Entergy Operations, Inc.
7003 Bald Hill Road P.O. Box 756 Port Gibson, MS 39150 Tel 601 4376694 Michael A. Krupa Director Nuclear Safety Assurance GNRO-2009/00016 February 20, 2009 u.s. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555
SUBJECT:
Supplement to Response to Basis for Denial of Condensate Storage Tank Setpoint Change letter dated November 5,2008 Grand Gulf Nuclear Station, Unit 1 Docket No. 50-416 License No. NPF-29
REFERENCES:
1.
2.
3.
Dear Sir or Madam:
Letter GNRO-2007/00016 from W. R. Brian, Entergy Operations, Inc.
to USNRC, "License Amendment Request Condensate Storage Tank Level-Low SetPOint Change," dated March 1,2007 (TAC # MD 4675)
Letter from NRC "Grand Gulf Nuclear Station, Unit 1 - Staff Evaluation and Basis for Denial of Proposed Technical Specification Change Related to the Condensate Storage Tank Level-Low SetPQint Changes (TAC No. MD4675)"
Letter GNRO-2008/00078 from M. A. Krupa, Entergy Operations, Inc.
to USNRC, "Response to Basis for Denial of Condensate Storage Tank SetPOint Change letter dated November 5,2008 (TAC No.
MD4675)"
By Reference 1, Entergy Operations, Inc. (Entergy) proposed a change to the Grand Gulf Nuclear Station, Unit 1 (GGNS) Technical Specifications (TS) to correct allowable values in TS Tables 3.3.5.1-1 and 3.3.5.2-1. By Reference 2, the NRC Staff provided an evaluation and basis for denial of the proposed change and requested Entergy's review and comments on the staff's evaluation. Entergy responded to the request and provided comments by Reference 3. This supplemental letter provides clarification of Entergy's response.
Reference 3 stated that Entergy was monitoring the efforts of the Technical Specification Task Force and the NRC to finalize the details and scope of the changes needed to resolve the instrument setpoint issue discussed in RI5-2006-17 and planned to support any NRC and industry solutions when finalized. To clarify this statement, if the G090016
GNRO-2009/00016 Page 2 of 2 Condensate Storage Tank (CST) Level-Low setpoint is affected by the approved TSTF traveler, then Entergy will submit a separate amendment request to implement the approved generic change. This is considered a commitment and is reflected in the Attachment.
The original no significant hazards consideration included in Reference 1 is not affected by any information contained in the supplemental letter.
If you have any questions or require additional information, please contact Bryan Ford at 601-368-5516.
I declare under penalty of perjury that the foregoing is true and correct. Executed on February 20, 2009 Sincerely,
~.~(~
MAKlRWB:amm
Attachment:
List of Regulatory Commitments of Regulatory Commitments cc:
Mr. Elmo E. Collins Regional Administrator, Region IV U. S. Nuclear Regulatory Commission 61 1 Ryan Plaza Drive, Suite 400 Arlington, TX 76011-4005 U.S. Nuclear Regulatory Commission ATIN: Mr. Carl F. Lyon, NRR/DORL (w/2)
ATTN: ADDRESSEE ONLY ATIN: U.S. Postal Delivery Address Only Mail Stop OWFN/8 B1 Washington, D.C. 20555-0001 Dr. Ed Thompson, MD, MPH Mississippi Department of Health P. O. Box 1700 Jackson, MS 39215-1700 NRC Senior Resident Inspector Grand Gulf Nuclear Station Port Gibson, MS 39150 G090016
G090016 Attachment To GNRO-2009/00016 List of Regulatory Commitments
Attachment to GNRO-2009/00016 Page 1 of 1 List of Regulatory Commitments The following table identifies those actions committed to by Entergy in this document. Any other statements in this submittal are provided for information purposes and are not considered to be regulatory commitments.
TYPE (Check one)
SCHEDULED ONE-CONTINUING COMPLETION COMMITMENT TIME COMPLIANCE DATE (If ACTION Required)
Entergy will follow the efforts of the Technical Within 6 Specification Task Force (TSTF) and NRC to months of finalize the details and scope of the changes approval of needed to resolve the instrument setpoint issue the TSTF discussed in RIS-2006-17. If the Condensate X
Traveler Storage Tank (CST) Level-Low setpoint is affected by the approved TSTF traveler, then Entergy will submit a separate amendment request to implement the approved generic change.
G090016