.60 TEC TEH 12 HOT 600UL 600UL 600UL 600UL
AREVA NP Inc Customer Name:
SONGS Unit 3 10/31/08 10:35:56 Component:
S/G 89 Page 12 of 17 (de0l)
Posr-U3CI5 Inspection Results MAI, MCI,
- MMT, i,
- SAT, SCT,
- SVT, TWD QUERY: de0l insoection resuits.try ROW COL VOLTS DEG CHN TND %TW 107 145 0.61 113 P2 TWD 25 108 48 0.44 138 P2 TWD 18 108 50 0.43 137 P2 TWO 18 108 58 0.42 80
?2 TWD 17 108 82 0.30 155 P2 TWD !1 108 138 0.27 122 P2 TWD 12 LOCATION EXT EXT CAL 4 LEG PROBE 08H
-0.83 TEC TEH 16 HOT 600UL VH2
-0.81 TEH TEC 22 COLD 60CUL VH2
+/-0.96 TEH TEC 22 COLD 600UL VC3
+0.89 TEh TEC 24 COLD 600UL 03C
-1.05 TEH TEC 9
COLD 600UL 08H
-0.93 TEC TEH 12 HOT 600UL 108 144 0.44 141 P2 TWO 20 07H
+0.76 TEC TEH 16 HOT 600UL 109 39 0.18 67 P3 TWD 9 DBC
-1.53 TEC TEH 5
HOT 60OUL 109 117 0.50 49 P2 TWD 19 09H
-1.13 TEH TEC 4
COLD 600UL 109 127 0.17 144 P3 TWD 8 DBC
-1.83 TEH TEC 2
COLD 600UL 109 137 0.21 145 P2 TWD 10 08H
+1.06 TEC TEH 8
HOT 600UL 0.70 79 P2 TWD 26 08H
-0.93 TEC TEH 8
HOT 60OUL 109 139 0.20 55 P3 TWD 8 DBC
-1.66 TEC TEH 13 HOT 600UL 0.23 4
P3 TWD 10 DBH
+1.50 TEC TEH 13 HOT 600UL 110 32 0.15 38 P3 TWD 8 DBH
+1.57 TEC TEH 2
HOT 60OUL 110 34 0.27 39 P2 TWD 13 07H
+0.29 TEC TEH 1
HOT 60OUL 110 44 0.35 122 P2 TWD 15 VH2
-0.66 TEC TEH 6
HOT 600UL 110 52 0.48 129 P2 TWD 19 VH2
-1.00
-TEH TEC 24 COLD 60OUL 110 122 0.71 127
?2 TWD 24 VH2
+0.00 TEH TEC 2
COLD 60OUL 110 136 0.38 134 P2 TWD 17 08H
+0.99 TEC TEH 8
HOT 60OUL 0.40 62 22 TWD 18 08H
-0.93 TEC TEN 8
HOT 600UL 110 138 0.23 85 P2 TWD 12 08H
. 0.10 TEC TEH 13 HOT 600UL 111 37 0.32 17 P3 TWD 14 DBC
+2.03 TEC TEN 6
HOT 600UL 111 47 0.27 122 P2 TWD 11 08C
+0.91 TEH TEC 23 COLD 600UL 111 113 0.46 120 P2 TWD 20 VH2
-0.90 TEH TEC 12 COLD 600UL 0.47 128 ?2 TWD 20 VH2
+0.90 TEH TEC 12 COLD 60OUL 1.1 131 0.27 100 P2 TWD 13 08H
+0.80 TEC TEH 3
HOT 600UL 0.22 91 P2 TWD 11 08H
-0.75 TEC TEH 3
HOT 60OUL 133 0.37 130 P2 TWD 17 08H
-0.02 TEC TEH 7
HOT 60OUL 0.37 130 ?2 TWD 15 08H
+0.79 TEC TE-7 HOT 60OUL 11 135 0.33 60 P2 TWD 15 VH2
+0.25 TEC TEH 8
HOT 60OUL 0.35 105 P2 TWD 16 07H
+0.79 TEC TEH 8
HOT 600UL Il1 137 0.85 124 P2 TWD 29 VH2
+0..83 TEC TEH 8
HOT 600UL 111 141 0.36 81 P3 TWO 17 D0H
-1.84 TEC TEN 16 HOT 600UL 111 143 0.30 84 P2 TWD 15 VC3
+0.87 TEC TEH 16 NOT S60UL 0.18 103 P2 TWD 10 VC3
-0.79 TEC TEH 16 HOT 600UL 0.43 155 P3 TWD 19 DEN
+1.49 TEC TEH 16 HOT 600UL 112 40 0.32 31 P3 TWD 16 DEH
+1.63 TEC TEH 5
112 124 0.78 110 P2 TWD 25 VH2
-1.06 TEH TEC 2
112 132 0.64 83 P2 TWD 24 07H
+0.85 TEC TEh 7
0.51 123 P2 TWD 20 08H
+0.83 TEE TEN 7
0.55 80
?2 TWD 22 VH2
+0.88 TEC TEH 7
112 142 0.37 8
P3 TWD 17 DBC
+1.86 TEC TEH 16 0.45 158 P2 TWD 20 VC2
-0.87 TEC TEH 16 HOT 60OUL COLD 600UL NOT G00UL HOT 600UL HOT 60OUL HOT 60OUL HOT 60OUL
AREVA NP !nc Customer Name:
SONGS Unit 3 10/31/08 10:35:56 Component: S/G 89 Page 13 of 17 (de0l) Post-U3C15 ansaection Results
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de0linspectiontesults.qry ROW COL VOLTS DEG CHN IND %TW LOCATION 113 67 0.57 89 P2 TWD 20 04C
+0.27 113 99 0.78 19 2
SAI TSHO
-7.78 0.51 15 2
SAT TSON
-7.52 EXT EXT CAL # LEG PROBE TEH TEC 29 COLD 60DUL TSH TSH 106 HOT 580PP TSH TSH '106 HOT 580PP 113 129 0.46 41 P2 TWD 17 09H
+0.83 TEN TEC 2
COLD 600UL 0.51 123 P2 TWD 19 VH2
+0.89 TEH TEC 2
COLD A600UL 0.37 93 P3 TWD 17 DBO
+2.18 TEH TEC 2
COLD 60OUL 114 90 0.24 138 P3 TWD 8 DBH
+1.35 TEH TEC 14 COLD 600UL 114 104 0.53 123 P2 TWD 19 VN2
-0.87 TEH TEC 13 COLD 600UL 114 106 0.35 29 P3 TWO 13 DBH
+1.89 TEH TEC 12 COLD 600UL 114 114 0.76 59 P2 TWD 27 VH2
-0.88 TEH TEC 12 COLD 600UL 0.40 133 P2 TWD 17 VH2
+0.90 TEH TEC 12 COLD 60OUL 114 130 0.33 92 P2 TWD 16 09H
-0.98 TOC TEH 3
HOT 600UL 0.32 137 P2 TWD 16 09H
+0.02 TEC TEH 3
HOT 60OUL 114 132 0.93 128 P2 TWD 30 07H
+0.81 TEC TEH 7
HOT 600UL 115 41 0.30 140 P2 TWD 13 VH!
+0.91 TEC TEH 6
HOT 600UL 0.30 46 P2 TWD 14 VHI
-0.62 TEC TEH 6
HOT 600UL 115 45 0.68 138 P2 TWD 24 VHN
-1.12 TEC TEH 6
HOT 60OUL 115 105 0.51 68 P2 TWD 21 VH2
+1.02 TEH TEC 12 COLD 600UL 115 127 0.41 145 P2 TWD 18 09H
+0.79 TEH TEC 1
COLD 600UL 115 129 0.36 108 22 TWD 16 09H
-0.72 TEH TEC 1
COLD 600UL 116 124 0.43 117 P2 TWD 17 08H
+0.89 TEH TEC 2
COLD 600UL 0.24 131 P2 TWD 10 08H
+0.46 TEH TEC 2
COLD 600UL 0.33 101 P2 TWD 13 09H
+0.78 TEH TEC.
2 COLD 600UL 116 126 0.31 78 P2 TWD 15 08H
+0.95 116 128 0.32 116 D2 TWD 13 08H
+0.79 0.52 92 P2 TWD 19 09D
+0.68 0.29 92 P2 TWD 12 08H
+0.28 0.25 141 P2 TWD 10 09H
-0.89 117 123 0.62 121 02 TWD 22 08H
+0.89 0.40 60 P2 TWD 16 06D
+0.83 117 125 0.19 44 P2 TWD 8 09D
-0.80 0.24 130 P2 TWD 10 09H
+0.42 117 129 0.27 90 02 TWD 13 08H
+1.08 113 46 0.i5 150 P2 TWD 8 VHN
+0.74 0.40 130 P2 TWD 17 VNI
-0.83 TEH TEC I
COLD 600UL TEN TEC 2
COLD 60DUL TEH TEC 2
COLD 600UL TEH TEC 2
COLD 600UL TEH TEC 2
COLD 600UL TEH TEC 2
COLD 600UL TEH TEC 2
COLD 60DUL TEN TEC 2
COLD 600UL TEH TEC 2
COLD 600UL TEN TEC 1
COLD 600UL TEC TEH 5
HOT 600UL TEC TEN 5
HOT 60OUL 118 92 0.26 58 P2 TWD 10 VH!
+1.05 119 123 0.59 55
?2 TWD 23 09H
+0.83 119 125 0.46 115 P2 TWD 20 09H
-1.04 0.21 52 D2 TWD !1 09H
-0.04 119 139 0.64 126 P2 TWD 24
!0C
-1.20 120 62 0.47 80 P2 TWD 19 VH1
-0.75 0.40 147 P2 TWD 17 VH2
-0.81 120) 80 0.28 50 P3 TWD 11 DBH
+1.79 120 92 0.45 113 P2 TWD 15 VH1
+0.81 120 112 0.25 58 P3 TWD 10 DON
-0.04 121 107 0.36 103 P3 TWD 15 DBH
+1.72 TEH TEC 14 TEH TEC 1
TEH TEC 1
TEC TOO 12 TEH TEC 26 TEO TOC 26 COLD 600UL COLD 600UL COLD 6000L COLD 600UL NOT 600UL COLD 600UL COLD 600UL TEH TEC 7
COLD 60OUL TEN TOO 15 COLD 600UL TEH TEC 13 COLD 600UL TEH TEC 13 COLD 600UL
AREVA NP Inc, 10/31/08 10:35:56 Cust6mer Name:
SONGS Unit 3 Component:
S/G 89 Page 14 of 17 (de0l) Post-U3C!5 Inspection Results
- MAT, MCI,
- MMT, MVI,
- SAI, SCI,
- SVI, TWD QUERY' deo ianspection results.qry ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 121 113 0.28 111 P2 TWD 11 VH1
-0.81 TEH TEC 13 COLD 60OUL 121 117 0.33 92 P2 TWD 13 VHl
+0.71 TEH TEC 4
COLD 600UL 121 121 0.45 109 P2 TWD 19 09H
+0.51 TEH TEC 3
COLD 600UL 0.54 110 F2 TWD 21 10H
-0.19 TEH TEC 3
COLD 60OUL 122 78 0.59 131 P2 TWD 23 VHN
-0.92 TEH TEC 7
COLD 600UL 122 86 0.22 136 P3 TWD 8 DBH
+0.43 TEN TEC 10 COLD 60OUL 122 112 0.63 68 P2 TWD 24 10H
+0.76 TEH TEC 12 COLD 600UL 122 116 0.31 30 P2 TWD 12 08H
-1.15 TEH TEC 3
COLD 600UL 0.45 152 P2 TWD 19 1OH
+0.02 TEH TEC 3
COLD 600UL 122 120 0.38 118 P2 TWD 14 08H
-0.73 TEH TEC 3
COLD 600UL 0.26 60 F2 TWO 10 08H
+0.57 TEH TEC 3
COLD 60OUL 0.48 139 P2 TWD 19 VHi
-0.90 TEH TEC 3
COLD 600UL 122 122 0.63 127 P2 TWD 24 10C
+0.87 TEH TEC 1
COLD 60OUL 123 45 0.71 114 P2 TWD 25 10C
+0.78 TEC TEH 6
HOT 600UL 123 83 0.33 107 P3 TWD 13 DBH
-0.56 TEH TEC 9
COLD 60OUL 123 85 0.32 125 P3 TWDO13 DBH
-1.89 TEH TEC 11 COLD 60OUL 123 115 0.31 85 P2 TWD 12 09H
+0.40 TEH TEC 3
COLD 600UL 123 117 0.66 137 P2 TWD 21 09H
-0.71 TEH TEC 3
COLD 600UL 0.19 37 22 TWD 8 09F
+0.42 TEH TEC 3
COLD 60OUL 0.27 36 P2 TWD 12 08H
+0.40 TEH TEC 3
COLD 600UL 123 119 0.27 87 P2 TWD 11 09H
-0'17 TEH TEC 4
COLD 600UL 0.51 113 P2 TWD 19 09H
+0.50 TEH TEC 4
COLD 60OUL 124 58 0.36 108 P2 TWD 15 VHi
+0.70 TEH TEC 24 COLD 60OUL 124 78 0.40 151 P2 TWD 16 VOI
-0.94 TEH TEC 8
COLD 600UL 124 98 0.28 118 P2 TWD 9 vii
+0.96 TEN TEC 15 COLD 600UL 124 1.14 0.19 127 ?2 TWD 8 05H
+0.80 TEH TEC 13 COLD 600UL 124 116 0.52 107 P2 TWD 19 08H
+0.91 TEH TEC 4
COLD 600UL 0.34 80 P2 TWD 14 09H
+0.23 TEH TEC 4
COLD rOCUL 0.13 17 P2 TWD 5 TOH
-0.97 TEH TEC 4
COLD 600UL 125 45 0.19 143 23 TWD 9 DBH
+0.51 TEC TEH 6
HOT 600UL 125 57 0.67 121 P2 TWD 20 VHl
-0.90 TEi TEC 25 COLD 600UL 0 53 109 P2 TWD 17 VHN
+0.80 TEH TEC 25 COLD 60OUL 125 65 0.34 158 P2 TWD 12 VN!
+0.56 TEH TEC 27 COLD 600UL 125 117 0.44 139 P2 TWD 17 08W
+0.94 TEH TEC 4
COLD 60OUL 126 62 0.35 71 P2 TWD 15 VH2
+0.70 TEH TEC 26 COLD 600UL 0.51 42 P2 TWD 20 VH!
-0.89 TEH TEC 26 COLD 60OUL 12,6 84 0.47 116 P2 TWD 20 VN1
+0.76 TEH TEC 10 COLD 600UL 126 86 0.43 139 P2 TWD 18 VHN
-0.91 TEh TEC 10 COLD 600UL 0.37 69 P2 TWD lo Vl
+0.82 TEN. TEC 10 COLD 600UL 126 108 0.47 72 P2 TWD 20 i0H
+0.31 TEH TEC 12 COLD 600UL 126 114 0.44
!1 P2 TWD 19 08H
+0.90 TEH TEC 12 COLD 60OUL 126 132 0.58 82 P2 TWD 23 VH2
-0.93 TEC TEH 7
NOT 600UL 127 51 0.42 31 P3 TWD 17 DBH
-1.59 TEH TEC 23 COLD 600UL 127 -----------------------------
6
+0.....
40.....TEN.......
TED......27
.....COLD..............
UL..
127/
61 0.49 96 P2 TWvD 16 10H
+0.40 TEh' TEC 27 COLD 600OUL
AREVA NP inc 10/31/08 10:35:56 Customer Name:
SONGS Unit 3 Component:
S/G 89 Page 15 of 17 (de01)
Post-U3C!5 Inspection Results
- MAT, MCI, 4MI, MV1,
- SAI, SCI,
- SVI, TWD QUERY: de01_inspectionresults.crv ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 127 63 0.27 120 P2 TWD 10 VH1
-0.88 TEH TEC 27 COLD 60OUL 0.39 107 P2 TWD 13 VH7
+0.88 TEH TEC 27 COLD 60UL 127 65 0.41 152 P2 TWD 14 V75
+0.69 TEh TEC 27 COLD 600UL 027 6
.35 123 P2 TWD 13 VHI
+0.10 TEH TEC 29 COLD 600UL 127 79 0.73 91 P2 TWD 27 V75
+0.79 TEH TEC
- 7.
COLD 600UL 127 85 0.73 110 P2 TWD 25 751
-0.69 TEN TEC 11 COLD 60OUL 127.
101 0.29 127 P2 TWD 11 VHi
-0.68 TEH TEC 14 COLD 6SOUL 127 111 0.45 56 P2 TWD 19 09H
-0.21 TEH TEC 12 COLD 60OUL 0.50 96 P2 TWD 20 10H
+0.55 TEH TEC 12 COLD 600UL 127 113 0.42 100 P2 TWD 18 08H
+0.94 TEH TEC 12 COLD 600UL 0.31 76 P2 TWD 14 09H
-0.80 TEH TEC 12 COLD 600UL 0.29 132 P2 TWD 13 09H
+0.35 TEH TEC 12 COLD 600UL 127 115 0.30 56 P2 TWD 11 08H
-0.45 TEH TEC 3
COLD 600UL 0.39 124 P2 TWD 14 08W
+0.78 TEH TEC 3
COLD 600UL 127 131 0.12 144 P3 TWD 5 DBH
+1.74 TEC TEH 3
HOT 600UL 0.35 87 P2 TWD 17 07H
+0.06 TEC TEH 3
HOT 600UL 128 50 0.85 130 P2 TWO 24 V52
-0.83 TEN TEC
- 22 coLD SO0UL 128 72 0.58 109 P2 TWD 22 VH1
-0.78 TEH TEC 22 COLD 600UL 0.72 68 P2 TWD 25 VH2
-0.83 TEH TEC 22 COLD 60OUL 128 76 0.47 1.40 P2 TWD 20 VHI
+0.67 TEH TEC 7
COLD 600UL 128 110 0.21 160 P2 TWD 8 08H
-0.90 TEH TEC 13 COLD 600UL 0.21 138 P2 TWD 8 08H
+0.87 TEH TEC 13 COLD 600UL 0.33 137 P2 TWD 13 l0H r0.79 TEH TEC 13 COLD 60OUL 0.27 142 P2 TWOD 11 0H
-0.95 TEH TEC 13 COLD 60OUL 129 116 0.32 101 P2 TWD 13 VH!
+0.63 TEH TEC 4
COLD 600UL 0.29 57 P2 TWD 11 09C
+0.86 TEH TEC 4
COLD 60OUL 123 124 0.61 99 22 TWD 21, VH2
+0.00 TEH TEC 2
COLD 60OUL 129 61 0.23 55 P2 TWD 8 V75
-0.61 TEH TEC 27 COLD 600UL 129 63 0.40 117 P2 TWO 14 101
+0.50 TEH TOC 27 COLD 600UL 0.54 63 P2 TWO 17 VH1
+0.90 TEH TEC 27 COLD 600UL 129 105 0.54 93 P2 TWD 20 V7!
+0.79 TEH TEC 13 COLD 600UL 129 11 0.37 112 P2 TWD 14 09H
-0.83 TEH TEC 13 COLD 600UL 0.28 133 P2 TWD 11 09H
+0.53 TEH TEC 13 COLD 60OUL 130 50 0.51 148 P2 TWD 20 VH2
-0.81 TEH TEC 22 COLD 600UL 130 54 0.21 20 P3 TWD 9
DB0
+1.78 TEN TOC 24 COLD 60OUL 130 62 0.71 107 P2 TWD 25 7i5
+0.91 TEN TEC 26 COLD 600UL 130 66 0.51 90 P2 TWD 20 VH!
+0.76 TEH TEC 26 COLD 0O0UL 130 68 0.48 95 P2 TWD 19 VH1
+0.89 TEH TEC 28 COLD 60OUL 0.21 128 P3 TWD 8 DB0
-0.06 TEN TEC 23 COLD 600UL 130 72 0.56 118 P2 TWD 22 VH1
+0.74 TEH TEC 22 COLD 600UL 130 78 0.74 125 P2 TWD 27 V75
+0.87 TEH TEC 7
COLD 600UL 130 94 0.62 49 P2 TWD 22 VH1
+0.78 TEH TEC 14 COLD 60OUL 130 112 0.42 101 P2 TWD 16 7H2
-0.78 TEH TEC 13 COLD 60OUL 130 120 0.43 137 P2 TWD 17 V72
-0.82 TEH TEC 4
COLD 600G L 131 49 0.29 22 P3 TWD 13 DnH
+1.72 TEH TEC 46 COLD 60OUL
AREVA NP Inc 10/31/08 10:35:56 Customer Name:
SONGS Unit 3 Component:
S/G 89 Page 16 of 17 (de0l) Post-U3C15 Inspection Results
- NAT, MCI,
- MMI, MVI,
- SAT, SCI,
- SVI, TWD QUERY: de0l _insoection results.qry ROW COL VOLTS DEG CNN IND %TW LOCATION EXT EXT CAL # LEG PROBE 132 54 0.26 23 P3 TWD 9 DBH
+1.64 TEH TEC 45 COLD 600UL 132 60 0.65 37 P2 TWD 23 VHN
-0.65 TEH TEC 45 COLD 60OUL 0.74 37 P2 TWD 25 VH2
-0.85 TEH TEC 45 COLD 60OUL 132 72 0.65 58 22 TWD 23 10H
+0.91 TEH TEC.47 COLD 600UL 0.54 127 P2 TWD 20 VHi
-0.87 TEH TEC 47 COLD 60OUL 132 74 0.43 130 22 TWD 17 VH2
-0.83 TEH TEC 47 COLD 60OUL 132 82 0.56 115 P2 TWD 21 VN1
-0.04 TEH TEC 47 COLD 60OUL 132 88 0.54 38 P2 TWD 20 VHI
+0.87 TEH TEC 47 COLD 60OUL 132 100 0.75 127 P2 TWD 25 VHN
-0.91 TEH TEC 47 COLD 600UL 0.65 126 P2 TWD 23 VH2
-0.87 TEH TEC 47 COLD 600UL 132 110 0.37 79 P2 TWD 14 08H
+0.93 TEH TEC 50 COLD 60OUL 0.30 128 P2 TWD 11 07H
+0.59 TEH TEC 50 COLD 60OUL 133 53 0.55 148 P3 TWD 21 DBH
+1.68 TEH TEC 46 COLD 600UL 0.68 98 P2 TWD 24 07H
+0.02 TEH TEC 46 COLD 600UL 133 65 0.i9 81 P3 TWD 9 DBH
+1.55 TEH TEC 46 COLD I60UL 133 93 0.19 40 P2 TWD 9 VHN
-0.94 TEH TEC 48 COLD 600UL 133 95 0.35 131 P2 TWD 14 VH!
+0.78 TEH TEC 47 COLD 600UL 133 101 0.40 133 P2 TWD 16 VHI
+0.73 TEH TEC 48 COLD 60OUL 133 103 0.46 99 P2 TWD 18 08H
+0.87 TEH TEC 48 COLD 600UL 0.16 124 P2 TWD 7 VHI
-0.79 TEH TEC 48 COLD 600UL 133 107 0.31 142 P2 TWD 13 09N
+0.85 TEH TEC 48 COLD 60OUL 0.14 156 P2 TWD 6
09H
-0.83 TEH TEC 48 COLD 600UL 0.40 76 P2 TWD 16 VH2
+0.85 TEH TEC 48 COLD 600UL 134 58 0.57 80 P2 TWD 21 VC3
+0.58 TEH TEC 45 COLD 600UL 134 68 0.50 133 P2 TWD 19 10H
-0.81 TEH TEC 45 COLD 600UL 0.27 40 P2 TWD 11 T0H
+0.85 TEH TEC 45 COLD 60OUL 134 74 0.70 115 P2 TWD 24 VH2
-0.90 TEH TEC 48 COLD 600UL 134 80 0.65 136 P2 TWD 23 VH1
-0.79 TEH TEC 48 COLD 60OUL 0.33 119 P2 TWD 14 VHi
+0.79 TEH TEC 48 COLD 60OUL 134 54 0.50 145 P2 TWD 19 VHN
-0.93 TEH TEC 47 COLD 600UL 134 86 0.35 51 P2 TWD 14 T0H
+0.27 TEH TEC 47 COLD 600UL 134 108 0.27 45 P2 TWD 12 i0H
+0.92 TEH TEC 48 COLD 600UL 135 77 0.50 95 P2 TWD 19 VNT
+0.86 TEH TEC 47 COLD 600UL 135 89 0.46 68 P2 TWD 18 VH3
-0.97 TEH TEC 47 COLD 600UL 135 95 0.37 113 P2 TWD 15 VHi
-0.92 TEH TEC 48 COLD 600UL 136 58 0.22 14 P3 TWD 10 DBH
-1.63 TEH TEC 46 COLD 60OUL 136 74 0.47 92 P2 TWD 18 VHl
+0.88 TEH TEC 47 COLD 60OUL 136 90 0.52 75 P2 TWD 20 V:4
+0.82 TEH TEC 47 COLD 600UL 136 94 0.67 125 P2 TWD 23 Vil
-0.94 TEN TEC 48 COLD 600UL 137 59 0.34 22 P3 TWD 14 DBC
+1.84 TEH TEC 46 COLD 600UL 137 79 0.35 64 P2 TWD 15 09H
-0.84 TEH TEC 48 COLD 600UL 137 81 0.36 31 P2 TWD 15 0NH
+/-0.86 TEH TEC 48 COLD 600UL 137 63 0.66 34 P2 TWD 23 09N
+0.86 TEH TEC 48 COLD 600UL
AREVA NP Inc 10131/08 10:35:56 Customer Name:
SONGS Unit 3 Component:
S/G 89 Page 17 of 17 (deOl)
Posz-U3C15 Inspection Results
- MA7, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, TWD QUERY: de01_insoectionresulýs.qry ROW COL VOLTS DEG CHN IND
%TW LOCATION EXT EXT CAL # LEG PROBE 137 91 0.60 101 P2 TWD 22 09H
+/-0.81 TEH TEC 48 COLD 600UL 0.45 142 P2 TWD 18 VHD
+0.88 TEN TEC 48 COLD 600UL 137 115 0.39 96 P2 TWD 18 VH2
-0.84 TEH TEC 49 COLD 60OUL 138 76 0.51 138 P2 TWD 19 10H
+0.85 TEH TEC 47 COLD 600UL 138 104 0.54 135 P2 TWD 20 VHD
-0.81 TEH TEC 48 COLD 600UL 0.22 90 P2 TWD 10 VH1
-0.21 TEH TEC 48 COLD 600UL 139 85 0.33 97 P2 TWD 14 VH3
+0.88 TEH TEC 47 COLD 600UL 139 89 0.52 i1 P2 TWD 20 09H
+0.91 TEH TEC 47 COLD 60OUL 0.25 155 P2 TWD 10 09H
-0.99 TEH TEC 47 COLD 600UL 139 95 0.24 85 P2 TWD 10 VHD
-0.94 TEH TEC 48 COLD 60OUL 139 99 0.28 83 P2 TWD 12 VH2
-0.95 TEH TEC 47 COLD 600UL 140 64 0.70 67 P3 TWD 25 DBH
-1.59 TEH TEC 46 COLD 600UL 140 112 0.37 125 P2 TWD 17 04H
+0.77 TEH TEC 49 COLD 600UL 0.48 45 P3 TWO 18 DBC
-1.60 TEH TEC 49 COLD
.600UL 0.36 123 P3 TWD 14 DBC
+1.64 TEH TEC 49 COLD 600UL 141 67 0.35 130 P22 TWD 14 VHD
-0.78 TEH TEC 46 COLD 600UL 0.22 56 P3 TWD 9 DBC
-1.61 TEH TEC 46 COLD 600UL 141 87 0.40 66 P2 TWD 16 VH2
+0.89 TEH TEC 48 COLD 600UL 141 97 0.32 64 P3 TWD 14 DBC
-1.57 TEH TEC 48 COLD 60OUL 141 99 0.35 109 P3 TWD 15 DOH
+2.07 TEH TEC 48 COLD 60OUL 0.30 105 P2 TWD.13 VH1
+0.96 TEH TEC 48 COLD 600UL 142 82 0.68 29 P3 TWD 24 DEC
.+1.81 TEH TEC 48 COLD 600UL 143 95 0.25 43 P3 TWD 11 DBE
-1.59 TEH TEC 48 COLD 60OUL 144 70 0.60 92 P2 TWD 22 VC1
+0.54 TEH TEC 46 COLD 600UL 144 76 0.20 90 P3 TWD 9
DBH
-1.80 TEH TEC 48 COLD 600UL 144 78 0.46 86 P3 TWO 18 DBH
-1.61 TEH TEC 48 COLD 600UL 144 80 0.41 168 P3.
TWD 15 DBH
+1.97 TEH TEC 47 COLD 60OUL 144 34 0.54 51 P2 TWD 20 VH3
+0.83 TEN TEC 48 COLD 600UL 144 94 0.34 126 P3 TWD 15 DBH
+1.82 TEH TEC 48 COLD 600UL 144 102 0.33 126 P2 TWD 16 09H
-1.01 TEH TEC 49 COLD 600UL 0.34 168 P3 TWD 13 DBC
+2.04 TEH TEC 49 COLD 600UL 0.37 119 P3 TWO 14 DBC
-1.90 TEH TEC 49 COLD 60OUL 145 73 0.34 93 P3 TWD 14 DNH
+/-1.86 TEH TED 48 COLD 600UL 145 79 0.22 105 P3 TWD 10 DBH
-1.37 TEH TEC 48 COLD 600UL 145 97 0.27
`10 P3 TWD 12 DEC
-1.94 TEH TEC 48 COLD 600UL 146 90 0.35 124 P2 TWD 14 VH3
-0.83 TEH TED 48 COLD 600UL 0.50 66 P3 TWD 19 DBC
+1.79 TEH TEC 48 COLD 600UL 1-46 92 0.92 46 P3 TWD 29 DEH
+2.15 TEH TED 48 COLD 600UL Toeal Tubes
- 51 Total Records:
692