Nuclear Northeast Procedure Use Is:
Control Copy:
&1 Continuous 0 Reference 0 Information Effective Date:
Page 1 of 36 SUPPORT PR Approved By:
Team 2A Procedure Owner NEW PROCEDURE
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION NO: 2-OSP-27.6 Rev: 0 Page 2 of 36
NO: 2-OSP-27.6 Rev: 0 Page 3 of 36 SUPPORT PROCEDURE.
UNIT 2 APPENDIX r
R DIESEL GENERATOR OPERATION TABLE OF CONTENTS Section Title 1. 0 2.0 PRECAUTIONS AND LIMITATIONS.................................................................................
4 3.0 PREREQUISITES..............................................................................................................
5 4.0 PROCEDURE 6
Securing Line Up From Feeder 13W92...................................................................
6 Securing Line Up From Feeder 13W93...................................................................
7 PURPOSE.........................................................................................................................
4 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.1 0 4.1 1 Post Engine Run Line Up......................................................................................
16 4.12 Testing The SBO/APP R Diesel Generator In Unit Mode On 13W93....................
17 4.1 3 Lining Up 13.8KV Feeder 13W92 To The SBO/APP R BUS...................................
6 Lining Up 13.8KV Feeder 13W93 To The SBO/APP R Bus....................................
6 Preparing For Engine Start.....................................................................................
7 Normal Engine Start (Manual Mode).....................................................................
10 Normal Engine Start (Auto Mode).........................................................................
11 Diesel Generator Operation..................................................................................
12 Normal Engine Shutdown (Manual Mode)............................................................
15 Normal Engine Shutdown (Parallel Mode)............................................................
15 Manual Operations................................................................................................
25
5.0 REFERENCES
26 6.0 RECORDS AND DOCUMENTATION..............................................................................
26 Attachments ATTACHMENT 1 APPENDIX R DG DATA SHEET..........................................................
27 ATTACHMENT 2 WARNING AND SHUTDOWN FAULT CODES....................................
28 ATTACHMENT 3 APPENDIX R DG TROUBLESHOOTING PROCEDURES.................. 32
NO:
2-OSP-27.6 Rev: 0 Page 4 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION 1.0 PURPOSE 1.I This procedure establishes requirements for operation of the Unit 2 Appendix R Diesel Generator.
2.0 PRECAUTIONS AND LIMITATIONS 2.1 2.2 2.3 2.4 2.5 TRO 3.8.B applies in Modes 1,2, 3 and 4.
The Appendix R Diesel Generator maximum continuous load is 2045 kW. During an emergency, maximum generator load is 2435 kW.
Do NOT operate the engine less than 750 KW for long periods of time. Idling for a prolonged period of time (more than 30 minutes) can damage an engine.
Running with engine coolant temperature too low (below 140°F) will dilute crank case oil with raw fuel.
Crankcase oil level should only be checked using the lube oil reservoir gauge glass when the engine is running. Removing the engine oil fill cap or dipstick can allow hot oil to splash out.
Pushing the Emergency Stop button OR placing the O/Manual/Auto switch to the 0 position will cause an immediate engine shutdown (bypassing the cooldown at idle). This hot shutdown should be avoided, if possible, to prolong reliability of engine.
NO: 2-OSP-27.6 Rev: 0 Page 5 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION 3.0 PREREQUISITES 3.1 3.2 Lube Oil Supply Reservoir gauge glass level indicates between 3/4 and FULL.
The following Appendix R Diesel Generator Fuel Day Tank Indications are extinguished:
Tank Rupture System Fail Critical High High Fuel Low Fuel Pump 2 Fail Pump 1 Fail The Appendix R Diesel Generator Fuel Day Tank Level Gauge indicates between 7/8 and FULL.
3.3 NOTE -
When the system heats up and the coolant expands, the surge tanks should indicate between 2/3 and 314 full. This reserves 114 to 1/3 of the tank volume to accommodate system surges.
3.4 The following coolant surge tank levels are within range:
The Appendix R DG Auxiliary Transfer Switch is aligned to MCC 22 or Temporary AC Source as follows: (Appendix R DG Auxiliaries MCC) 3.5.1 3.5.2 Jacket Water Surge Tank level between 114 and 1/3 full (cold level)
After Cooler Surge Tank level between 114 and 1/3 full (cold level) 3.5 Source 1 Available (White Light Illuminated)
Source 1 Connected (Green Light Illuminated)
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION 4.0 PROCEDURE 4.1 Linina Up 13.8KV Feeder 13W92 To The SBO/APP R BUS
___ 4.1.I 4.1.2 REQUEST the CRS to refer to Technical Specification 3.8.1.
E the Appendix R DG will be paralleled to 13W92, THEN REQUEST the CCR to notify the SO.
4.1.3 ENSURE the following breakers are OPEN:
- MainGTBreaker
- GT25
- GT26
- 52GTlBT
- ASS
- SBOIASS 4.1.4 ENSURE the following breakers are CLOSED:
- SBOH
- SBOL
- OSP Securina Line UP From Feeder 13W92 4.2 -
4.2.1 ENSURE the following breakers are OPEN:
- SBOIASS
- SBOL SBOH Linina Up 13.8KV Feeder 13W93 To The SBOlAPP R Bus 4.3
__ 4.3.1 ENSURE the following breakers are OPEN:
- SBOIASS
- SBOH
__ 4.3.2 ENSURE breaker ASS is CLOSED.
NO: 2-OSP-27.6 Rev: 0 Page 6 of 36
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION 4.4 Securinq Line Up From Feeder 13W93
__ 4.4.1 ENSURE the following breakers are OPEN:
- SBOIASS
- ASS 4.5 Preparins For Enaine Start
__ 4.5.1 PERFORM any required test line up per test procedure.
NO: 2-OSP-27.6 Rev: 0 Page 7 of 36 NOTE Opening the Tool Room roll-up door may affect Centac operation. CCR permission is required prior to opening the Tool Room roll-up door.
The design maximum temperatures for the Unit 2 Appendix R DG are:
104°F for the electrical distribution equipment 122°F for the Diesel Generator air intake
__ 4.5.2 PERFORM the following as necessary to prevent exceeding design maximum temperatures:
___ 4.5.2.1 the Tool Room roll-up door will be opened, THEN REQUEST permission from the CCR to open the Tool Room roll-up door.
__ 4.5.2.2 ENSURE one of the following is open:
Elevation)
- The Maintenance Loading Bay overhead door (15' OR Tool Room roll-up door (1 5 'Elevation)
__ 4.5.3 ALIGN FOP-I 1, Fuel Oil Pump, as follows: (Fuel Oil Pump Room)
- CLOSE GT7-GT33, GTI-FOP-I 1 Discharge Stop.
- OPEN GTI-GT25, GTI-FOP-11 Discharge Test Connection Stop ROTATE Fuel Oil Folwarding Pump # I Manual Transfer Switch to the SBO/APP R DG Position. (Fuel Oil Pump Room)
ENSURE DF-152, Appx R Diesel Generator Day Tank Fuel Oil Return Valve, is OPEN.
Valve.
__ 4.5.4
___ 4.5.5
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION NO: 2-OSP-27.6 Rev: 0 Page 8 of 36
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION I
I I
NO: 2-OSP-27.6 Rev: 0 Page 9 of 36 CAUTION When aligning Service Water to supply cooling to the Appendix R DG Heat Exchangers, placing Service Water in service slowly ensures flow will NOT adversely affect the operation of the conventional Service Water header.
___ 4.5.12 E Service Water will be the cooling source, THEN ALIGN Service Water to the Appendix R DG as follows:
___ 4.5.12.1 OPEN SWT-837.
4.5.12.2 ADJUST Cooling Water flow as follows:
~
a)
THROTTLE UW-840 to achieve approximately 137 gpm as indicated by Fl-7980, Aftercooler Water Flow.
~
b)
THROTTLE UW-836 to achieve approximately 185 gpm as indicated by Fl-7979, Jacket Water Flow.
___ 4.5.13 E City Water will be the cooling source, 4.5.13.1 OPEN the following:
THEN ALIGN City Water to The Appendix R DG as follows:
___ a)
UW-854
___ b)
UW-855
___ 4.5.13.2 ADJUST Cooling Water flow as follows:
___ a)
THROTTLE UW-840 to achieve approximately 87 gpm as indicated by Fl-7980, Aftercooler Water Flow.
~
b)
THROTTLE UW-836 to achieve approximately 118 gpm as indicated by Fl-7979, Jacket Water Flow.
___ 4.5.14 E de-energizing the Appendix R DG Auxiliaries MCC, THEN OPEN the temporary AC Feed.
NO: 2-OSP-27.6 Rev: 0 Page 10 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION 4.6 Normal Enaine Start (Manual Mode)
NOTE -
There is no time delay when starting the engine in manual mode.
The default starting sequence is 3 start cycles, comprised of 10 seconds of cranking and 10 seconds of rest.
When the coolant reaches operating temperature completed, the generator will ramp up to rated speed and voltage.
the warm-up at idle time is 4.6.1 4.6.2 TURN the OlMANUALfAUTO switch to the MANUAL position.
4.6.3 PRESS AND RELEASE the Manual Run/Stop button.
ENSURE that Section 4.5, Preparing For Engine Start, has been performed.
NOTE The -\\- momentary pushbutton on Menu A of the Operator Panel is used to close and open breaker SBOIASS.
\\ indicates breaker SBO/ASS is open, PUSH to close
- indicates breaker SBO/ASS is closed, PUSH to open When using the -\\- momentary pushbutton, breaker SBO/ASS will close only when set-up conditions allow (i.e. dead bus OR generator synchronized with bus).
___ 4.6.4 E Manually closing breaker SBO/ASS, 4.6.5 CLOSE breaker SBO/ASS as follows:
THEN PRESS the Manual Close Button on the front of the Breaker.
__ 4.6.5.1 PRESS AND HOLD the -\\- momentary pushbutton until the symbol indicates --- (breaker SBO/ASS closed).
4.6.5.2 RELEASE the momentary pushbutton.
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION I
I I
NO: 2-OSP-27.6 Rev: 0 Page 11 of 36 4.7 Normal Engine Start (Auto Mode) -
NOTE The default crank starting sequence is 3 start cycles, comprised of 10 seconds of cranking followed by 10 seconds of rest.
There will be a delay of ten seconds from pressing the start button until the start of the engine to allow the operator to move away from the engine.
When the coolant reaches operating temperature completed, the generator will ramp up to rated speed and voltage.
the warm-up at idle time is 4.7.1
___ 4.7.2 PERFORM the following on the LCD display:
ENSURE that Section 4.5, Preparing For Engine Start, has been performed.
___ 4.7.2.1 SELECT CONTROL.
___ 4.7.2.2 SELECT START GENSET.
__ 4.7.3 CHECK the following:
__ 4.7.3.1 Engine starts
__ 4.7.3.2 Engine comes up to rated speed
___ 4.7.3.3 Generator synchronizes to the bus
___ 4.7.3.4 Generator picks up the nominal load
NO: 2-OSP-27.6 Rev: 0 Page 12 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION 4.8 Diesel Generator ODeration NOTE A fault that could result in engine damage causes an immediate engine shutdown.
All other faults allow the engine to run during the cooldown sequence before engine shutdown.
Warning alarms will NOT cause a shutdown, but may indicate abnormal operation.
__ 4.8.1 a Warning Condition occurs (Warning Status Indicator illuminates yellow),
THEN PERFORM the following:
___ 4.8.1.I IF the Alarm Module warning horn annunciated, THEN momentarily PUSH the PUSH TO SILENCE HORN button.
REFER to the following for assistance in correcting the condition:
4.8.1.2
- ATTACHMENT 2, WARNING AND SHUTDOWN FAULT
- ATTACHMENT 3, APPENDIX R DG CODES TROUBLESHOOTING PROCEDURES
___ 4.8.1.3 WHEN the condition is corrected, THEN the Warning Status Indicator may be reset as follows:
a)
PRESS FAULT ACKNOWLEDGE button. (front panel)
NO: 2-OSP-27.6 Rev: 0 Page 13 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION NOTE If a Shutdown Fault occurs while in AUTO, then STOP GENSET must be selected before the Shutdown Fault can be reset. The engine will restart automatically if the fault is reset prior to selecting STOP GENSET.
If a shutdown condition occurs, the Shutdown Status Indicator will illuminate red and the engine will shutdown immediately abnormal condition is sensed.
on a cooldown timer at any time an 4.8.2 E a shutdown condition occurs (Shutdown Status Indicator illuminates red),
THEN PERFORM the following:
__ 4.8.2.1 E the Alarm Module warning horn annunciated, THEN momentarily PUSH the PUSH TO SILENCE HORN button.
4.8.2.2 E in AUTO, THEN PERFORM the following:
____ a)
WHEN the engine stops, THEN PERFORM the following on the LCD display:
__ 1)
SELECTCONTROL.
- 2)
SELECT STOP GENSET.
4.8.2.3 REFER to the following for assistance in correcting the condition:
- ATTACHMENT 2, WARNING AND SHUTDOWN FAULT
- ATTACHMENT 3, APPENDIX R DG CODES TROUBLESHOOTING PROCEDURES
___ 4.8.2.4 PERFORM the following to reset the shutdown condition:
__ a) E the EMERGENCY STOP button was pressed, THEN PULL the EMERGENCY STOP button out b)
PLACE the OIMANUALIAUTO switch in 0.
c)
PRESS the front panel FAULT ACKNOWLEDGE button.
__ d)
PLACE the O/MANUAL/AUTO switch in AUTO
SUPPORT PROCEDURE
- UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION
__ 4.8.3 NO: 2-OSP-27.6 Rev: 0 Page 14 of 36 4.8.4
__ 4.8.5 4.8.6 4.8.7 IF desired to ALlGN the Appendix R DG Auxiliaries MCC to the Appendix R DG, THEN PERFORM the following:
4.8.3.1 CHECK the generator is at rated speed and voltage as indicated by the LCD display message.
ENSURE the Appendix R DG Auxiliary Transfer Switch is aligned as follows:
4.8.3.2
__ a)
CHECK Source 2 Available (Yellow Light illuminated).
PLACE the Appendix R DG Auxiliaries NORMALETANDBY switch in the NORMAL position (aligned to the Appendix R DG Output). (Appendix R DG Auxiliaries MCC) a)
CHECK Source 2 Connected (Red Light illuminated).
4.8.3.3 CHECK that the DG Area Fan is running.
ADJUST cooling water throttle valves to maintain normal cooling temperatures:
UW-836 UW-840 IF it is desired to adjust diesel generator load, THEN PERFORM the following:
4.8.6.1 SELECT Base Load using the arrow key from the UTILITY Menu.
ADJUST load as desired using the "+" or 'I-" keys.
4.8.6.2 IF it is desired to adjust diesel generator VARs, THEN PERFORM the following:
4.8.7.1 SELECT PF LEVEL using the arrow key from the UTILITY Menu.
ADJUST VARs as desired using the "+" or "-" keys.
4.8.7.2 4.8.8 RECORD Appendix R DG parameters if desired using ATTACHMENT 1, APPENDIX R DG DATA SHEET.
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION NOTE When the Appendix R DG Day Tank is operating in AUTO, the Appendix R DG Day Tank Level should be maintained between 7/8 and FULL.
NO: 2-OSP-27.6 Rev: 0 Page 15 of 36
___ 4.8.9 MONITOR Appendix R DG Day Tank Level.
____ 4.8.1 0 MONITOR Lube Oil Supply Reservoir gauge glass level
___ 4.8.10.1 E gauge glass level indicates less than 1/4 full, THEN REFILL Lube Oil Supply Reservoir with proper grade of oil (SAE 15W - 40).
4.8.1 1 CHECK the engine systems for leakage.
4.8.1 1.I leakage is observed, Normal Engine Shutdown (Manual Mode)
THEN INITIATE a WR as necessary.
4.9 -
4.9.1 REQUEST the CCR to notify the SO that the Appendix R DG will be unloaded.
E desired to transfer Appendix R DG Auxiliaries to MCC 22 or Temporary AC Power, THEN PERFORM the following:
__ 4.9.2
___ 4.9.2.1 ENSURE the Appendix R DG Auxiliary Transfer Switch is aligned as follows:
a)
CHECK Source 1 Available (White Light illuminated)
PLACE the Appendix R DG NORMAL/ STANDBY switch in the STANDBY position (aligned to MCC 22). (Appendix R DG Auxiliaries MCC)
___ 4.9.2.2
__ a)
CHECK Source 1 Connected (Green Light illuminated).
~
4.9.3 PRESS AND RELEASE the Manual RunlStop button.
__ 4.9.3.1 ENSURE breaker SBO/ASS is Open. (SBO/APP R Diesel 4.10 Normal Encline Shutdown (Parallel Mode)
Generator Switchgear)
__ 4.10.1 REQUEST the CCR to notify the SO that the Appendix R DG will be unloaded.
NO: 2-OSP-27.6 Rev: 0 Page 16 of 36 SUPPORT PROCEDURE
- UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION
__ 4.10.2 E desired to transfer Appendix R DG Auxiliaries to MCC 22 or Temporary AC Power, THEN PERFORM the following:
~
4.10.2.1 ENSURE the Appendix R DG Auxiliary Transfer Switch is aligned as follows:
___ a)
CHECK Source 1 Available (White Light illuminated).
PLACE the Appendix R DG NORMAL/ STANDBY switch in the STANDBY position (aligned to MCC 22). (Appendix R DG Auxiliaries MCC)
___ 4.10.2.2 a)
CHECK Source 1 Connected (Green Light illuminated).
NOTE The preset cooldown time (at rated speed) will vary dependent on the kW output.
The generator will stop after the cooldown at idle time is completed.
___ 4.10.2.3 PERFORM the following on the LCD display:
__ a)
SELECTCONTROL.
b)
SELECT STOP GENSET.
~
4.10.2.4 ENSURE breaker SBO/ASS is open. (SBO/APP R Diesel 4.11 Post Engine Run Line UP 4.11.1.1 RESTORE breaker line up using the applicable procedure section.
___ 4.1 1.1.2 PLACE the UNlTlPARALLEL switch in UNIT. (SBOIAPP R Switchgear 13.8KV Bus)
E the Appendix R DG Heat Exchangers are aligned to Service Water, THEN ALIGN the Appendix R DG Heat Exchangers to City Water as follows:
Generator Switchgear)
__ 4.1 1.I
.3 a)
CLOSE SWT-837 to secure Service Water flow.
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION
___ b)
OPEN the following:
__ 1)
UW-854
- 2)
UW-855
___ c)
ADJUST Cooling Water flow as follows:
- 1) THROTTLE UW-840 to achieve approximately 100 gpm as indicated by Fl-7980, Aftercooler Water Flow.
- 2)
THROTTLE UW-836 to achieve approximately 100 gpm as indicated by Fl-7979, Jacket Water Flow.
WAIT a minimum of 5 minutes for City Water to flush residual service water from the Appendix R DG Heat Exchangers and piping.
___ d)
____ 4.1 1.1.4 CLOSE the following to secure City Water to the Appendix R DG Heat Exchangers:
a)
UW-854
__ b)
UW-855 4.1 1.2 CLOSE DF-152, Appx R Diesel Generator Day Tank Fuel Oil Return valve.
___ 4.1 1.3 ALtGN FOP-I 1, Fuel Oil Pump, as follows: (Fuel Oil Pump Room)
CLOSE GTI-GT25, GTI-FOP-11 Discharge Test Connection Stop
- OPEN GTI-GT33, GTI-FOP-11 Discharge Stop.
___ 4.1 1.4 ROTATE Fuel Oil Forwarding Pump #I Manual Transfer Switch to the Turbine Auxiliary MCC 88TPX. (Fuel Oil Pump Room)
Valve.
___ 4.11.5 CLOSE the roll-up door previously opened.
___ 4.1 1.6 ENSURE the Lube Oil Supply Reservoir is refilled with the proper grade of oil (SAE 15W - 40).
4.12 Testinn The SBOlAPP R Diesel Generator In Unit Mode On 13W93
___ 4.12.1
___ 4.12.2 ENSURE that breaker GT/2F is racked out.
ENSURE the Unit 3 13.8 KVcircuit is being supplied by 13W92.
NO: 2-OSP-27.6 Rev: 0 Page 17 of 36
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION
~
__ 4.12.3 ENSURE that GT2 auxiliaries are transferred to their emergency supply (13W77) per 2-SOP-31.2.2, Gas Turbine 2 Local Operations.
___ 4.12.4 ENSURE that Assembly K has been transferred to emergency supply on 11 EC4.
4.12.5 ENSURE the TSC Bus 2 has been transferred to 13W92.
4.12.6 ENSURE the essential plant loads are supplied from 13.8KV L&P Buses 1,2 and 4.
___ 4.12.7 ENSURE Feeder 13W93 is aligned to e SBO/App R Bus per Section 4.3.
___ 4.12.8 ENSURE that Alternate Safe Shutdown System (ASSS) loads are ready to be started.
NO: 2-OSP-27.6 Rev: 0 Page 18 of 36 NOTE -
Opening the Tool Room roll-up door may affect Centac operation. CCR permission is required prior to opening the Tool Room roll-up door.
The design maximum temperatures for the Unit 2 Appendix R DG are:
104°F for the electrical distribution equipment 122°F for the Diesel Generator air intake
___ 4.12.9 PERFORM the following as necessary to prevent exceeding design maximum temperatures:
E the Tool Room roll-up door will be opened, THEN REQUEST permission from the CCR to open the Tool Room roll-up door.
__ 4.12.9.2 ENSURE one of the following is open:
___ 4.12.9.1
- Maintenance Loading Bay overhead door (15' Elevation)
OR Tool Room roll-up door (15 'Elevation)
__ 4.12.10 ALIGN FOP-I 1, Fuel Oil Pump, as follows: (Fuel Oil Pump Room)
- CLOSE GTI-GT33, GTI-FOP-11 Discharge Stop.
- OPEN GTI-GT25, GTI-FOP-11 Discharge Test Connection Stop Valve.
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION NO: 2-OSP-27.6 Rev: 0 Page 19 of 36
NO: 2-OSP-27.6 Rev: 0 Page 20 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION CAUTION When aligning Service Water to supply cooling to the Appendix R DG Heat Exchangers, placing Service Water in service slowly ensures flow will NOT adversely affect the operation of the conventional Service Water header.
Do NOT check lube oil level using the engine mounted dipstick while the generator set is operating. Crankcase pressure can blow out hot oil and cause severe burns.
4.12.18 E Service Water will be the cooling source, THEN ALIGN Service Water to the Appendix R DG as follows:
__ 4.12.18.1 OPEN SWT-837.
___ 4.12.18.2 ADJUST Cooling Water flow as follows:
~
a)
THROTTLE UW-840 to achieve approximately 137 gpm as indicated by Fl-7980, Aftercooler Water Flow.
~
b)
THROTTLE UW-836 to achieve approximately 185 gpm as indicated by Fl-7979, Jacket Water Flow.
4.q2.19 ECity Water will be the cooling source, THEN ALIGN City Water to the Appendix R DG as follows:
4.12.19.1 OPEN the following:
__ a)
UW-854
__ b)
UW-855 4.12.19.2 ADJUST Cooling Water flow as follows:
a)
THROTTLE UW-840 to achieve approximately 87 gpm as indicated by Fl-7980, Aftercooler Water Flow.
___ b)
THROTTLE UW-836 to achieve approximately 11 8 gpm as indicated by Fl-7979, Jacket Water Flow.
NO: 2-OSP-27.6 Rev: 0 Page 21 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION 1
I I
NOTE There is no time delay when starting the engine in manual mode.
The default starting sequence is 3 start cycles, comprised of 10 seconds of cranking and 10 seconds of rest.
When the coolant reaches operating temperature the generator will ramp up to rated speed and voltage.
the warm-up at idle time is done 4.12.20 TURN the O/MANUAL/AUTO switch to the MANUAL position.
4.12.21 PRESS AND RELEASE the Manual RunlStop button.
NOTE A fault that could result in engine damage causes an immediate engine shutdown.
All other faults allow the engine to run during the cooldown sequence before engine shutdown.
Warning alarms will NOT cause a shutdown, but may indicate abnormal operation.
___ 4.12.22 E a Warning Condition occurs (Warning Status Indicator illuminates yellow),
THEN PERFORM the following:
4.12.22.1 the Alarm Module warning horn annunciated, THEN momentarily PUSH the PUSH TO SILENCE HORN button.
4.12.22.2 REFER to the following for assistance in correcting the condition:
- ATTACHMENT 2, WARNING AND SHUTDOWN FAULT
- ATTACHMENT 3, APPENDIX R DG CODES TROUBLESHOOTING PROCEDURES
___ 4.12.22.3 WHEN the condition is corrected, THEN the Warning Status Indicator may be reset as follows:
___ a)
PRESS the front panel FAULT ACKNOWLEDGE button.
NO: 2-OSP-27.6 Rev: 0 Page 22 of 36 SUPPORT PROCEDURE
- UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION NOTE If a shutdown condition occurs, the Shutdown Status Indicator will illuminate red and the engine will shutdown immediately condition is sensed.
on a cooldown timer at any time an abnormal
~
4.12.23 a shutdown condition occurs (Shutdown Status Indicator illuminates red),
THEN PERFORM the following:
___ 4.12.23.1 E the Alarm Module warning horn annunciated, THEN momentarily PUSH the PUSH TO SILENCE HORN button.
__ 4.12.23.2 REFER to the following for assistance in correcting the condition:
- ATTACHMENT 2, WARNING AND SHUTDOWN FAULT
- ATTACHMENT 3, APPENDIX R DG CODES TROUBLESHOOTING PROCEDURES
___ 4.12.23.3 PERFORM the following to reset the shutdown condition:
a)
IF the EMERGENCY STOP button was pressed, THEN PULL the EMERGENCY STOP button out.
b)
PLACE the OlMANUAUAUTO switch in 0.
c)
PRESS the front panel FAULT ACKNOWLEDGE
__ d)
PLACE the O/MANUAL/AUTO switch in AUTO.
desired to ALIGN the Appendix R DG Auxiliaries MCC to the button.
__ 4.12.24 Appendix R DG, THEN PERFORM the following:
__ 4.12.24.1 CHECK the generator is at rated speed and voltage, as indicated by the LCD display message.
__ 4.12.24.2 ENSURE the Appendix R DG Auxiliary Transfer Switch is aligned as follows:
a)
CHECK Source 2 Available (Yellow Light illuminated).
NO: 2-OSP-27.6 Rev: 0 Page 23 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION
___ 4.12.24.3 PLACE the Appendix R DG Auxiliaries NORMAUSTANDBY switch in the NORMAL position (aligned to the Appendix R DG Output). (Appendix R DG Auxiliaries MCC)
___ a)
CHECK Source 2 Connected (Red Light illuminated).
4.12.25 CHECK that the DG Area Fan is running.
___ 4.12.26 ADJUST cooling water throttle valves to maintain normal cooling temperatures:
- UW-836
- UW-840
___ 4.12.27 RECORD Appendix R DG parameters if desired using ATTACHMENT 1, APPENDIX R DG DATA SHEET.
NOTE When the Appendix R DG Day Tank is operating in AUTO, the Appendix R DG Day Tank Level should be maintained between 7/8 and FULL.
__ 4.12.28 MONITOR Appendix R DG Day Tank Level.
___ 4.12.29 MONITOR Lube Oil Supply Reservoir gauge glass level.
___ 4.12.29.1 WHEN gauge glass level indicates less than 114 full, THEN REFILL Lube Oil Supply Reservoir with proper grade of oil (SAE 15W - 40).
__ 4.12.30 CHECK the engine systems for leakage.
___ 4.12.30.1 E leakage is observed,
__ 4.12.31 INFORM the CRS that Technical Specification, SA0 703 and ODCM Actions are applicable.
THEN INITIATE a WR as necessary.
NOTE The next step will de-energize 13.8KV L&P Bus 3.
___ 4.12.32 REQUEST the CCR notify the DO to open breaker F3-1.
__ 4.12.33 REQUEST the CCR obtain permission from the DO to energize feeder 13W93 from the Unit 2 Appendix R Diesel.
NO: 2-OSP-27.6 Rev: 0 Page 24 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION NOTE -
The -\\- momentary pushbutton on Menu A of the Operator Panel is used to close and open breaker SBO/ASS.
\\ indicates breaker SBO/ASS is open, PUSH to close
- indicates breaker SBO/ASS is closed, PUSH to open When using the -\\- momentary pushbutton, breaker SBO/ASS will close only when set-up conditions allow (Le. dead bus generator synchronized with bus.
4.12.34 CLOSE breaker SBO/ASS.
NOTE -
An announcement should be made prior to starting any equipment.
4.12.35 START the required ASSS loads
~
4.12.36 SECURE the ASSS loads.
NOTE The next step will de-energize 13.8KV L&P Bus 3.
4.12.37 REQUEST the CCR make an announcement that 13.8KV L&P bus 3 will be de-energized.
___ 4.12.38 OPEN breaker ASS.
4.12.39 REQUEST the CCR to restore 13.8KV L&P Bus 3.
4.12.40 SHUTDOWN the SBO/APP R Diesel Generator per Section 4.9, Normal Engine Shutdown (Manual Mode).
__ 4.12.41 RESTORE plant loads.
___ 4.12.42 PERFORM Section 4.1 1, Post Engine Run Line Up,
NO: 2-OSP-27.6 Rev: 0 Page 25 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION 4.13 Manual ODerations
__ 4.13.1 E desired to operate a breaker manually,
___ 4.13.1.1 Eclosing the breaker, THEN PERFORM the following:
THEN PERFORM the following:
___ a) the closing springs are discharged, b)
PRESS the Manual Close button.
THEN PRESS the manual Trip button.
manually CHARGE using the charging tool.
___ 4.13.1.2 E opening the breaker,
NO: 2-OSP-27.6 Rev: 0 Page 26 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION
5.0 REFERENCES
5.1 Commitment Documents 5.2 Development Documents 5.2.1 TRM 3.8.8 5.2.2 5.2.3 FSAR Chap. 8, Electrical Systems Operator's Manual, GenSet Model DQLA, DQLB, Cummins Power Generation 908-01 11 B, 07-2004 QSK78(DQLA,DQLB) Control System, PowerCommand Control 3200, Publication No 3550(GB) Issue 2 - Aug '04 Operator's Manual, PowerCommand 15 Amp @ 12 Volt and 12 Amp @
24 Volt Battery Chargers, Cummins Power Generation 901-0105C, 9-2006 FCM Fuel Control and Monitoring System, Detail Specifications, PYRCO, Inc.
FCM Controls & Level Settings Tank Serial Number - 453 9218, Tank Firmware Version: 01-05, PYRCO, Inc.
5.2.4 5.2.5 5.2.6 5.2.7 5.3 Interface Documents 5.3.1 2-COL-27.6, Unit 2 Appendix R Diesel Generator.
6.0 RECORDS AND DOCUMENTATION The following records are generated by this procedure and SHALL be maintained in accordance with IPEC Records Retention Schedule:
6.1 ATTACHMENT 1, APPENDIX R DG DATA SHEET
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION ATTACHMENT 1 APPENDIX R DG DATA SHEET (Page 1 of 1)
NO: 2-OSP-27.6 Rev: 0 Page 27 of 36 Date:
TIME/ READINGS PARAMETER Appendix R DG Engine Data Coolant Temperature "F
Lube Oil Pressure Psig Engine Speed 1800 RPM Battery Voltage Fuel Rail Pressure Pslg Fuel Pump Pressure Psig Fuel Inlet Temperature "F
Coolant Pressure PSQ Lube Oil Temperature "F
Lube Oil Level L1 Amps L2 Amps L3 Amps Appendix R DG Alternator Data 5 113 4 Amps 5 113 4 Amps 5 113 4 Amps Frequency 59 7-60 3 HZ Total kW 5 2700 kW Total kVA 5 3375 kVA Total PF PI-8030, Day Tank Fill Pump Pressure TE-8027, Day Tank Oil Cooler Temperature psig "F
314 - FULL 213 - 314 Lube Oil Reservoir Sight Glass Level LG-8032, Jacket Water Surge Tank Sight Glass Level LG-8031, After Cooler Surge Tank Sight Glass Level TI-908, Jacket Water Heat Exchanger Outlet Temperature TI-909 After Cooler Heat Exchanger Outlet Temperature 213 - 314 "F
"F 5 118 gpm 5 185 gpm 5 87 gpm 5 137 gpm Fl-7979, Appendix R DG Jacket Water Flow (City Water)
FI-7979, Appendix R DG Jacket Water Flow (Service Water)
Fl-7980, Appendix R DG Aftercooler Water Flow (City Water)
Fl-7980, Appendix R DG Aftercooler Water Flow (Service Water)
Normal range NOT specified by vendor.
"AS LEFT" minimum following completion of run.
NO 2-OSP-276 Page 28 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION ATTACHMENT 2 WARNING AND SHUTDOWN FAULT CODES (Page 1 of 4)
FlCURE 3-3 G R A P W A L DISPL&Y AH0 MEW SELECTION BUTTONS NOTE Fault codeslmessages will be displayed in the Description Line of the graphical display. (Refer to Figure 3-3 above)
The fault codes have been divided into four categories to help determine what corrective action to take for safe operation of the generator set. Use this Attachment to find the category (CTG) and fault description for all codes. Gaps in the code numbers are for codes that do NOT apply to this genset.
Category A Fault Codes: Pertain to engine or alternator shutdown faults that require immediate repair by qualified service personnel (generator set non-operational).
Control prevents the generator set from being restarted.
Category B Fault Codes: Consist of faults that can affect genset performance or cause engine, alternator, or connected equipment damage. Operate only when generator set is powering critical loads and c a n w be shut down. Requires repair by qualified service personnel.
Category C Fault Codes: Consist of faults that do NOT affect generator set performance but require qualified service personnel to repair. These codes indicate a defective harness or wiring problem.
These codes can also indicate a defective engine sensor, leaving no engine protectior (Engine damage can occur without detection). Continued operation may void generator set warranty if damage occurs that relates to fault condition.
Category D Fault Codes: Consist of faults that are repairable by site personnel.
Service will be required by qualified service personnel if site personnel c a n u resolve the problem after taking the corrective actions suggested in Attachment 3.
Category E Fault Codes: Indicates non-critical operational status of generator set, external faults, or customer fault inputs. May require repair by qualified service personnel
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION ATTACHMENT 2 WARNING AND SHUTDOWN FAULT CODES (Paae 2 of 4)
NO: 2-OSP-27.6 Rev: 0 Page 29 of 36 I CTG 1 CODE/ LAMP~ DISPLAYED MESSAGE I
A A
B 11 1 Shtdn Internal ECM error 11 2 11 3 Wrno Actuator sensor fault Shtdn Actuator NOT responding I
A I 115 I Shtdnl No speed signal I
A A
116 117 Shtdn I Time press sensor high Shtdn 1 Time press sensor low B
B C
118 Wrng Pump press sensor high 119 Wrng Pump press sensor low 121 Wrng No engine speed signal D I 197 I Wrng I Coolant level warning c I 212 I Wrno I oil temoerature sensor B
343 Wrng Internal ECM error C I 222 I WrngIAirpressuresensor A I 228 1 Shtdn I Low coolant oressure B
B C
C B
C I
C I 231 1 WrnaICoolant pressuresensor I
122 Wrng Manifold air press sensor 123 Wrng Manifold air press sensor 135 Wrng Oil pressure sensor 141 Wrng Oil pressure sensor 143 Wrng Low oil pressure 144 Wrna Coolant temperature sensor A I 234 I Shtdn I Overspeed 1
A A
A D I 235 I ShtdnI Coolant level alarm A I 236 I ShtdnI Position sensor 397 Wrng Fueling actuator #2 398 Wrng Fueling actuator #2 399 Wrna Fuelina actuator #2 C
1 263 I Wrng I Fuel temperature sensor C I 265 I Wrna I Fuel temoerature sensor D
I A I 266 I Shtdnl Fuel temperature I
441 Wrng I Low battery voltage 1
D I 326 I Wrna I Oil level warning I
D B
B 442 Wrng High battery voltage 449 Wrng High fuel supply pressure 451 Wrno Fuel rail oressure sensor I
1 A I 378 I Wrna 1 Fueling actuator # I C
A C
A 1 379 1 Wrng I Fueling actuator #1 A I 394 I Wrna 1 Fuelina actuator#l 213 Wrng Oil temperature sensor 214 Shtdn High oil temperature 221 Wrna Air Pressure sensor A I 395 I Wrng I Fueling actuator#l A I 396 I Wrno I Fueiino actuator #2 B
A B
452 Wrng Fuel rail pressure sensor 455 Shtdn Fuel control valve sensor 467 Wrna Timing rail act sensor B
B I 421 I WrnoI Hiohoil temoerature 415 I ShtdnI Low oil pressure alarm D I 471 Wrng Lowoil level 1
B 488 C
498 Wrng High intake manifold temp Wrng Oillevelsensor I
B I 482 I Wrna I Hiah fuel SUPP~V pressure I
c 1 499 I WrngIOillevelsensor A
1 514 I Shtdnl Fuel control valve 1
D I 253 I ShtdnI Oil level alarm
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION ATTACHMENT 2 WARNING AND SHUTDOWN FAULT CODES (Paqe 3 of 4)
NO: 2-OSP-27.6 Rev: 0 Page 30 of 36 CTG I CODE~ LAMP~ DISPLAYED MESSAGE I CTG A
A CODE LAMP DISPLAYED MESSAGE 1333 Shtdn Manual switch oor hi 1334 Shtdn Critical scaler oor B
B B
B 546 Wrng Fuel pressure sensor 547 Wrng Fuel pressure sensor 554 Wrng Fuel rail pressure sensor 555 Wrna Blowbypressure E
E E
1336 Shtdn Cooldown complete 1337 None Networkwink 1341 Shtdn Load demand stoo A
1343 Shtdn I Slot 1 card B
B B
689 Wrng Crank shaft sensor 719 Wrng Blowby pressure sensor 729 Wrna Blowbv oressure sensor A
C 1349 Shtdn Slot 7card 1351 Wrng Slot 4 I network enabled B
B B
C 1419 Wrng Fuel rail driver 1421 1422 1424 Wrna Hiah side driver Wrng Timing rail driver #1 Wrng Timing rail driver #2 B
C A
1319 Wrng High alternator temp 1321 Wrng Common warning driver 1322 Shtdn Load aov kW setpoint oor hi A
E 1323 Shtdn Load gov kW setpoint oor 10 1324 I Wrng Load gov kVAR oor hi B
B A
D B
A A
1325 Wrng Load gov kVAR oor lo 1326 Wrng Backup starter disconnect 1327 Shtdn Load gov kW analog oor 1328 Wrng Genset CB tripped 1329 1331 Shtdn AVR driver shorted 1332 Shtdn Manual switch oor lo Wrng AVR DC power failure I
B I 1335 1 Wrna I Non critical scaler oor I
A I 556 1 Shtdn I Blowby pressure A
1 586 I Shtdn I RunlStoo switch A I 587 I Shtdnl RunlStop switch I
D I 611 I Wrng I Engine hot D 1 688 1 Shtdnl Hiah oil level alarm I
A 1 1344 I Shtdnl Slot 2 card I
A A
I 1345 I Shtdnl Slot 3 card I 1346 I Shtdn I Slot 4 incorrect I
I A I 1347 I ShtdnI Slot 5 card I
778 A
I 1348 1 Shtdn] Slot 6 card Wrng Camshaft sensor Shtdn/ customer input #1 Wrng Shtdn Customer input #2
\\Almn 1311 1312 1313 Shtdni Network Fault 1 Wrng I
C I 1414 I Wrng I Run relay contact I
1314 1315 1316 1317 hidnil Network Fault 2 Wrng I
C I 1415 I Wrng 1 Run relay driver I
Shtdni/ Network Fault 3 Wrng I
D 1 1416 1 Wrng IFail toshutdown I
I D I 1417 I Wrng/ Power down error I
1318 Wrnn C
C I 1427 I Wrng I Overspeed relay driver 1 1428 I Wrng 1 LOP shutdown. relay driver I
D 1 1433 I Shtdn I Emeraencv stop - local I
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION ATTACHMENT 2 WARNING AND SHUTDOWN FAULT CODES (Pase 4 of 4)
NO: 2-OSP-27.6 Rev: 0 Page 31 of 36 I CTG I CODE~ LAMP~ DISPLAYED MESSAGE I CTG CODE A
1473 A
1474 LAMP DISPLAYED MESSAGE Shtdn Watchdog failure Shtdn Software version mismatch 1 ;
1 1455 1 Shtdnl Uti1 CB contact __
I 1456 Wrng Bus out of range D
A B
1 E I 1457 I Wrnq 1 Fail to synchronize I
1442 Wrng Battery is weak 1443 Wrng Batteryisdead 1444 Wrno kwoverload E I 1458 I Wrng I Phase rotation A I 1459 I ShtdnI Reverse kW C
C 1492 1493 Wrng 1 Load dump relay driver Wrng I Display control driver I
E 1 1465 1 None 1 Ready to load I
A B
E E
C I 1466 I Wrng I Modem failure C I 1467 I Wrno I Unable to connect modem 1461 Shtdn Loss offield 1462 Wrng High ground current 1463 None W i n A u t o 1464 None Loaddump C
B A
21 12 Wrng Aftercooler temp sensor 2113 Wrng High aftercooler temp 2114 Shtdn Hioh aftercooler temo I
C 1 1475 1 Wrna I First start backup I
C B
A 1468 Wrng Network erorr 1471 Wrng High current 1472 Shtdn Overcurrent 1494 Wrng Modem power relay drlver b & k a k n - s h u t d o w ; 2 driver 1
C I 1496 I Wrna I Auto mode relay driver I
I C
C 1 1497 I Wrng I Manual run LED driver I 1498 I Wrno I Exercise run LED driver 1
C 1499 Wrng I Remote start LED driver C
21 1 1 I Wrng I Aftercooler temp sensor I
I I
I I
I I
I I
I I
I I
I I
NO: 2-OSP-27.6 Rev: 0 Page 32 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION ATTACHMENT 3 APPENDIX R DG TROUBLESHOOTING PROCEDURES (Page 1 of 5)
WARNING Many troubleshooting procedures present hazards which can result in severe personal injury or death. Only qualified service personnel with knowledge of fuels, electricity and mechanical hazards should perform service procedures. Review safety precautions SYMPTOM CODE: 146 LAMP: Warning MESSAGE:
HIGH COOLANT TEMP WARNING CODE: 151 LAMP: Shutdown MESSAGE:
HIGH COOLANT TEMP ALARM CORRECTIVE ACTION Indicates engine has begun to overheat and jacket Nater coolant temperature has risen to an Jnacceptable level. If generator is powering non-xitical and critical loads and c a n m be shut down, Jse the following:
A.
Reduce load if possible by turning off non-critical loads.
B. Check air inlets and outlets and remove any obstructions to airflow.
- c. If engine can be stopped, follow 151 High Coolant Temp Alarm procedure.
indicates engine has overheated Jacket water 3oolant temperature has risen above the shutdown trip point or the coolant level is low. Allow engine to 3001 down completely before proceeding with the
'ollowing checks:
A. Check jacket water coolant level and replenish if low. Look for coolant leakage and repair if necessary.
B. Check for obstructions to cooling airflow and correct as necessary.
C. Check fan belt and repair if necessary.
D. Reset control and restart after locating and correcting problem.
NO: 2-OSP-27.6 Rev: 0 Page 33 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION ATTACHMENT 3 APPENDIX R DG TROUBLESHOOTING PROCEDURES (Page 2 of 5)
SYMPTOM
>ODE: 152 AMP: Warning MESSAGE:
-OW COOLANT TEMP
>ODE: 197
-AMP: Warning MESSAGE:
2OOLANT LEVEL WARNING SODE: 235
-AMP: Shutdown MESSAGE:
SOOLANT LEVEL ALARM
>ODE: 253
_AMP: Shutdown MESSAGE:
31L LEVEL ALARM CORRECTIVE ACTION Indicates engine coolant heater is NOT operating or is NOT circulating coolant. Set is in standby mode but is NOT operating. Warning occurs when engine jacket water coolant temperature is 70" F (21" C) or lower.
NOTE: In applications where the ambient temperature falls below 40" F (4" C), Low Coolant Temp may be indicated even though the coolant heaters are operating.
Check for the following conditions:
A. Coolant heater NOT connected to power supply. Check for blown fuse or disconnected heater cord and correct as required.
B. Check for low jacket water coolant level and replenish if required. Look for possible coolant leakage points and repair as required.
Indicates engine jacket water coolant level has fallen to an unacceptable level. If generator is powering critical loads and c a n g be shut down, wait until next shutdown period, then follow 235 Coolant Level Alarm procedure. If engine can be stopped, follow 235 procedure.
Indicates engine jacket water coolant level has fallen below the alarm trip point. Allow engine to cool down completely before proceeding.
A. Check jacket water coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary.
B. Reset control and restart after locating and correcting problem.
Indicates engine oil level has dropped below the shutdown trip point. Check oil level, lines and filters.
If oil system is OK but oil level is low, replenish.
Reset control and restart.
SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION ATTACHMENT 3 APPENDIX R DG TROUBLESHOOTING PROCEDURES (Page 3 of 5)
NO:
2-OSP-27.6 Rev: 0 Page 34 of 36 SYMPTOM
,ODE:
326
-AMP: Warning MESSAGE:
31L LEVEL WARNING
- ODE: 359
-AMP: Warning MESSAGE:
ENGINE FAILED TO START
>ODE: 441
-AMP: Warning MESSAGE:
-OW BATTERY VOLTAGE 30DE: 442
.AMP: Warning MESSAGE:
iIGH BATTERY VOLTAGE CORRECTIVE ACTION Indicates that the engine oil level has exceeded the warning trip point for high oil level. If generator is powering critical loads and c a n m be shut down, wait until next shutdown period, then follow 688 High Oil Level Alarm procedure. If engine can be stopped follow 688 procedure.
Indicates possible fault with control or starting system. Check for the following conditions:
A. Poor battery cable connections. Clean the battery cable terminals and tighten all connections.
B. Discharged or defective battery. Recharge or replace the battery.
A. Discharged or defective battery. Check the battery charger fuse.
B. Recharge or replace the battery. Poor battery cable connections. Clean the battery cable terminals and tighten all connections.
C. Check engine DC alternator. Replace engine DC alternator if normal battery charging voltage (24 to 26 VDC) is NOT obtained.
D. Check float level if applicable (raise float level).
Indicates battery voltage is below 24 VDC.
Indicates battery voltage exceeds 32 VDC Check float level on battery charger if applicable (lower float level)
Check engine DC alternator. Replace engine DC alternator if normal battery charging voltage (24 to 26 VDC) is NOT obtained.
E SHOOTING PROCEDURES MESSAGE:
LOW OIL LEVEL CODE: 61 1 LAMP: Warning MESSAGE:
ENGINE HOT CODE: 688 LAMP: Shutdown MESSAGE:
HIGH OIL LEVEL ALARM CODE: 1311 through 1318 LAMP: ShutdownNVarning MESSAGE:
Customer Defined Fault CODE: 1416 LAMP: Warning MESSAGE:
FAIL TO SHUTDOWN CODE: 1417 LAMP: Warning MESSAGE:
POWER DOWN ERROR CODE: 1433l1434 LAMP: Shutdown MESSAGE:
EMERGENCY STOP - LOCAL I EMERGENCY STOP - REMOTE Of 5)
CORRECTIVE ACTION Indicates en dropped to an unacceptable level. If gen ing critical loads and c a n u be t until next shutdown period, then follow 253 Oil level Alarm procedure. If engine can be stopped follow 253 procedure.
Indicates that an engine hot shut down has occurred (cooldown timers were bypassed). This condition will occur when the engine coolant temperature is above the normal operating level and the operator presses the Emergency Switch or moves the OlManuallAuto switch to the 0 (Off) position. This type of shutdown should be avoided. Can cause possible loss of performance and engine damage.
Indicates that the engine oil level has exceeded the alarm trip point for high oil level. Check oil level.
Drain oil to operating level.
When anyone of these customer defined inputs is detected by the control, the corresponding fault message is displayed. The nature of the fault is an optional customer selection. These fault functions can be programmed to initiate a shutdown or warning as indicated by the Warning or Shutdown lamp.
Note: Customer fault messages are editable. The message displayed for the code shown (131 1 through 1318) is determined by the customer.
Status - indicates that the "Fault Bypass" mode is enabled. This mode is primarily used by service personnel for troubleshooting purposes. In this mode the generator set ignores the majority of system shutdown faults.
Indicates that the control can NOT power down due to some unknown condition. Possible drain on battery. Contact an authorized service center for service.
Indicates local or remote Emergency Stop.
Emergency Stop shutdown status can be reset only at the local control panel.
To reset the locallremote Emergency Stop button:
Pull the button out.
Move the O/Manual/Auto switch to 0 (off).
Press the front panel Fault Acknowledge button.
Select Manual or Auto, as required.
NO:
2-OSP-27.6 Rev: 0 Page 36 of 36 SUPPORT PROCEDURE - UNIT 2 APPENDIX R DIESEL GENERATOR OPERATION APPENDIX R DG TROUBLESHOOTING PROCEDURES (Page 5 of 5)
SYMPTOM CODE: 1438 LAMP: Warning MESSAGE:
FAIL TO CRANK CODE: 1439 LAMP: Warning MESSAGE:
FUEL LEVEL LOW IN DAY CODE: 1441 LAMP: Warning MESSAGE:
FUEL LEVEL LOW IN MAIN CODE: 1442 LAMP: Warning MESSAGE:
BATTERY IS WEAK CODE: 1443 LAMP: Warning MESSAGE:
CORRECTIVE ACTION Indicates possible fault with control or starting system. Check for the following conditions:
A. Poor battery cable connections. Clean the battery cable terminals and tighten all connections.
B. Discharged or defective battery. Recharge or replace the battery.
Indicates fuel supply is running low. Check fuel supply and replenish as required.
Indicates fuel supply is running low. Check fuel supply and replenish as required.
Indicates battery voltage drops below 14.4 volts for two seconds, during starting. Discharged or defective battery.
See Warning message 441 Low Battery Voltage.
Indicates battery has dropped below genset operating range (3.5 volts when cranking) to power the starter and the control circuitry.
See Warning message 441 Low Battery Voltage.